Comparison
Three-phase motor on two phases with a capacitor leg
Short answer
Wiring a three-phase motor to two live supply phases is single-phasing: weak or absent starting torque and two windings carrying all the current. A capacitor-generated third leg turns the motor but delivers roughly below 80% of normal three-phase power, with balance that drifts as the load moves. The permanent fix is a VFD whose manual explicitly allows single-phase input, sized to the motor's nameplate full-load current.

On this page
- What two live phases do to the motor
- What the capacitor leg actually delivers
- The three options side by side
- Worked example: measuring the leg against the NEMA limit
- The permanent fix: a VFD documented for single-phase input
- Before you restart: safety, protection and motor checks
- The decision
- Questions asked
Wiring a three-phase motor across two live supply legs is not a usable two-phase mode — it is single-phasing, and the motor pays for it in overheated windings and stalled starts. The capacitor trick common on pump panels does turn the shaft, but it does not rebuild a real third phase: plan on roughly below 80% of the motor's normal three-phase power, with balance that drifts as the load moves. The decision splits three ways. Two live phases with the third open: reject it, and stop the motor when a phase is lost. A capacitor-generated leg: temporary only, derated and verified by measurement. Permanent service: a VFD whose manual explicitly allows single-phase input, sized to the motor's nameplate full-load current.
What two live phases do to the motor #
Three phase currents, each displaced 120 electrical degrees, build the rotating field that drags the rotor around. Open one line and the field collapses toward a single pulsating component. A motor at rest has almost no starting torque in that state: it hums, draws locked-rotor current on the two remaining lines, and stalls under anything but the smallest load. A motor already spinning keeps turning, because the rotor's motion sustains torque from the field components that are left — which is exactly why continued rotation proves nothing about current or temperature.
The damage is a current problem before it becomes a temperature problem. With balanced voltages each winding carries the same current, and a small voltage unbalance produces a disproportionately larger current unbalance, so one or two windings run hot while an average-current reading can still look acceptable. NEMA MG 1, the motors-and-generators standard, treats voltage unbalance up to 1% as the condition for full rated output, requires derating above that, and calls anything over 2% unacceptable for continuous service; use the edition your motor documentation cites. Where that imbalance shows up in the rest of the installation is covered in this page on single-phasing voltage imbalance and its system effects.
Protection has to see the fault as well: use an overload device that monitors all three lines. A starter watching only two can miss a delta-connected winding that is quietly overloaded while the monitored lines look normal.
What the capacitor leg actually delivers #
A capacitor tapped from one healthy line and feeding the open terminal shifts that line's current by close to 90 degrees, so the motor sees a synthesized third leg. It is not a utility phase. The leg's voltage is current through a reactance feeding a motor whose impedance changes with speed and slip, so the leg voltage moves with shaft load, and the balance tuned at one duty point does not hold at another.
Static converter practice puts usable shaft power at roughly below 80% of the motor's normal three-phase rating, and that assumes the network is tuned to the actual duty point. Treat the figure as a ceiling on the load you may connect, not as a rating the motor keeps. A submersible pump makes the picture harsher: the motor depends on water flow for cooling, and a long drop cable adds voltage drop on exactly the weakest leg.
There is no nameplate microfarad value to copy, because the right capacitance depends on that same motor impedance and load. Pick it by measurement: trim the network until the three line currents sit closest together at the real duty point, and recheck whenever the load changes. Adding capacitance to chase a weak leg does the opposite of fixing the balance — it is the same mechanism that overheats a static phase converter motor when more run capacitance is added.
If the motor has already spent time on a two-phase-plus-capacitor supply, check it for damage before trusting it again; the practical checks are laid out in this guide to troubleshooting induction motor single-phasing risks.
The three options side by side #
| Supply method | Starting and running behavior | Motor risk | Decision |
|---|---|---|---|
| Two live phases, third open | Almost no starting torque under load; a spinning motor keeps turning on two windings with heavy current unbalance | Winding burnout that a two-line starter can miss | Reject; stop the motor on phase loss and add phase-failure protection |
| Capacitor-generated third leg | Starts and runs when the network suits the load; torque, leg voltage and balance all move with load | Overheated winding or capacitor once the load leaves the tuned point; power capped at roughly below 80% of three-phase | Temporary only; derate, measure currents at the duty point, watch temperature |
| VFD documented for single-phase input | Controlled soft start, adjustable speed, balanced output | Low, when the drive is sized from nameplate current and the motor data is entered correctly | The permanent fix |
Worked example: measuring the leg against the NEMA limit #
Measure line-to-line voltage at the motor terminals with the load running at its real duty point, because the leg voltage sags as the load grows. Example inputs, chosen to show the arithmetic: 248 V, 236 V and 229 V measured on a 240 V-class system with a capacitor leg.
NEMA MG 1 defines percent voltage unbalance as the largest deviation from the average line-to-line voltage, divided by that average, times 100:
- Average = (248 + 236 + 229) / 3 = 713 / 3 = 237.7 V
- Largest deviation = 248 − 237.7 = 10.3 V
- Unbalance = 100 × 10.3 / 237.7 = 4.3%
4.3% is more than double NEMA MG 1's 2% unacceptable line, so this supply cannot carry the motor's rated load: the load has to come down well below the plate, and no reading that high supports continuous duty. Check the result against the motor documentation and, for the installation requirement, the local authority having jurisdiction. Measure the three line currents at the same time and apply the same formula; the winding with the highest current is the one heating. Because the leg voltage recovers when the load drops, a reading taken unloaded flatters the arrangement — always measure at the duty point.
The permanent fix: a VFD documented for single-phase input #
A VFD converts whatever the input gives it into a DC bus and rebuilds three clean phases from that bus, so the motor sees balanced output regardless of the missing phase — soft start, adjustable speed and real overload protection included. What the drive does not do is forgive an input connection its manual forbids. Feeding two terminals of a three-phase-input rectifier forces the remaining legs and the DC-bus capacitors to carry higher ripple current; some manufacturers document exactly that connection with a larger frame or reduced continuous output required, and others prohibit it. The manual decides, and the permitted supply configurations and ratings sit in the drive data governed by IEC 61800-5-1, the safety standard for adjustable-speed drive systems.
Size by current, not horsepower: the permitted continuous output current must meet or exceed the motor's nameplate full-load current at the motor's voltage. A 5 hp, 230 V motor with a 14.8 A nameplate, for example, needs at least 14.8 A of permitted continuous output — that nameplate current is an example, so read your plate. The full walk-through is in sizing a VFD for a three-phase motor on single-phase input, and the input wiring itself in wiring the drive's R, S and T input from a 240 V single-phase supply.
One step is non-negotiable: remove the phase-shifting capacitor network from the motor circuit before the drive ever outputs. Capacitors on a PWM output draw sharp current spikes, destroy themselves and corrupt the drive's current measurement.
Before you restart: safety, protection and motor checks #
NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, sets the work practices: de-energize, lock out and verify the absence of voltage before you open the panel, the motor terminal box or the drive, and confirm the requirement with your local authority having jurisdiction and the equipment documentation.
With the circuit dead and verified:
- Record every nameplate value first, and set the overload from the nameplate full-load current, as covered in setting overload relays from motor nameplate full-load current.
- Measure winding resistance phase to phase at the terminal box. Comparable readings support continuity; a clearly higher reading points to a damaged winding or a burnt joint from the earlier two-phase running.
- Test insulation resistance with a 500 V DC megohmmeter, judged against IEEE 43 and the motor manufacturer's limit, with the drive disconnected from the circuit under test.
- Confirm the driven load turns freely, then give the motor a brief low-speed command to verify direction; swap two output leads only with the drive stopped and locked out.
The decision #
- Two live phases, no converter: reject. A stopped motor will not start under load, and a running motor is cooking its windings; on any fixed installation add phase-failure protection so the motor stops itself.
- Capacitor leg: temporary, derated, measured. Keep the load well below the plate — roughly below the 80% ceiling at best — re-measure unbalance and line currents at the duty point, and treat any reading above NEMA's line as an order to shed more load. Watch winding temperature, and do not call the arrangement continuous duty.
- Permanent service: a VFD whose manual explicitly allows single-phase input, sized to the nameplate full-load current, with the capacitors removed from the motor circuit and the overload set from the plate. Of the three options, only that one delivers rated motor life.
Questions asked
Can a three-phase motor start under load on a capacitor-generated leg?
Usually not reliably. The artificial leg's voltage sags hardest exactly when the motor draws locked-rotor current, so starting torque falls sharply; pumps and compressors that need breakaway torque may hum, jerk or stall. Start the motor unloaded or lightly loaded and expect weak acceleration. That limitation, more than the reduced running power, is what marks the capacitor arrangement as temporary.
Can a standard three-phase-input VFD run on single-phase input if I feed only two terminals?
Only if the manual for that drive and frame explicitly allows the connection. Some manufacturers document a single-phase input and require the next-larger frame or a reduced continuous output, because the rectifier and DC-bus capacitors see higher ripple current. Others prohibit it outright. The manual decides, not the terminal layout.
Is a rotary phase converter better than a capacitor leg for continuous duty?
Yes, generally. A rotary converter uses an idler motor to generate a genuinely rotating field, so the third-leg voltage holds steadier as the load changes and the driven motor can work closer to its nameplate rating than on a static capacitor arrangement. It still needs measured balance and correct three-phase overload protection, and a single-phase-input VFD remains the cleanest permanent fix.
How do you choose the capacitance for the third leg?
There is no plate value to copy: the right capacitance depends on the motor's impedance, speed and the actual load, so it is chosen by measurement. Adding capacitance to chase a weak leg pushes winding current up rather than down.
Does single-phasing damage a motor that keeps turning?
Yes. Continued rotation comes from the rotor's own motion, while the load current crowds into the remaining windings; a small voltage unbalance becomes a much larger current unbalance, so the hottest winding can hide behind a normal-looking average reading. NEMA MG 1 puts the voltage-unbalance limit for continuous rated service at 2%, and a motor run beyond it must be derated or taken off that supply.
