What a solid-state phase converter does for a 5 HP motor
Short answer
For a 5 HP, 220/240 V three-phase motor that never changes speed, a fixed-output solid-state phase converter is the no-frills answer: no idler, no capacitors to tune, no keypad. Size the unit on its continuous output amps — at least the motor's 15.2 A at 230 V — and on its published single-phase input current, about 21 A in the worked example, then protect the input at 125 percent of that current under NEC Article 455.

On this page
- Can you buy a converter that is only a converter?
- How is it different from a rotary or static converter?
- Why does a badly balanced third leg cook the motor?
- What size converter does a 5 HP motor need?
- What breaker and conductors does the input circuit need?
- How do you wire and commission it without surprises?
- When is a VFD the better answer instead?
- Questions asked
A 5 HP, 220/240 V three-phase motor that never changes speed does not need an idler motor, a capacitor bank or a keypad. A fixed-output electronic phase converter — solid-state, no parameters, no display — takes 220 V single phase in and synthesizes three regulated legs out, so the machine's own start button works exactly as it did on a utility three-phase supply. This article compares the electronic unit with the static and rotary options, works the input-current and conductor sizing with real numbers, and ends with a decision for each case: the electronic converter for fixed speed, a VFD only when the speed may ever need to change.
Can you buy a converter that is only a converter? #
Yes. A fixed-output electronic phase converter takes 220 V single phase in and synthesizes three balanced legs out at the motor's voltage, with no keypad, no parameters and no speed control — for a 5 HP, 220/240 V three-phase motor at fixed speed, it is the direct answer.
Inside the box the single-phase supply is rectified to a DC bus, and switching power stages rebuild the three output legs at the correct amplitude and 120-degree spacing. Regulation runs continuously, so the output holds its balance as the load swings — the one property neither a capacitor bank nor an idler motor gives you without tuning. The idea is not new: a 5 hp solid-state prototype was completed in the early 1990s, and the class has been a catalog item ever since, with current listings aimed at compressors, pumps, saws and fans in exactly this size class, running from shop single-phase service. What the unit leaves out is everything a VFD does besides convert: no speed trim, no ramp, no fault menu to learn. For one motor at one speed, that is the point.
How is it different from a rotary or static converter? #
The three legacy options differ in how they make the third leg and how balanced it stays under load; only the electronic converter regulates all three legs, and only the VFD adds speed control you do not need.
| Option | How the third leg is made | Interface | Balance under load | Fit for a fixed-speed 5 HP machine |
|---|---|---|---|---|
| Static converter | Capacitors assist the start; the leg stays capacitor-derived | The machine's own switch | Worst; the motor runs derated | Starts the motor, but not at full torque |
| Rotary converter | A spinning idler motor generates it | The machine's own switch | Good, drifts with load and tuning | Works, but adds a spinning machine, noise and idle losses |
| Fixed-output electronic converter | Power electronics rectify the supply and resynthesize all three legs | The machine's own switch | Regulated as the load moves | The no-frills match |
| VFD on single-phase input | The same power electronics, output at variable frequency | Keypad and parameters | Regulated | Works, but brings speed control and settings you may not need |
Two notes on the legacy rows. A static converter leaves the motor on two true phases plus a capacitor-derived leg after the start, which derates the machine — the same mechanism behind why a static phase converter struggles even on small pump motors. A rotary converter does the job properly, but the idler spins whenever you need three-phase, and that continuous appetite is why a rotary phase converter idles at such high current. The electronic unit has neither an idler to spin nor a start or run capacitor bank to tune.
Why does a badly balanced third leg cook the motor? #
Unequal leg voltages drive a negative-sequence field that turns against the rotor, and because the motor's negative-sequence impedance is small, a 2 percent voltage imbalance can turn into a current imbalance six to ten times larger — heat the windings must shed.
An induction motor makes torque from one rotating field. Unequal leg voltages or phase angles off the 120-degree mark add a negative-sequence field rotating against the rotor, cutting torque and driving circulating currents through the windings. A motor's negative-sequence impedance sits near its locked-rotor impedance, which is why the current imbalance lands an order of magnitude above the voltage imbalance; NEMA MG-1, the motors-and-generators standard, publishes a derating curve on exactly that basis, applying from about 1 percent voltage imbalance. In the shop this reads as one leg running hot, a hum under load and nuisance trips on the overload relay.
A regulating electronic converter attacks the mechanism itself: it holds the three line-to-line voltages close to equal while the load moves. Balance is also the reason converted three-phase keeps a machine running only while leg voltages stay balanced, which guide to converted three-phase and leg voltage balance explains in detail. Static and rotary banks hold balance by tuning; this one holds it by control.
What size converter does a 5 HP motor need? #
Size it twice: output side, a continuous rating of at least the motor's 15.2 A nameplate full-load current; input side, the converter's published single-phase input current sets the whole supply.
Output side first. NFPA 70, the National Electrical Code, 2023 edition, Table 430.250 lists 15.2 A of full-load current for a 5 HP, 230 V three-phase motor; use the nameplate value when your motor differs, and compare amps rather than the horsepower label, because an HP rating assumes a typical motor. Starting is the second demand: across the line, a NEMA Design B motor of this size draws roughly six times full-load current — about 90 A here — for well under a second, so the converter's documented starting capability must cover that surge, or the unit trips the moment the machine's start button is pressed.
The supply is sized from the converter, not the motor: the nameplate carries a rated input current and that figure governs. To see the order of magnitude before ordering, work an example:
Input current = shaft power ÷ (input voltage × efficiency × power factor)
Illustrative inputs: shaft power 5 HP = 5 × 746 W = 3,730 W; input voltage 230 V single phase (the nominal middle of a 220–240 V service); combined motor-plus-converter efficiency 0.85; power factor 0.9.
Input current = 3,730 W ÷ (230 V × 0.85 × 0.9) = 3,730 W ÷ 175.95 ≈ 21.2 A
The nameplate number overrides the estimate, because it already includes the converter's real losses and power factor. Every downstream decision — branch conductors, breaker, disconnect — hangs off that input current, not off the motor's running current.
What breaker and conductors does the input circuit need? #
NFPA 70, the National Electrical Code, 2023 edition, Article 455 requires conductors supplying a single-phase converter to have an ampacity of at least 125 percent of its rated input current — for the 21.2 A example, 26.5 A of conductor, a 30 A breaker and 10 AWG copper.
Run the arithmetic with the example input current: 21.2 A × 1.25 = 26.5 A of minimum conductor ampacity. In the same code, Table 310.16 gives 10 AWG copper 35 A in the 75 °C column, which carries the load with margin, while 12 AWG at 25 A does not. The next standard overcurrent device size above 26.5 A is 30 A, per NEC 240.6(A). If the converter's nameplate input current differs from the example, put that nameplate number through the same two steps — the rule follows the nameplate, not my illustrative inputs.
The breaker must also survive a fault, not just carry load: its interrupting rating has to match the available fault current at the panel and the published duty a circuit breaker's fault rating must be tested for. Confirm the branch-circuit details with your authority having jurisdiction and the converter's installation manual; local amendments and the unit's listing settle the final numbers.
How do you wire and commission it without surprises? #
Wire the single-phase supply and ground to the converter input, three conductors onward to the motor, leave the machine's own contactor and overload relay in place at nameplate full-load current, and verify the three output voltages before the motor ever spins.
- De-energize the supply, lock it out and verify absence of voltage at the converter terminals before opening anything — this step precedes every procedure below that opens a terminal box.
- Read the motor nameplate for voltage, full-load current and connection, and set the lead links for the 220/240 V arrangement, not the 460 V one.
- Land the two single-phase hots and the equipment grounding conductor on the converter input; run three output conductors to the starter or motor; never land an output conductor on a neutral or ground bar.
- Keep the machine's contactor and thermal overload in circuit, with the overload set to the nameplate full-load current.
- Energize with the motor leads open and measure the three line-to-line output voltages, comparing the spread against the tolerance the converter's manual states.
- Reconnect the motor, start it unloaded and clamp all three line currents, then repeat at working load; imbalance that appears only under load points at regulation, not at the motor.
- If rotation runs backward, swap any two output conductors at the motor — locked out again first.
- A generated leg that shows voltage but carries no current under load has a recognizable pattern, and diagnostics for a solid-state phase converter with no amps on its generated leg walk through it.
When is a VFD the better answer instead? #
Choose a VFD instead when the load may ever need soft starting, controlled deceleration, reversing or a speed change; it also turns single phase into three phase, at the price of a parameter set and a derating exercise on its single-phase input.
Decide on the load, not on the technology. Fixed speed, the machine's own controls, nothing to program — the dedicated electronic converter is the right tool, and the sizing above applies as written. The moment the load wants a soft ramp, a controlled stop, reversing or a speed trim, the converter is the wrong tool and the VFD is right; on a single-phase input a VFD must be sized so its output current covers the motor within the input's limit, which is the whole job in sizing a VFD for a three-phase motor on single-phase input.
One last differentiator: decelerating loads push energy back toward the supply. Some electronic converters are documented to pass that regenerated energy out to the line; treat that as a model-specific feature to confirm in the manufacturer's literature and with your utility. Most general-purpose VFDs burn braking energy in a resistor bank unless they are explicitly line-regenerative units.
For the machine in front of you — one fixed speed, a heavy metal start button, no interface — the decision is the fixed-output electronic converter on a branch built around its published input current.
Questions asked
Can one solid-state converter run several machines at once?
Only if the converter's continuous output rating covers the combined full-load current of everything that may run together, and its documentation explicitly allows multiple motors. The hard case is the largest machine starting while the others run: its locked-rotor surge adds to the running load. Many units are rated for a single motor, so treat a multi-machine shop as a sizing question for the specific model, not a nameplate horsepower match.
Does the converter's third leg connect to neutral?
No. The three output conductors are lines; the motor consumes only line-to-line voltage, and none of them is a neutral. Bond the supply's equipment grounding conductor and the motor frame normally, and never land an output conductor on a ground or neutral bar. Follow the grounding diagram in the converter's installation manual, because internal grounding arrangements differ between models.
Will the converter run a motor connected for 460 V?
Not usefully. With the motor leads set for 460 V and the converter delivering its 230 V-class output, the motor sees half its rated volts per hertz and produces roughly one quarter of rated torque, so it stalls or trips the overload at start. Set the lead links for the 220/240 V connection shown on the nameplate or inside the terminal box before blaming the converter.
How much power does it waste when nothing is running?
A rotary converter's idler motor draws real power every minute it spins, which is why its idle current runs high. An electronic converter has no idler to spin; until a machine starts, its draw is limited to small control-electronics losses. Across a shop day of sitting idle, that difference shows up as less heat and less on the meter.
Can I keep the machine's magnetic starter?
Yes, and you should. The converter behaves like a three-phase source, so the existing three-pole contactor and thermal overload work unchanged; set the overload to the motor's nameplate full-load current. One check: if the contactor's control coil is fed from two of the converter's output legs, confirm those legs hold their line-to-line voltage while the motor starts, because a sagging coil voltage can drop the contactor out mid-start.