Explainer
What maps motor lead color to T-number conversion
Short answer
No standard converts motor lead insulation colors to T-numbers; NEMA and IEC documents fix the numbering scheme, never the colors. The maker's connection diagram and numbered lead tags govern; the only field convention, Black-A, Red-B, Orange-C, labels supply phases. When the diagram is gone, count the leads, sort the windings with a low-resistance ohmmeter, and prove rotation with an uncoupled bump test.

On this page
- Is there a standard chart that converts motor lead colors to T-numbers?
- Which colors on the job actually label something fixed?
- What numbers do motor makers print on the leads?
- Where does the color-to-number map for your motor live?
- Can you rebuild the map by measurement when the diagram is gone?
- Which supply phase goes on which lead?
- How do you prove rotation before you couple the load?
- What should you record so the next technician doesn't repeat this?
- Questions asked
No standard table converts motor lead insulation colors to lead numbers, and the chart someone remembers from a long-gone web page never described the industry — it described one manufacturer's product line. The only fixed color convention on a motor job is field-cable labeling, and it names supply phases, not terminals. The real color-to-number map lives on the motor itself: the connection diagram on the nameplate or inside the conduit box lid, and the numbered tags on the lead ends. This article separates the three labeling systems you meet on the job, shows where the genuine map lives, and gives the resistance measurements and bump test that rebuild it and prove it when the diagram is gone.
Is there a standard chart that converts motor lead colors to T-numbers? #
No standard table converts insulation color to lead number: North American motors carry T1 through T9 (or T12 on twelve-lead machines) under the NEMA MG-1 marking scheme, IEC 60034-8 assigns the U1, V1, W1 markings, and neither document ties any insulation color to any number. Both documents cover terminal markings and direction of rotation; color is left to the manufacturer. That is why lead colors differ between makers, and sometimes between production runs of the same frame. A conversion chart found online, or rescued from a dead link, describes only the product line it was drawn for. Carry it to another maker's motor and it can be quietly wrong, which is exactly the failure mode that starts the search for "the" chart in the first place. The marking scheme is standard; the colors are not.
Which colors on the job actually label something fixed? #
The only fixed color convention in the field is power-system cable labeling — Black for phase A, Red for phase B, Orange for phase C — and it names supply conductors in the panel and raceway, never terminals on the motor. Three different labeling systems get mixed together on a motor job, and most confusion about "converting" colors comes from bridging the wrong pair of them:
| Label set | Example | What it identifies |
|---|---|---|
| Supply phase | A, B, C (Black, Red, Orange field cable) | The source conductor in the panel and raceway |
| Lead number | T1 through T9, or U1/V1/W1 | One end of a winding, per the standard's marking scheme |
| Lead color | Whatever the maker molded that year | The winding end, only per that maker's diagram |
The field convention converts cable color to a phase letter. Which phase letter lands on which lead number is a separate decision, made by rotation, not by color. Nothing converts color to lead number directly.
What numbers do motor makers print on the leads? #
North American motors carry numbered leads T1 through T9, or T1 through T12 on dual-voltage machines with extra start and run options, while IEC motors use letter-number markings U1, V1, W1 and their second winding ends U2, V2, W2. The number or letter identifies a winding end; the marking pattern is what the standards fix. A chart written for T-numbered leads does not transfer to a motor marked U1/V1/W1 — convert the marking scheme first, then the connection. On a nine-lead dual-voltage machine, three of the nine are the common group rather than line ends, so the count alone does not tell you which lead does which job. The connection diagram on the motor does.
Where does the color-to-number map for your motor live? #
The map lives on the motor itself: read the connection diagram on the nameplate or inside the conduit box lid first, then the numbered tags on the lead ends, and let numbered tags outrank insulation color every time. Work the priority in this order. If the diagram lists colors beside the numbers, that table governs this motor — record it before you disconnect anything. If the diagram shows only numbers, read the stamped or printed tags on the leads; a numbered tag beats a color. If the leads carry neither tags nor a diagram, stop and get the diagram from the manufacturer using the nameplate model and serial number, or rebuild the map by measurement as below. Several manufacturers publish catalog wiring-diagram documents listing both numbers and colors; such a document governs its own product line only, and only when your nameplate's motor type and lead count match it.
Can you rebuild the map by measurement when the diagram is gone? #
Measurement rebuilds the map when the diagram is gone: count the leads, then read winding continuity with a low-resistance ohmmeter — on a nine-lead dual-voltage wye motor you will find three winding pairs and three leads common through the internal wye point. Before anyone opens the terminal box, NFPA 70E, the 2024 edition, requires establishing an electrically safe work condition: de-energize, lock out and verify absence of voltage; confirm the details with your authority having jurisdiction and the equipment documentation.
Separate every lead from the supply and from each other, then count. Three leads means a single-voltage connection already made inside. Six means wye or delta brought out for external connection. Nine means a dual-voltage wye; twelve means dual voltage with added start and run choices — what continuity across those pairs tells you is covered in what continuity across 12 lead motor winding pairs tells you. An ordinary meter can do the sorting if you know its limits; see what a multimeter shows about three-phase motor winding resistance.
Worked example, with illustrative readings for a 230/460 V nine-lead wye motor, all leads separated, measured with a low-resistance ohmmeter: T1–T4, T2–T5 and T3–T6 each read 1.2 Ω, and the three common-lead pairs T7–T8, T7–T9 and T8–T9 each read 2.4 Ω. The arithmetic checks the topology: each 2.4 Ω path runs through two half-windings in series, so 1.2 Ω + 1.2 Ω = 2.4 Ω, and the doubled reading confirms the internal wye point. Equal readings across the three pairs show balanced windings. Absolute values scale with motor size — a bigger machine reads milliohms where this example reads ohms — so the identifier is the structure (three pairs plus a common trio that reads twice one half-winding), not the number itself.
Resistance has a hard limit: it sorts leads into groups but cannot tell you which pair is phase 1 rather than phase 2, nor which end of a winding is the start. That assignment needs the diagram, the manufacturer, or the rotation proof below. Wrong polarity in a series connection announces itself later as high current, noise and heat — not as a wrong resistance reading.
Which supply phase goes on which lead? #
With the field convention Black-A, Red-B, Orange-C, the plain connection is A to T1, B to T2 and C to T3, reversed only when the driven equipment needs the opposite rotation — the colors themselves decide nothing. The catch is that cable colors do not prove the source sequences A-B-C; an upstream installer may not have followed the convention. Measure the sequence with a phase-sequence meter at the starter, or settle it with a bump test. The phase order at the motor fixes nothing except rotation direction, as covered in why phase order on a three-phase spindle only sets rotation.
| Connection | Result | Decided by |
|---|---|---|
| A-B-C to T1-T2-T3 | Rotation as the diagram marks it, if the source really sequences A-B-C | Measured phase sequence |
| Any two supply conductors swapped | Reversed rotation | The driven equipment's direction arrow |
How do you prove rotation before you couple the load? #
Bump the motor uncoupled before you trust any connection: pulse the starter for the shortest possible run, watch the shaft from the reference end the diagram defines, and swap any two supply conductors at the starter if the shaft turns the wrong way. Secure the shaft key and guards first, and never bump a pump, fan or compressor that the manufacturer forbids turning backward — reverse rotation can damage them before you release the button. If the direction is wrong, lock out, swap any two of the three supply conductors at the starter or the motor lead box, and re-bump uncoupled. Do not rewire inside a single-speed motor for a simple reversal. On a drive-fed machine, reverse rotation comes from swapping two output conductors or from the drive's direction command — one or the other, never both, because they cancel; why a phase swap before a VFD won't reverse the motor covers that trap. Mark the proven direction on the motor.
What should you record so the next technician doesn't repeat this? #
Write the mapping down where the next technician will look: tag every lead with its T number, write the phase-to-lead order inside the box lid, and record the winding resistances you measured so a future imbalance has a baseline. Photograph the nameplate and the lead tags before disconnecting anything, and use heat-shrink or numbered cable markers, not color alone. At the first start, check current in all three phases at no load — matched currents confirm the connection and polarity, and a significant imbalance sends you back to the lead assignment. One phase is not a test: why testing one phase current on a 480 V motor is not enough explains what a single reading hides. The decision, in one line: the motor's own diagram and tags are the only conversion table, measurement sorts the leads into groups, and the uncoupled bump test settles the last unknown, which is rotation.
Questions asked
Do manufacturer wiring-diagram catalogs work for any motor of the same lead count?
Some motor manufacturers publish catalog wiring-diagram documents that list lead numbers and colors together. Treat one as valid only for that maker's product line, and only after the motor type, pole count and lead arrangement on your nameplate match the diagram. A wye-connection diagram never describes a delta-connected motor, even at the same lead count.
Can I use an insulation-resistance tester to sort the leads?
No. A megohmmeter measures insulation between the windings and the frame, which is a different test at a different voltage. Sorting leads needs a low-resistance ohmmeter that reads winding continuity in ohms or milliohms. Use the insulation tester afterward to confirm the windings are sound to ground before the motor returns to service.
What if two motors on the same job follow different color schemes?
Expect exactly that. Lead colors are a manufacturer choice and can differ between builders or even production runs. Convert each motor from its own diagram or tag set, mark the final phase-to-lead order on each machine, and never carry a conversion from one motor to the next just because the lead counts match.
Does the color order tell me the supply phase sequence?
No. Black-A, Red-B, Orange-C describes how the conductors were labeled when the cable was pulled, not how the source actually sequences. An upstream installation can depart from that convention, so prove the sequence at the starter with a phase-sequence meter, or settle rotation with the uncoupled bump test before the load is coupled.