What IEC motor terminal markings mean against NEMA leads

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

IEC 60034-8 marks the six ends of three windings U1/V1/W1 (starts) and U2/V2/W2 (finishes); on a six-lead motor they cross to NEMA T1 through T6 in that order. The cross-reference stops there because NEMA nine-lead motors split phases for series/parallel reconnection at 2:1 and bury a junction, while IEC machines link whole windings star or delta at 1.73:1.

On this page
  1. What do U1, V1, W1, U2, V2 and W2 mean on a motor terminal board?
  2. How do IEC terminals cross-reference to NEMA T leads?
  3. Why does the IEC to NEMA mapping stop at six leads?
  4. Is a star/delta change the same as a NEMA series/parallel change?
  5. Which connection do I choose for the supply in the plant?
  6. How do I confirm winding pairs and polarity after a rewind?
  7. What changes when the motor has twelve leads?
  8. Questions asked

The IEC letters on a terminal board are a winding map, not a rival numbering of the same machine: U1, V1 and W1 are the starts of the three phase windings, U2, V2 and W2 their finishes, and on a motor with six accessible ends they line up with NEMA T1 through T6 in that order. Past six leads the two systems part ways. NEMA dual-voltage machines split each phase into half-windings and bury a junction for series/parallel reconnection, while IEC machines bring out whole windings to link in star or delta, a 1.73:1 voltage step against the 2:1 step. What follows is the cross-reference, the reason it stops at six leads, and the connection to choose for each nameplate you will meet.

What do U1, V1, W1, U2, V2 and W2 mean on a motor terminal board? #

IEC 60034-8 labels the two ends of each phase winding: the letter names the winding (U, V or W) and the suffix separates its start (1) from its finish (2), so U2 is the finish of the winding that begins at U1. The letters carry no voltage information; the connection diagram on the nameplate supplies that.

Older boards use letters only: U, V and W for the starts, X, Y and Z for the finishes, with X the far end of U, Y of V and Z of W. Both notations describe one machine, three windings with all six ends brought out to the box. NEMA MG-1, the US counterpart to the IEC 60034 series, is the standard family behind the T-lead numbering the next section crosses to.

How do IEC terminals cross-reference to NEMA T leads? #

On a motor with six accessible winding ends, the accepted cross-reference runs U1 to T1, V1 to T2, W1 to T3, U2 to T4, V2 to T5 and W2 to T6, in the same phase order.

IEC terminal NEMA lead Winding role
U1 T1 Phase U start
V1 T2 Phase V start
W1 T3 Phase W start
U2 T4 Phase U finish
V2 T5 Phase V finish
W2 T6 Phase W finish

The table is a label correspondence for three whole windings with both ends out, the normal IEC machine. It says nothing about T7, T8 or T9, because a six-terminal board has no half-windings to number. Use it as the starting point and confirm it against the motor's own connection diagram: a rewind shop or a previous owner may have re-marked a board, and a printed table cannot see that.

Why does the IEC to NEMA mapping stop at six leads? #

Because the two standards build different machines: a NEMA nine-lead motor splits each phase into two half-windings, brings out nine ends and buries the tenth junction, so T7, T8 and T9 have no IEC counterpart. A nine-lead wye machine keeps its star point inside the frame, so it reconnects series or parallel across its voltage pair but can never be linked into delta. Older nine-lead delta machines bury three corners and can never be star.

The IEC six-terminal machine is the mirror image: whole windings in the box, star or delta available, no series/parallel option at all. The cross-reference is therefore complete at six leads and silent beyond them. Wherever a nine-lead motor goes it follows its own diagram, onto a full-voltage starter or when wiring nine-lead dual voltage motor leads to a VFD.

Is a star/delta change the same as a NEMA series/parallel change? #

No: star and delta on three whole windings move the allowable line voltage by the square root of three, about 1.73, while the NEMA series/parallel scheme moves it by exactly 2.

Worked example, hypothetical nameplate delta 220 V / star 380 V, 50 Hz, three whole windings each rated 220 V:

  • Star on a 380 V line: each winding sees 380 ÷ 1.732 = 219.4 V, its rated voltage.
  • Delta on a 220 V line: each winding sees the full line voltage, again its rating.

One winding set, two line voltages one step apart: that is the whole star/delta idea.

Second worked example, hypothetical nameplate 230/460 V, nine leads, six half-windings each rated 230 V:

  • High voltage: two half-windings in series per phase, 2 × 230 V = 460 V.
  • Low voltage: the same halves in parallel, 230 V per phase.

The schemes are not interchangeable; a machine wound for one cannot be linked into the other unless it brings out twelve leads. In the box, star is U2, V2 and W2 linked with the supply on U1, V1 and W1; delta is three links, each start joined to the finish of a different phase: U1 with W2, V1 with U2, W1 with V2. What star and delta jumper bars mean on a motor terminal box shows how to read bars already fitted, and why a motor draws different line current in wye and delta covers the current side of the swap.

Which connection do I choose for the supply in the plant? #

Read the nameplate voltage pair and connect the winding side that matches your line: a delta 220 V / star 380 V machine on a 380 V line goes in star with U2, V2 and W2 linked, and on a 220 V line it goes in delta.

The decisions by case:

  • Nameplate with a delta/star voltage pair: star on the higher voltage, delta on the lower. The country the motor was built in plays no part; the printed pair is the whole instruction.
  • Nine-lead 230/460 V machine: series links on the higher voltage, parallel on the lower, exactly as its own diagram prints them.
  • Single-voltage nameplate: one connection, nothing to link, supply on U1, V1 and W1.

Measure the actual line voltage at the starter before you close onto the motor and select the nameplate connection for what you read. After first energization, check rotation; to reverse, swap two supply phases at the starter or isolator, never the winding ends in the box. Where a site rule governs motor connections, confirm it with the authority having jurisdiction alongside the motor documentation.

How do I confirm winding pairs and polarity after a rewind? #

Treat the labels as claims after any rewind: isolate, lock out and prove the motor dead at the terminal box, then use an ohmmeter to find the three pairs before you trust a single letter on a lug.

Continuity between ends should show exactly three pairs, U1 with U2, V1 with V2 and W1 with W2, with no path between different pairs. Check each end to the frame while the meter is out; reading motor lead-to-ground ohms on a 480 V compressor shows what good and failed readings look like on that test.

A continuity reading finds a pair; it cannot tell which end is the start. Take polarity from the rewinder's winding sheet or from a documented polarity test, never from wire color or from the labels of the motor that came out. One reversed winding makes a star or delta connection electrically wrong even with the pairs right. Finish with a resistance balance check, three comparable phase readings judged against the motor documentation: it catches an open or a grossly mismatched winding, and it does not prove polarity.

What changes when the motor has twelve leads? #

A twelve-lead motor brings out both ends of all six half-windings, so it can be linked series or parallel and star or delta, the one winding set that serves both the NEMA and the IEC connection habits. Twelve ends do not extend the six-lead cross-reference by guesswork: the board follows its own diagram, and each half-winding carries its own designation there.

What the extra ends buy is range. The same frame takes the series/parallel step or the star/delta step, in the combinations its nameplate prints, and a machine bought for one scheme can be re-linked for the other; one worked reconnection of the kind is reconnecting a 12-lead 575 V delta motor to 480 V wye. Identify the half-windings the same way as after a rewind before moving any link.

Questions asked

Can I add NEMA numbers next to the IEC letters on a terminal board?

Yes, once the three pairs are confirmed with the motor isolated: mark both systems on each lug, U1 with T1 through W2 with T6, so the next electrician can work in either. Do not carry the numbering past six leads, because on a nine- or twelve-lead board the extra numbers belong to half-windings that only the manufacturer's diagram can assign.

Does the cross-reference hold at a star-delta starter?

Yes. The line contactor lands on the winding starts U1, V1 and W1, the delta contactor picks up the finishes, and the star contactor shorts the finishes together during run-up. The starter works in winding ends, not national conventions, so wire it to the letters on the board and the transition behaves as the diagram shows.

What does a reversed winding look like at start-up?

The motor hums or growls, draws current far above its rating and either crawls or sits still, because one winding is magnetically fighting the other two. That is a polarity fault, not a supply problem. Isolate the motor again, re-identify the start of each pair, and refit the links before resetting anything.

How do I connect a six-terminal motor to a variable frequency drive?

Link the windings for the voltage the drive actually delivers, not for the utility line. A drive outputting 400 V feeds a delta 380 V / star 660 V machine in delta with the star point left open, and the drive's motor voltage setting is then entered to match the connection made. The star and delta pair describes the winding; the drive simply supplies it.

Keep reading

  • Explainer

    What star and delta jumper bars mean on a motor terminal box

    One jumper bar joining the three winding ends is a star connection — the supply lands on the other three terminals. Three bars, each bridging one terminal to its neighbour, are delta. At 380 V in star, each winding sees about 219 V and the leads carry the plate's 2.7 A; delta needs a 220 V-class supply and about 4.7 A at the leads.

    Motors and motor starters

  • Explainer

    Motor nameplate current is line current, not winding current

    The amps printed on a three-phase motor nameplate are line current: what a clamp meter reads in each supply conductor at full load in the plate's designated connection. In star, winding current equals line current; in delta, each winding carries the line current divided by 1.73 — about 14.5 A for a 25 A plate.