Troubleshooting
What relay rating a contactor coil switching circuit needs
Short answer
The switching device's load side must be rated for the measured line-to-line coil voltage, 240 V AC minimum on this circuit, and for the coil's inductive pickup duty, so a 120 V AC-rated SSR output is rejected. When a coil burns while its SSR is commanded OFF, verify the relay's off-state leakage current before replacing the coil.

On this page
- What the readings tell you, and what they do not
- Input rating and load rating are separate specifications
- Measure the coil voltage line to line before selecting anything
- Sizing the switch for the line-to-line coil drawing 70 mA
- Prove that OFF really removes coil excitation
- The decision, case by case
- Questions asked
A contactor coil wired across two lines of a 240 V three-phase supply needs a switching device whose load side is rated for the full line-to-line voltage and for an inductive load: 240 V AC minimum on the switched output. A 120 V AC-rated SSR output is inadequate for that circuit, and when a coil burns while its SSR sits commanded OFF for days, the relay's off-state leakage current is the first thing to verify, before the coil is even replaced. The relay's control-input rating is a separate choice, made to match whatever drives it. One safety note before the hands-on steps below: isolate the circuit, lock it out and test for absence of voltage before opening a panel or touching coil terminals. An OFF command is not isolation, and with a line-to-line coil both conductors can be live to ground.
What the readings tell you, and what they do not #
The sequence matters. A coil that failed after about three days with its relay commanded OFF makes off-state energization the priority check, but it does not name the failure mechanism by itself. Work through these checks in order:
- Commanded-OFF coil failure: suspect off-state leakage through the SSR, but also a miswired parallel feed, an indicator or suppression branch around the output, a damaged output device, or a coil wound for a lower voltage.
- The 70 mA pushbutton reading: this describes that test condition only. It is not pickup current, not leakage, and not the current that flowed during the failure. Confirm the armature seated cleanly before the reading was taken; a humming, partially closed contactor draws a sustained elevated current.
- Controller status "OFF": this proves the command state, not that the output interrupted coil power. The coil-terminal voltage is the only proof.
- Record together: command state, coil-terminal voltage, coil current and mechanical contactor position, at pickup, while held ON, and while commanded OFF.
Input rating and load rating are separate specifications #
The signal chain runs from the operator command, through the controller output, into the relay's input, and finally through the relay's load terminals to the coil. Each interface has its own voltage and current requirement, and the contactor's three-phase power poles say nothing about what its coil needs.
- Electromechanical relay: select the relay coil for the control voltage and whether the supply is AC or DC; select the contacts separately for the coil voltage, the pickup current and the inductive switching duty.
- SSR: the input operating range and the load-side range are independent specifications, and the output must match the load's AC or DC supply type. So a relay named only by a single voltage is an incomplete description. If the lower control-level figure is the tested SSR's output rating, reject it for this circuit. If it names only the input, read the output specification before judging.
An AC contactor coil draws more current with its magnetic gap open than after the armature seats, so a sealed-current reading cannot size the switch; the pickup current and the coil's VA at pickup set the duty, the same way an undersized interposing contact fails on contactor coil inrush. SSR selection guides assign random-switching outputs to inductive loads and call for extra derating headroom on them, because the zero-cross function is aimed at resistive loads. Use the relay maker's inductive-load rating, never its resistive figure alone.
Measure the coil voltage line to line before selecting anything #
Do not derive the coil voltage from a line-to-neutral measurement. The supply is described by its line-to-line voltage, but its winding arrangement is unspecified. Measure directly across the two conductors feeding the coil. If the source turns out to be a wye with a correspondingly lower line-to-neutral voltage, the line-to-line value will come out near 208 V instead; that is a measured fact about the supply, not a downgrade of the stated source. Either way, one output rating covers both cases, as the worked example below shows.
Sizing the switch for the line-to-line coil drawing 70 mA #
Inputs:
- Coil connected between L1 and L2 of the stated three-phase source (the installation's own description; verify with a meter as above).
- Sealed coil current of 70 mA, measured with a manual pushbutton energizing the contactor (the site test).
- Alternative supply: a wye system with the lower line-to-neutral voltage (the case raised by the supply question).
Rule in words: the switched output's voltage rating must equal or exceed the measured line-to-line coil voltage. The coil's apparent power is its terminal voltage times its current, S = V_coil × I_coil, a single-phase quantity because the coil spans two conductors even on a three-phase supply.
Arithmetic:
- Wye case line-to-line voltage: V_LL = √3 × V_LN = 1.732 × 120 V = 207.8 V ≈ 208 V.
- Apparent coil power at the stated supply: S = 240 V × 0.070 A = 16.8 VA.
- Apparent coil power on a wye supply: S = 208 V × 0.070 A = 14.6 VA.
Result: the coil demands about 16.8 VA sealed on the stated supply, or about 14.6 VA on a wye supply. These are volt-amperes, not watts; real power additionally depends on the coil's power factor, and neither figure represents the pickup demand, which is higher.
Decision: specify a switched output rated for the measured line-to-line coil voltage or higher; that single rating covers both the stated supply and the wye case. An output rated below the line-to-line value is rejected for this circuit. Size the current rating from the contactor's published pickup current with the relay maker's inductive-load derating, not from the sealed reading.
Prove that OFF really removes coil excitation #
Relay manufacturers' own FAQ documentation states that leakage current flows while an SSR input is OFF, and that driving a small relay coil from it can leave that coil slightly energized. Small SSRs commonly quote a few milliamps of off-state leakage, with 2 to 3 mA a typical figure; the datasheet value for your part is the one that counts. A contactor coil left marginally energized for days can overheat and burn, which fits the reported failure. Diagnosing SSR off-state leakage and ghost voltage follows the same method described there for DC loads: voltage and current must be read together, with the load connected.
- Isolate and lock out before touching wiring; an OFF command is not a safe state for hands-on work.
- Command the sequence while recording coil-terminal voltage, coil current and mechanical position. Check the controller's output status, not the screen.
- The contactor must pick up positively, hold seated without chatter, and release on OFF. If voltage is present yet the armature hesitates, apply the checks in motor starter coil has voltage but won't pull in.
- For the OFF state, measure current in series with a meter that resolves milliamps; a multimeter on an amps range can read a false zero while leakage flows. A high-impedance voltmeter across the coil may show ghost voltage with negligible current, which is why both quantities are read.
- Compare coil and relay temperatures under representative duty against the manufacturers' limits.
The decision, case by case #
- SSR output rated only 120 V AC: reject for this circuit; the load-side rating is below the line-to-line coil voltage.
- SSR rated 240 V AC or higher, AC output, random-switching: acceptable when its inductive-load rating covers the coil's published pickup current and its datasheet leakage keeps the commanded-OFF coil current below the contactor's must-release level.
- Electromechanical interposing relay: coil matched to the controller output's voltage and AC or DC type; contacts rated for the line-to-line coil voltage with a utilization-category rating for electromagnetic loads, AC-15 under IEC 60947-5-1, at or above the coil's sealed volt-amperes. Confirm the selection against the relay documentation and the equipment manuals, and with the local authority having jurisdiction where the installation falls under a code requirement.
- Wye supply measuring about 208 V line to line: the same minimum output rating covers it; measure first, then order nothing less.
Questions asked
Can I keep the 120 V SSRs and add an interposing relay?
Yes, and it is often the cleanest fix. Let the SSR switch a small electromechanical relay whose coil suits the SSR's output rating, and let that relay's contacts switch the contactor coil at full line-to-line voltage. Pick a relay whose must-release current is above the SSR's datasheet leakage, so the off-state current cannot hold the interposing relay in.
Why did the leakage test read zero?
A multimeter in series may not resolve a few milliamps on the range used, and the leakage path through a snubber network charges without transferring much current. A high-impedance voltmeter across the disconnected coil can instead show a misleading voltage. Measure with the coil connected, using a meter that resolves milliamps, and interpret voltage and current together.
Should the SSR be zero-cross or random switching for a contactor coil?
Relay selection guides assign random-switching SSRs to inductive loads; the zero-cross function is intended for resistive loads and can misbehave when the load current lags the voltage. For a contactor coil, choose a random-switching AC output and apply the maker's inductive-load derating to the coil's published pickup current.
Is 70 mA a normal sealed current for a contactor coil?
Yes. Small AC contactor coils commonly draw tens of milliamps once the armature seats, so the reading is plausible as a sealed value. It does not size the switch: the open-gap pickup current is higher, commonly several times the sealed current, and that inrush with the maker's inductive derating sets the contact or output rating.