Troubleshooting
Why an interposing relay welds on contactor coil inrush
Short answer
A relay marked 6 A at 230 VAC for resistive load is not qualified to make and break a large AC contactor coil with a 65 A pickup; the contacts weld and only a tap frees them. Fit a relay with a documented inductive making and breaking rating, a high-inrush relay or a small interposing contactor rated AC-15, keep the integrated varistor, and do not add a parallel RC network as an inrush limiter, because across the coil it limits nothing.

On this page
The relay welds because a 6 A at 230 VAC marking is a resistive-load figure that says nothing about making and breaking a big AC coil, and the contactor data sheet states a 65 A inrush for that coil. Every PLC start command closes the relay's contact onto that pulse, and contact bounce remakes it several times in the first milliseconds, until the faces weld lightly enough that a tap frees them. The decision: fit a relay with a documented inductive making and breaking rating for the coil, either a high-inrush relay or a small interposing contactor; keep the contactor's integrated varistor; and do not add a parallel RC network, because across the coil it limits no pickup current. Below: how to prove which part failed, the selection check with the arithmetic, and how to qualify the replacement.
What the ampere marking covers #
A control relay has three separate duties: carry current continuously, make current (close onto it), and break current (interrupt it). The ampere figure printed on a general-purpose relay documents the first, with a resistive load. An AC coil is an electromagnetic load: at pickup the magnetic circuit is open and the current is high, and it falls sharply once the armature seals. Carrying the sealed current is easy; surviving the make is what fails.
IEC 60947-5-1 (2003 edition) covers electromechanical control circuit devices and defines utilization categories for exactly this duty: AC-14 for small electromagnetic loads and AC-15 for AC electromagnetic loads, the category a relay switching a contactor coil must be rated for. The same standard requires contactor relays to also meet the tests of IEC 60947-4-1, the contactors standard, except for the utilization category. Read the category and the rated current at your coil voltage from the relay's data sheet, and confirm the selection with the panel documentation and your authority having jurisdiction.
Why the pickup peak welds the contact #
Two effects stack up at every make:
- The pulse is large and inductive. Each bounce interrupts the pickup current and sustains a small arc, and each remake dumps the full pulse through a tiny contact spot; the local heating microwelds the faces. Repeated making of a large current is the same mechanism that melts a contactor contact on high-speed transfer.
- Anything that slows the armature lengthens the pulse. Low voltage at the coil terminals, a loose connection or a sticky mechanism keeps the magnet open longer, so the high current flows longer, the condition behind a motor starter coil that has voltage but won't pull in.
A tap that frees the contact points at the contact itself: a light weld or adhesion, not a control fault. A relay held on by a stuck PLC output would not release when tapped, so establish which of the two you have before ordering parts.
Isolate, then separate the two faults #
A welded relay contact leaves the contactor coil circuit live with the PLC output off, and the contactor itself stays closed. De-energize the control and coil circuits, lock them out and test for absence of voltage, the verification your electrical safety program requires under NFPA 70E (2024 edition), which covers workplace electrical safety, before opening the panel or pulling the relay.
With the circuits dead, work through these checks:
- Record the relay's full part number, socket type, coil voltage and contact arrangement; the replacement must fit that socket or replace it.
- Measure continuity across the relay's normally open contact. Near zero ohms with the relay coil de-energized means a welded or mechanically stuck contact.
- Inspect the socket terminals and wiring for heat discoloration and looseness; a welded relay usually leaves both behind.
- Read the contactor coil data properly: whether the stated inrush is a peak or an RMS value, and how long it lasts. That definition decides the number the replacement must cover.
The check: a 6 A relay against a 65 A pickup at 230 V #
Inputs. Coil voltage 230 VAC (contactor nameplate and data sheet). Stated coil inrush 65 A (the contactor data sheet, as read on site). Relay marked 6 A at 230 VAC with no utilization category (the installed relay's face).
Rule. For an AC electromagnetic load, select the relay by its AC-15 data at the coil voltage: the documented making current must equal or exceed the coil's pickup current, and the breaking rating must cover the sealed coil current. A resistive ampere marking documents neither number.
Arithmetic. The ratio of the actual making duty to the only current printed on the relay:
65 A ÷ 6 A ≈ 10.8
The contact closes onto roughly eleven times its marked current at every start. If the data sheet's inrush figure is RMS, the crest is higher still: 65 A × 1.41 ≈ 92 A. Read the definition before sizing against it.
Result. The installed relay has no documented making current and no inductive breaking rating for this load, and the observed failure, contacts that free with a tap, is a making-duty weld.
Decision. The relay comes out. A replacement goes in only when its published AC-15 making current at the coil voltage covers the stated pickup (or its crest, if the figure is RMS) and its breaking rating covers the sealed current. That means a high-inrush relay or a small interposing contactor; a larger resistive ampere marking alone changes nothing.
Keep the varistor, skip the RC network #
The integrated varistor is a voltage-dependent resistor across the coil. At pickup it does nothing: the pickup current flows because the coil is an open magnetic circuit, not because of a voltage spike. When the coil circuit opens, the varistor limits the inductive voltage peak and shortens the breaking arc. Removing it would raise the switch-off stress on whatever breaks the coil current and would not reduce the making duty, so it stays.
An RC network across the coil is a parallel branch, so it cannot limit the coil's pickup current either. Worse, its capacitor draws its own charging current at the exact instant the relay closes, adding making duty, and it alters the contactor's release time. Fit only the suppression arrangements the contactor manufacturer documents for that coil, and never treat an RC unit in that position as an inrush limiter, because it is not one there.
Qualifying the replacement #
Choose by published switching data, not by width or the headline ampere figure:
- High-inrush relay. Its data sheet states a making current for inductive and capacitive loads well above its thermal rating. Confirm that figure covers the pickup at the coil voltage, and that the socket and the PLC output match its coil: voltage, current draw and suppression type. More poles give you a spare contact to move onto when one burns.
- Interposing contactor. A small contactor also works, but its motor rating in kW at AC-3 describes motor duty, not coil switching. Read its AC-15 making and breaking figures at the coil voltage instead. The PLC output now drives that contactor's coil, so its coil current belongs in the output's load check too.
Commissioning the repair #
- Verify the voltage at the contactor's coil terminals during pickup; a slow seal lengthens the inrush and loads the new relay the same way.
- Run repeated start and stop commands and confirm the relay releases and the contactor drops out every time.
- Re-check terminal tightness after the first hours of operation; a loose coil connection imitates a relay fault.
The call #
For this duty the call is fixed. A relay documented only as a resistive ampere figure comes out of any circuit that makes a large AC coil, whatever its frame or socket. In goes a high-inrush relay or a small contactor whose AC-15 making current at the coil voltage covers the stated pickup and whose breaking rating covers the sealed current. The integrated varistor stays, no RC network is added as an inrush fix, and the repair is proven by repeated clean start and stop cycles with full voltage at the coil during pickup.
Questions asked
Can I parallel two relay contacts to share the inrush?
No. Two contacts never touch at the same instant, so the first to close takes the whole pickup pulse alone and the second adds bounce, not capacity. No manufacturer documents extra making current for paralleled contacts. A multi-pole relay is still worth having: when one contact burns you move the wire to a spare pole instead of waiting for a new relay.
Does the integrated varistor cause the sticking?
No. It sits across the coil and conducts only when the voltage across it rises at switch-off, so it carries nothing during pickup, which is when the weld forms. It reduces the breaking arc and the voltage spike at interruption. Removing it would not lower the making duty and would raise the stress on whatever device breaks the coil current.
Is the sealed coil current the problem?
No. Once the armature seals, the coil current falls to a small holding value that any of these contacts carries easily. The weld forms in the first milliseconds of the make, which is why the fix is a making-current rating, not a bigger continuous rating. The breaking side still matters: the relay must interrupt the sealed inductive current, and that is what the AC-15 breaking figure covers.
Why does tapping the relay free it?
The weld is a thin bond between the contact faces; a mechanical shock breaks it and the return spring pulls the armature back. That behavior tells you the fault is at the contact, not a held command from the PLC, because an energized relay coil would not let go when tapped. The weld re-forms within a few operations, since the making duty is unchanged.
Will a relay with a higher ampere rating fix it?
Not by itself. A larger resistive marking still documents nothing about making an inductive load, and general-purpose relays of the same frame differ mainly in breaking capacity. Ask for the making current and the AC-15 rating at your coil voltage, and compare them with the coil's stated pickup and sealed current. That comparison, not the ampere figure, is the qualification.

