Explainer
When line reactor impedance is missing from an arc flash study
Short answer
A line reactor or matrix filter's ampere rating is not an impedance. Without its resistance, reactance and X/R, the only defensible downstream bolted fault current is the filter-neglected case — a maximum-current boundary. Added series reactance can pull the fault below the upstream breaker's instantaneous pickup and stretch clearing time, so the boundary is not automatically the worst incident-energy case: obtain certified impedance, test the de-energized filter, or replace it with equipment that publishes its data.

On this page
The ampere rating stamped on a line reactor or a matrix harmonic filter is not an impedance, and it cannot be converted into one. Until per-phase resistance, reactance and X/R arrive from the vendor or from a documented test, the only downstream bolted fault current an arc flash study can defend is the filter-neglected value — and that value is a maximum-current boundary, not the installed-system result. Stopping there is not conservative either: the added series reactance reduces fault current, and a reduced current can drop below the upstream breaker's instantaneous pickup and stretch the clearing time from a couple of cycles to tens of them. The maximum-current case is therefore not automatically the worst incident energy case. This article identifies the missing data, works the case both ways with real arithmetic, and gives the decision for each path out: certified data, a documented test, or replacement with equipment that publishes its impedance.
What the nameplate gives you, and what it does not #
A filter rated 1200 A carries a current-capacity statement: the continuous amperes its conductors and cores withstand. It fixes none of the quantities a fault calculation consumes — resistance, reactance, inductance, X/R. Identical units from one production run let you treat all three installations as one impedance once a value exists, but they do not create the value.
The data a short-circuit model needs from the filter is specific: per-phase resistance and reactance at the power frequency, or inductance from which the reactance follows, or a percent impedance stated together with the voltage and current base it is referenced to — plus the X/R ratio. Reactors of this class normally ship with exactly these numbers published. The resistance is small next to the reactance, so the ratio runs high, and it matters twice: it sets the asymmetric first-cycle duty the downstream equipment must withstand, and it feeds the corrections in the fault calculation itself. When the circuit X/R ends up above the ratio a device was tested at, its duty has to be re-derived before the rating can be relied on; calculating equipment duty above the tested X/R ratio works that recalculation through.
Why the neglected case is a boundary, not an answer #
For a filter whose schematic shows two series inductances per phase and nothing else in the fault path, the neglected case is the optimistic extreme: series impedance in the path can only pull the downstream bolted current down. What the neglected calculation gives you is the highest bolted current the model can produce. That is a boundary, and nothing more.
Two things go wrong if the study stops there. First, the label would carry a current no installed conductor will ever see. Second — the trap — less current is not automatically safer. The upstream breaker clears instantaneously only while fault current stays above its instantaneous pickup, and pickups carry a tolerance band the manufacturer's documentation states. Pull the current below that band and clearing leaves the instantaneous region: instead of one or two cycles, the fault times out through the delayed curves, where tens of cycles are routine. Incident energy scales close to linearly with clearing time, so the case with less current can deposit more energy at the arc.
The calculation standard anticipates the mechanism. IEEE 1584 (2018 edition), the guide for performing arc-flash hazard calculations, evaluates the energy at full arcing current and again at 85% of it, and the worse of the two results governs — precisely because a lower arcing current with a longer clearing time can be the damaging case. That is why arc flash software reports 85% of the arcing current. The same mechanism applies one element earlier in the circuit here: an upstream instantaneous setting may not cut arc flash, and a series filter is one of the ways the fault current slides out of that setting's reach.
Worked example: 480 V VFD bus behind a 1200 A filter #
Inputs #
- Bus voltage: V_LL = 480 V, three-phase, 60 Hz — the installed feeder to the VFD bus.
- Available bolted fault current at the filter input: I_in = 30 kA — an illustrative value; take yours from the short-circuit study at the filter's line side.
- Filter impedance: Z_f = 0.010 Ω per phase at 60 Hz, about 27 µH — an illustrative value standing in for the certified resistance and reactance the vendor owes you.
- Arithmetic assumption: reactance dominates both the source and the filter, so magnitudes add. The study itself adds R and X as vectors, with each element's X/R applied.
The rule in words #
Turn the input fault current into a source impedance, add the filter impedance in series, and turn the total back into a current: the line-to-line voltage divided by root 3 times the total per-phase impedance.
The arithmetic #
Z_source = 480 V / (√3 × 30,000 A) = 480 / 51,960 = 0.00924 Ω per phase
Z_total = 0.00924 Ω + 0.010 Ω = 0.01924 Ω per phase
I_filtered = 480 V / (√3 × 0.01924 Ω) = 480 / 0.03332 = 14,400 A, about 14.4 kA
Result and decision #
The filtered case lands at about 14.4 kA downstream — 52% below the 30 kA neglected case, because 14.4/30 = 0.48. The neglected case remains the maximum-current boundary. The reduced case is the one that can govern energy, and the threshold is the breaker, not the arithmetic: whenever the upstream instantaneous pickup, with its tolerance band, begins above 14.4 kA, a fault beyond the filter clears on the delayed curves, and the label must carry whichever case produces the higher incident energy. The example also sizes what the missing data hides: series impedance comparable to the source's own — 0.010 Ω against 0.00924 Ω — roughly halves the downstream bolted current. Until a certified or tested impedance exists, only the boundary case can be computed, so the boundary case is what the study runs.
What goes in the study file and on the label meanwhile #
NFPA 70E, the 2024 edition of the Standard for Electrical Safety in the Workplace, requires an incident energy analysis where energized work could expose a worker to an arc (Article 130), and Section 130.5(H) requires a label at the equipment stating the incident energy with its working distance, the arc flash boundary and the date. The analysis is required to reflect the system as installed and to be updated when the system changes. Editions and local amendments differ, so confirm the exact labeling requirement with the authority having jurisdiction and the equipment documentation.
With the filter data refused — a request for the per-phase impedance, and a second request for the output bolted current at a stated input current, both declined as proprietary information — the defensible package is:
- The equipment record: model line, rated current, the schematic representation (two series inductances per phase) and the shared production-run identity.
- The data request: what was asked and what was answered, so the gap is documented rather than silent.
- The calculation: the neglected case, retained as the maximum-current boundary, with a plain statement that the installed-system current and clearing time are unresolved.
- The consequence: instantaneous clearing is demonstrated only for the neglected case; with the filter in the path, clearing can sit on the delayed curves and the energy can run higher.
Label the incident energy from the neglected case and record beside it that the value is a boundary pending the filter data. Keep the gap as a tracked open item in the study file rather than a footnote, the way scoping an outsourced arc flash study you can maintain in ETAP keeps model assumptions from being lost between study versions.
Three ways to close the impedance gap #
-
Certified data. Ask the filter manufacturer for per-phase resistance and reactance at the power frequency with the X/R ratio, a percent impedance with its base, or the vendor's own output bolted current calculated for the input current you measure. Ask before the purchase order is cut: written into the specification, the data is a deliverable; asked after delivery, it is a favor.
-
A documented test. Before any cover comes off the filter or its termination box, de-energize the feeder, lock out and tag out, and verify absence of voltage at the terminals — the NFPA 70E sequence, together with the equipment's own procedures. Then isolate the filter and measure each phase's series inductance and winding resistance, and have the readings reviewed and approved as engineering data before they enter the model.
-
Replacement with published data. Where the data cannot be obtained, specify a reactor or filter that publishes its impedance — and, ideally, its output fault current for a stated input. Every downstream current, clearing time and incident energy result becomes verifiable, and the label stops resting on a boundary.
The decision, case by case #
- Certified impedance in hand: model the series path with vector R and X, run both the neglected and the filtered cases, read the filtered current against the instantaneous pickup band, and label whichever case produces the higher incident energy.
- Data refused and no test possible: label the neglected case as a boundary, document the request and the refusal, flag the clearing time as unresolved, and keep the item open in the study file and the purchase specification.
- Replacement under way: model from the published data, update the analysis as NFPA 70E requires whenever the system changes, and reissue the labels.
The move to avoid is presenting the filter-neglected bolted current as the installed-system answer. It is a boundary. Whether the filtered case is worse depends on where the pickup band sits relative to the filtered current, and only the impedance — certified, tested, or published on replacement equipment — settles it.
Questions asked
What should the purchase specification for the next filter demand?
Demand, in writing and before the order is placed: per-phase resistance and reactance at the power frequency, or inductance in millihenrys; or a percent impedance with the voltage and current base it is referenced to; the X/R ratio; and the vendor's calculated bolted fault current at the output for a stated available current at the input. Written into the specification it is a deliverable; asked after delivery it is a favor.
How can the impedance be measured if the vendor will not release it?
Only on a unit that is locked out and verified dead: isolate the filter and measure each phase's series inductance with an inductance bridge or LCR instrument, and the winding resistance with a DC micro-ohmmeter. Reactance at 60 Hz is 377 times the henry value, so a measured 27 µH reads as about 0.010 Ω. Have the numbers reviewed and approved as engineering data before they enter the model.
How often must the analysis be reviewed once the gap is closed?
NFPA 70E, 2024 edition, Section 130.5 has the incident energy analysis updated whenever the electrical distribution system changes and reviewed at intervals not exceeding five years. Installing, replacing or finally characterizing the filter is such a change, so the study and its labels get revised then. Confirm the interval with the authority having jurisdiction, because editions and local amendments differ.
Does the missing X/R change anything besides fault current?
Yes, twice. The series path's X/R sets the asymmetric first-cycle current, and when the circuit X/R exceeds the ratio the downstream equipment was tested at, its short-circuit duty must be recalculated with the published multipliers before the rating can be relied on. And when the filter pulls fault current down, a current-limiting device can fall below its threshold and stop limiting, so let-through performance cannot be assumed from the higher-current case.
