Where 3RW44 manual mode lives on PROFIBUS control

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

Decide first whether the HMI's manual and automatic selection changes PLC logic or command authority inside the 3RW44. On a Y-link the starter exchanges only cyclic data and takes parameters only through the GSD file, so unless the installed module's communication chapter documents a starter-level mode command, implement the selection in one PLC arbitration routine and gate both command sources with the same permissives.

On this page
  1. Does the HMI button change PLC logic or the starter's command source?
  2. Can a 3RW44 switch its own mode over PROFIBUS at all?
  3. Which GSD file matches your PROFIBUS module?
  4. Where does the manual or automatic decision sit in the PLC?
  5. What does the command-word logic look like in practice?
  6. What happens to the digital inputs when PROFIBUS drops?
  7. How do you verify the bus before trusting any command bit?
  8. So where should the manual mode live?
  9. Questions asked

An HMI button that switches a 3RW44-driven motor between automatic and manual raises one question before any bit gets assigned: does the selection change which PLC routine commands the motor, or does it change the command source the soft starter itself accepts? With the starter under cyclic PROFIBUS control, both answers route through the same telegram, so the decision comes first and the telegram mapping follows from the installed module's documentation, never from a forum note. This article walks the decision, the GSD match, the PLC arbitration logic and the verification in that order.

Does the HMI button change PLC logic or the starter's command source? #

In most installations the HMI selection changes only the PLC logic: with automatic and operator requests travelling through one cyclic PROFIBUS telegram, the 3RW44 keeps a single command source — the PLC — and manual or automatic simply names which PLC routine fills that telegram. Command authority means the source whose start and stop commands the starter currently accepts. A mode selector in the PLC chooses the origin of the command word; the starter never sees the difference, because both origins arrive as the same cyclic telegram. A starter-level mode change would instead reassign the command source inside the device, and that transition exists only where the interface documentation defines it.

Read the required behavior first and place it:

Required behavior Where it lives What defines it
Operator starts and stops from the HMI instead of the sequence PLC arbitration logic Your control program
The starter itself changes operating mode or command source Inside the starter Communication chapter and GSD for the installed module
Local control at the starter's own controls Local and remote handling at the starter Starter documentation

If the answer is the first row, everything that follows is PLC work plus a documented telegram check. If it is the second row, stop until the communication chapter and the GSD for your installed module are in hand. If it is the third, settle local and remote ownership first, because an HMI commanding a starter held in local control is a dead button.

Can a 3RW44 switch its own mode over PROFIBUS at all? #

Only where the communication documentation for the installed interface defines such a command: on a Y-link the 3RW44 behaves as a DPV0 slave, parameter assignment happens only through the GSD file, and only cyclic data is transmitted, with no acyclic writes over the bus. That limitation is the engineering reason the shortcut "set manual or automatic on the first bit" cannot be accepted unchecked. A bit position means something only inside the documented word layout, byte order and configured telegram of your module version, so a bit number quoted without those documents describes some other device. Get the communication chapter that supplements the 3RW44 system manual for PROFIBUS, plus the matching GSD, from the manufacturer's support portal or an authorized distributor. If that pair documents a mode command, use it exactly as written; if it does not, the selection is PLC work.

Which GSD file matches your PROFIBUS module? #

The GSD file must match the product version of the PROFIBUS module fitted to your starter: the manufacturer's GSD index covers 3RW44 PROFIBUS modules of product version E03 or lower, under order numbers of the form 3RW44**-*BC**, and a mismatched file mis-describes the cyclic telegram. A GSD file is the device description the engineering tool uses to configure the station's cyclic data layout, so the wrong file means a command word built to the wrong map. Identify the fitted module, select the corresponding GSD entry in the engineering project, and configure the station with it — the walkthrough for connecting a commissioning tool to a PROFIBUS drive through an S7-300 project covers that configuration step. Set the station address at the starter to the address configured in the project, and keep it unique on the segment. The GSD and the communication chapter are the only sources allowed to define a bit's meaning.

Where does the manual or automatic decision sit in the PLC? #

The decision sits in one PLC arbitration routine: the HMI writes a mode-request variable, the PLC accepts it only when transition conditions permit, and a single routine builds the starter's command word from either the automatic sequence or the operator request, never from both raw. Trace the full path: HMI request, PLC mode logic, PLC output image, starter acceptance, returned status. Show requested mode and accepted mode as separate values on the HMI whenever a transition can be rejected or delayed, so an operator can see that a selection was refused rather than silently ignored.

Inspect every writer of the transmitted command data. If two routines write the same output, whichever runs later in the scan wins, and an HMI selection can be overwritten within one cycle. One routine owns the word; everything else feeds it. The same ownership question governs what happens when the bus starts up, which the article on soft starter PROFIBUS parameter ownership at bus start works through.

What does the command-word logic look like in practice? #

Work the selection on named booleans before touching the telegram: the run command the PLC transmits is the permissive-gated output of the selected source, and three evaluated cases show why the transition itself needs a design decision. The following is an illustrative example with declared inputs, not a measured result.

Example: a 350 kW induced-draft fan runs from the soft starter, and the PLC transmits a run command bit. Declare the variables:

  • HMI_Mode_Manual: BOOL, FALSE in automatic
  • Seq_Start_Req: BOOL, TRUE when the sequence calls for the fan
  • HMI_Start_Req: BOOL, TRUE only while the operator holds the start pushbutton
  • Permissives_OK: BOOL, TRUE when no trip is active, the bus exchange is healthy and the starter reports ready

The logic: Run = ((NOT HMI_Mode_Manual AND Seq_Start_Req) OR (HMI_Mode_Manual AND HMI_Start_Req)) AND Permissives_OK.

Case A, automatic: HMI_Mode_Manual = FALSE, Seq_Start_Req = TRUE, Permissives_OK = TRUE. (TRUE AND TRUE) OR (FALSE AND FALSE) = TRUE, and TRUE AND TRUE = TRUE. The fan runs.

Case B, switch to manual while running with no button pressed: HMI_Mode_Manual = TRUE, Seq_Start_Req = TRUE, HMI_Start_Req = FALSE. (TRUE AND TRUE) OR (TRUE AND FALSE) = FALSE OR FALSE = FALSE, and FALSE AND TRUE = FALSE. The run command drops and the fan coasts to a stop — possibly the opposite of what the process wants on a running fan.

Case C, manual with a seal-in: a hold bit HMI_Run_Hold sets when the run bit rises in manual and resets on a stop command or a lost permissive. Once started, Run = HMI_Run_Hold AND Permissives_OK, so releasing the button keeps the fan running: TRUE AND TRUE = TRUE.

The decision: use Case C unless the process genuinely wants a running fan to stop on a mode change, and write that choice into the transition logic, not into the telegram.

What happens to the digital inputs when PROFIBUS drops? #

The starter's wired inputs do not fall silent when the bus goes down: the documented handling for external signals is to set each input to no action while PROFIBUS is inactive, so wiring states cannot start or stop the motor behind the PLC during a bus fault. What the motor itself should do on bus failure — controlled stop, coast, or another documented response — is a control-design decision to write into the logic and test with the bus deliberately interrupted while the motor runs. Keep hardwired emergency stop and local isolation outside this discussion entirely: they stay wired and functional regardless of the bus.

How do you verify the bus before trusting any command bit? #

Prove the station identity, the configured telegram and the cyclic exchange before you assign meaning to any bit: a bus that looks healthy can still carry a mis-mapped word, and an output that toggles in the PLC proves only that a variable changed. Before opening the starter's compartment or verifying terminal states, de-energize the feeder and test for absence of voltage; NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers the precautions for energized diagnostics you cannot avoid — confirm the local requirements with the authority having jurisdiction and the equipment documentation.

Work through these checks in order: the fitted module identification matches the device configured in the project; the station address matches and is unique; the bus exchanges cyclic data without persistent station or configuration faults. Choose the transmission rate within what the segment length, cable and construction allow, and check connectors and termination — the article on installing a robust PROFIBUS DP network inside an MCC covers the physical side. For first commissioning without the motor connected, the article on testing a soft starter without three-phase power connected shows how far you can get safely.

Then check the mapping: change one PLC output and watch the corresponding starter indication. If the output toggles and the starter indication does not follow, the mapping, the function or the command source is wrong. A telegram can exchange without faults while carrying a mis-mapped word — the article on missing motor current from a PROFIBUS DP telegram shows exactly what that looks like.

So where should the manual mode live? #

Put manual and automatic selection in the PLC unless the communication chapter of your installed interface documents a starter-level mode command, because with one cyclic telegram the starter cannot tell which source asked, and every command path must cross the same permissives. The decision by case:

  • Both sources travel one cyclic telegram and no mode command is documented: implement the selection in one PLC arbitration routine with the Case C seal-in, show requested and accepted mode on the HMI, and keep every path through the same permissives and stop conditions.
  • The communication chapter documents a starter-level mode command for the installed module: use it exactly as documented, and keep the PLC arbitration in front of it anyway.
  • The motor must run from the starter's own controls: settle local versus remote ownership at the starter before any HMI command is allowed to act.

No undocumented bit, no parameter write the telegram does not define, and no HMI path around the permissives — those three lines are the whole decision.

Questions asked

Which documents define the 3RW44 PROFIBUS control and status words?

Request two items from the manufacturer's support portal or an authorized distributor: the PROFIBUS communication chapter that supplements the 3RW44 system manual, and the GSD file matching the product version of the module fitted to your starter. The equipment manual describes the hardware and its terminals; the communication chapter is the document that defines the cyclic control and status words.

Can the HMI write to the soft starter directly instead of going through the PLC?

In this arrangement the HMI and the starter are both stations on the bus, but the clean design keeps the PLC as the only writer of the starter's command word. The HMI writes a request to the PLC, the PLC arbitrates permissives and transitions, and one routine transmits the result. A direct write from the HMI would bypass the permissives and the arbitration.

What should the motor do when the PROFIBUS cable breaks during manual running?

That is a control-design decision to write into the logic before commissioning, not a starter default to accept after the fact. Define a bus timeout behavior, choose a controlled stop or another documented response, and test it with the bus deliberately interrupted while the motor runs, so the response is proven rather than assumed.

Does the same approach apply to the 3RW55 soft starter series?

The 3RW55 is a different series with its own communication modules and its own control and status word definitions, so its manual and automatic handling is answered by that series' communication manual, not by 3RW44 documents. The PLC-side arbitration logic carries over unchanged; the telegram layout does not.

Does the no-action input setting disable the starter's digital inputs entirely?

No. It only changes what an input does while PROFIBUS is inactive, so a wiring state cannot move the motor during a bus fault. Hardwired emergency stop and local isolation stay wired and functional in every mode; the setting affects command-level inputs, not safety-relevant wiring.

Keep reading

  • Explainer

    How a 3RW55 soft starter selects one control source

    A 3RW55 soft starter accepts start and stop commands from only one selected control source at a time. Treat the PROFINET port, the panel On/Off station and the High Feature HMI as mutually exclusive sources: only the selected one may request a start, and a fresh start action is required after every source change so a maintained run request left behind cannot restart the motor.

    Motors and motor starters

  • Explainer

    Soft starter PROFIBUS parameter ownership at bus start

    With the starter's 'Parameters disabled CPU/Master' parameter at its factory Off setting, the HW Config values overwrite locally entered parameters every time the bus starts. No SFB 53 call is needed for cyclic commands and status; SFB 53 (WRREC) into data sets 131, 141 or 151 is only for changing parameters from the PLC program at runtime.

    Motors and motor starters

  • Selection guide

    Which soft starter control mode fits each load type

    Pumps get torque control with a controlled stop, fans and compressors get a current ramp with the limit near 3.5 times nameplate full-load current, and conveyors get a current ramp with soft deceleration. Choose the mode from the load's failure mode, then confirm the result with a measured start and stop.

    Motors and motor starters

Why a soft starter trips control voltage above 110% on a generator