Explainer

Soft starter PROFIBUS parameter ownership at bus start

Motors and motor starters Published 5 min read By Current Intel engineering team

Short answer

With the starter's 'Parameters disabled CPU/Master' parameter at its factory Off setting, the HW Config values overwrite locally entered parameters every time the bus starts. No SFB 53 call is needed for cyclic commands and status; SFB 53 (WRREC) into data sets 131, 141 or 151 is only for changing parameters from the PLC program at runtime.

On this page
  1. One switch decides parameter ownership
  2. Cyclic commands and status need no record blocks
  3. Worked example: locating the motor-running bit when the input area begins at byte 320
  4. PS1 and writes from the program
  5. The decision for each case
  6. Questions asked

You do not need SFB 53 in your user program to run a soft starter over PROFIBUS. Two mechanisms share the cable and must not be confused: the cyclic process image, which carries commands and status every scan through ordinary I/O access, and parameterization, which happens when the bus starts. One setting on the starter decides who owns the parameters: with "Parameters disabled CPU/Master" at its factory Off position, the values stored in the HW Config GSD object or in the Object Manager overwrite everything entered at the starter display at every bus start. SFB 53, the WRREC record-write service aimed at parameter data sets 131, 141 or 151, is only for changing parameters from the PLC program while the plant runs. The reference throughout is the SIRIUS 3RW44 equipment manual, edition 06/2016.

One switch decides parameter ownership #

A GSD file is the device description that lets HW Config integrate the starter as a PROFIBUS slave. What you enter on that GSD object, or in the Object Manager, is startup parameterization: values held by the CPU and pushed to the starter when the bus starts, separate from the command and status data exchanged cyclically. The starter's "Parameters disabled CPU/Master" parameter gates that push.

Setting What happens at bus start Choose it when
Off (factory) The CPU/master values overwrite the parameters on the starter the project owns the values, or the program must write parameters
On CPU/master parameterization is blocked; local values stay you commission at the display and the values must survive restarts

Two consequences follow. A ramp time or current limit entered at the display and tested successfully proves nothing until the bus has restarted once with your setting in place: with the factory Off position, the next CPU restart, power cycle or hardware download hands the value back to the project. And local hardware settings are a different layer again — the DIP switches covered in Soft starter DIP switch start mode settings and what each one does are read by the starter itself and are not part of this data traffic — so judge an overwrite only after checking where a value actually came from.

The decision is one owner per starter. If the crew commissions at the display, set the parameter to On. If the project is the record, leave Off and maintain every value in HW Config — the current limit chosen as in Setting a soft starter current limit without overheating the motor is one of them. Make the change and its verification restart with the machine stopped and locked out; opening the cabinet to reach the display is covered by your site's electrical safety procedure — for US practice NFPA 70E, 2024 edition, the standard for workplace electrical safety — so confirm the steps with the safety officer and the equipment documentation before the door comes open.

Cyclic commands and status need no record blocks #

Configuring the slave from its GSD file establishes the cyclic exchange; no parameter-write block is needed for it. The areas are named from the PLC's viewpoint: the process image output (PIO) holds the bits the CPU sets — its requests to the starter — and the process image input (PII) holds the bits the starter returns, its status. The bit assignment is chapter 9.7 of the 06/2016 manual; build named variables from that table rather than mapping arbitrary words, because a healthy bus will happily deliver a good command to the wrong bit.

Keep the directions separate in code: a command expresses what the PLC requests, a status reports what the starter actually does. The starter's PCS 7 library, for comparison, resets its command at the end of each block execution cycle, and a trip resets the PIO — if you write your own logic, decide once whether commands are pulses or held levels and apply that consistently.

Worked example: locating the motor-running bit when the input area begins at byte 320 #

Inputs, with their source:

  • First byte of the starter's PII area, read from the address column of the slave in HW Config: 320 here — an example value; your project shows its own number.
  • Motor-running status: PII bit 0.1, the assignment the starter's PCS 7 library help documents, inside the chapter 9.7 layout.

Rule in words: the absolute address of a status bit is the first byte of the area plus the bit's byte offset, with the bit number unchanged. Arithmetic: byte 320 + offset 0 = byte 320, bit 1, so the running status sits at input I 320.1. Result: the PLC variable behind the motor-running lamp decodes that bit and nothing else in the byte.

Decision: verify it in a known stopped state and then in a controlled run before trusting the lamp. The threshold is the kind of quantity, not a number — as long as the HMI needs states, the cyclic image is enough; the moment it needs an accumulated value such as motor on-time, no bit in the image carries it, and you move to the record interface or to PLC-derived timing.

PS1 and writes from the program #

PS1 means parameter set 1: a named group of settings — ramps, current limits, protection values — stored in the starter, not a message on the wire. Three operations get tangled here: editing a set, selecting which set is active, and commanding the motor. Only the first can involve records, and only when the edit must come from the program.

That is the single job of SFB 53, the WRREC service: writing a whole record into the starter. Chapter 9.12.15 of the manual assigns the parameter data sets 131, 141 and 151 to this service; match the set holding your parameter to its record number in that table. Because the record is a structured block and not a single scalar, use read-modify-write: read the record with the record-read service into a data block, change only the intended fields, and write the complete record back, so unrelated settings survive and no uninitialized memory reaches the starter. The call pattern is the same one used for time synchronization over PROFIBUS DPV1 with SFB 53 WRREC.

The decision for each case #

  • Commands and status only: use the cyclic image per chapter 9.7; call no SFB 53.
  • Display-entered values must survive bus starts: set "Parameters disabled CPU/Master" to On.
  • The project is the record: keep the factory Off and maintain every value in HW Config.
  • Parameters must change while running: keep Off and change them with SFB 53 (WRREC), a full-record read-modify-write into the data set chapter 9.12.15 assigns — 131, 141 or 151.

Questions asked

When exactly does the master overwrite the starter's parameters?

Only when the bus starts and the CPU parameterizes its slaves — after a CPU restart, a power cycle or a download of the hardware configuration. Between bus starts nothing is pushed, so a display change can look stable for days and then revert at the first restart. That delay is why the overwrite is so often misread as a random fault.

With the setting at On, can the PLC still change parameters at runtime?

No. On blocks CPU/master parameterization completely, and a record write from the program is master parameterization. Choose one owner: the project owns the values (keep Off, maintain them in HW Config, write records when needed) or the starter owns them (set On, change them at the display, accept no programmatic writes).

How do I show motor on-time on an HMI?

No bit in the cyclic image carries accumulated running time. Check the starter's documentation for a record or diagnostic value that holds operating hours; if none is available, derive the hours in the PLC from the running status bit with a retentive counter, label the number as PLC-derived, and define when it resets and whether it survives a memory reset.

Keep reading

  • Troubleshooting

    Fixing a soft starter phase loss fault after a voltage change

    Set the soft starter's mains voltage parameter to 400 V and its motor rated current to the pump's 400 V nameplate value. The phase-loss monitor compares each phase with the programmed reference; at 400 V on a 690 V setting every phase reads about 42% low, past the documented 15% drop threshold, so the starter trips loss of phase even with all phases present.

    Motors and motor starters

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • Troubleshooting

    Why a soft starter barely improves utility bus voltage dip

    On a fixed-impedance screening calculation, cutting starting current from 600% to 400% scales a 10% utility-bus dip to about 6.7%, so a modeled 2-point gain signals a study-method or data problem, not a soft-starter fault. A 10% dip on a shared medium-voltage feed also exceeds the roughly 5% planning ceiling utilities apply at the point of common coupling. Keep the starter for the motor and the mechanical train; fix the study, then the supply, before ruling the starter out.