Soft starter DIP switch start mode settings and what each one does

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

Soft start ramps voltage up with an initial-torque pick, current limit caps starting current at a chosen percentage of nameplate FLA, kickstart adds one short high-current pulse for stuck shafts, and soft stop ramps voltage down at one to three times the start time. On 3–37 A frames every start-time choice stops at 15 s; match the mode to the load and change one switch group at a time.

On this page
  1. Which start mode does each load need?
  2. What does the soft start setting actually set?
  3. How do you turn the current-limit percentage into amps?
  4. When does a shaft need the kickstart pulse?
  5. How long can the ramp run on your frame?
  6. What does soft stop actually stop?
  7. Which symptom points at which switch?
  8. How do you change a setting and prove the start?
  9. Questions asked

Four documented settings decide how an Allen-Bradley SMC-3 soft starter brings a motor up and lets it coast down: the start mode (soft start or current limit), the start ramp time, the optional kickstart pulse and the soft-stop ramp-down multiple. Match the mode to the load first, set the time or percentage second, and change one switch group at a time, verifying with a start under the motor's real load. The start-time list is shortened on the small 3–37 A frames, and the switch assignments changed between series, so positions copied from an older unit or a larger frame will not produce the settings you expect. The literature counts five start and stop modes and documents the four below; the fifth's settings belong to the installation instructions for your catalog number, and every value here is specific to this family rather than to soft starters in general.

Which start mode does each load need? #

Take soft start for loads that only need a gentler voltage ramp, and current limit only when the supply constrains the current a start may draw; the limit choices are 150, 250, 350 and 450% of the motor's nameplate FLA, and dip switch 3 selects between them.

Soft start is the general-purpose mode: the starter raises motor voltage from the initial-torque level to full voltage across the ramp, which suits pumps, fans, conveyors and anything that needs starting stress reduced rather than current capped. Current limit exists for the constrained supply, a generator, a long feeder or a transformer already loaded, where a ceiling on amps is the point. When current reaches the limit, the starter stops raising voltage and holds until the current falls back under it, then resumes the ramp.

If nothing constrains your supply, current limit buys nothing and costs torque: the lower the ceiling, the less accelerating torque the motor develops and the longer it sits at high slip current. For the load-type side of the decision, conveyors against pumps against crushers, the article on which soft starter control mode fits each load type matches modes to loads; this one stays with what the switches set.

What does the soft start setting actually set? #

Soft start raises the motor from an initial torque level to full voltage over the ramp time: the initial-torque positions are 15, 25, 35 or 65% of locked-rotor torque, and dip switches 1, 2 and 8 program the ramp time from the 2 to 30 s list.

Treat those as two separate questions. Initial torque decides whether the shaft breaks away at all; ramp time decides how fast voltage climbs toward full. Ramp time is a voltage schedule, not a promised acceleration duration: a fan that reaches its torque balance early finishes the start before the ramp ends, and a load that never reaches balance stalls no matter how long the ramp is.

Start the initial torque low and step up only if the shaft will not turn: if it never breaks away, move the torque position up one step or clear the mechanical problem first. If it turns but takes too long, lengthen the ramp one position at a time, within the list your frame actually offers. That list has a catch on small frames, and it is the next thing to check.

How do you turn the current-limit percentage into amps? #

Multiply nameplate FLA by the percentage and divide by 100: for a motor with 20 A on its nameplate, the 350% position gives 20 × 350 ÷ 100 = 70 A, so the starter holds acceleration at or below that ceiling.

The inputs are a hypothetical example, a three-phase motor at 460 V with 20 A on the nameplate and current-limit mode selected at 350%, and the arithmetic is setting math: a ceiling estimate to confirm against the measured start, not a universal figure. What moves it: the percentage scales the ceiling in proportion, so the 250% position on that same motor is 20 × 250 ÷ 100 = 50 A, and nothing means anything until the percentage multiplies the real nameplate FLA rather than the starter's frame rating.

Two consequences follow. If the load cannot finish accelerating under the ceiling, extending the ramp time does not raise it; the motor stalls against the limit, the failure the article on why a large motor stalls when the soft starter hits current limit dissects. And a low ceiling stretches the time the motor spends at high slip current, so setting a soft starter current limit without overheating the motor is its own balancing act.

Keep the protection roles straight as well: the current limit shapes the start and protects nothing; the electronic overload dialed to the nameplate protects the motor; and branch-circuit short-circuit and ground-fault protection is a separate device that NFPA 70, the National Electrical Code, 2023 edition, covers for motor circuits in Article 430. Confirm the installation with the authority having jurisdiction and the starter's documentation.

When does a shaft need the kickstart pulse? #

Only when the load will not begin rotating: kickstart injects one 450% FLA current pulse at the start of the ramp, adjustable from 0.5 to 1.5 s, giving a short torque boost for breakaway.

The pulse sits at the front of whichever start mode is selected, an add-on rather than a separate way through the ramp. Its one job is breakaway: a crusher packed after a shutdown or a conveyor parked under load sometimes will not start turning on the ramp's opening voltage, and the pulse gives one high-torque shove to get the shaft moving.

It is not a cure for slow acceleration: slow acceleration needs more torque across the whole ramp, which means the initial-torque position, the ramp position or the limit ceiling. A pulse at the front changes nothing about the last half of the start. And on a supply that already sags during starts, the pulse pulls its maximum current at the worst moment for the bus.

How long can the ramp run on your frame? #

On 3–37 A frames the start-time list is 2, 5, 10 and 15 s for both soft start and current limit; the 20, 25 and 30 s positions documented for larger frames do not exist on them.

The manufacturer annotates both start-time lists with that small-frame restriction, so the longest ramp a unit of that size offers is the 15 s position. A recipe transcribed from a larger starter's sheet lands wherever that count maps on the small frame, not on the position you copied.

The assignments themselves also changed between series: positions that produced one setting on an older SMC-3 map differently on a Series B frame, which is a common cause of a starter that sits idle after a swap. The walkthrough of resolving an SMC-3 no-start caused by the Series B DIP switch settings covers that exact failure. Before trusting any position you did not set yourself, read the switch legend for your frame, printed inside the unit or in its installation instructions.

What does soft stop actually stop? #

Nothing mechanical: soft stop ramps the voltage down at one, two or three times the starting time, and the motor stops only when the load torque exceeds the motor torque at that falling voltage, so a high-inertia load coasts past the end of the ramp.

The documentation is explicit that the motor stops when load torque exceeds motor torque at the reduced voltage: the multiple extends the coast, it does not control it, and it never applies braking torque the way a drive's controlled deceleration does. Enable it where an abrupt cut shocks the process and an extended coast to rest is what the process wants.

The multiple multiplies the selected starting time, so a frame capped at the 15 s start position tops out at 3 × 15 s = 45 s of voltage decay. If the process needs the shaft stopped within a definite time, the ramp cannot promise that; that is a mechanical brake's job.

Which symptom points at which switch? #

Read the behavior first: a shaft that never breaks away points at initial torque or the kickstart position, slow acceleration points at ramp time or a low current limit, and a coast longer than the process allows points at the soft-stop multiple or plain load inertia.

Symptom What it points to Next check
Shaft never breaks away Initial-torque position too low, or kickstart not enabled Step the torque up one position; enable kickstart only for a genuine breakaway problem
Turns, but acceleration is too slow Ramp position too short, or the limit ceiling too low for the load Time the start; compare running current with the limit percentage
Motor stalls partway with current pinned at the limit Ceiling below the torque the load needs to finish Raise the limit one position, or return to soft start if the supply allows
Coast-down longer than the process allows Soft-stop multiple, or plain load inertia Check the multiple; time the actual coast and compare
Start behaves differently after a swap or rebuild Copied positions on a different frame or series Verify every position against the legend for that frame

Match the symptom before you move a switch, because a trip is information the switches may not be asking for.

How do you change a setting and prove the start? #

De-energize, lock out and verify absence of voltage before you open the starter, then change one switch group at a time, restore power and start under the motor's normal load, timing the acceleration and the coast-down against what the process actually needs.

  1. Record the nameplate FLA and every switch position as found, and set the overload dial to the nameplate value; the article on setting overload relays from motor nameplate full-load current covers that dial.
  2. Change one group at a time: mode first, then ramp time or limit percentage, then kickstart, then soft stop, recording each new position.
  3. Restore power and start under representative load; watch the current against the limit ceiling and time energize-to-full-speed.
  4. Watch the stop the same way: time the coast and compare it with what the process tolerates.
  5. After a trip, reset with the push-to-reset button only after reading the indication; the article on diagnosing a soft starter fault or alarm before resetting it gives the right order.
  6. Leave the configuration sheet with the panel: the next person debugging needs the positions as much as the symptom.

Questions asked

Which DIP switch sets which function on an SMC-3?

On the documented assignments, dip switch 3 selects between soft start and current limit, and dip switches 1, 2 and 8 together program the start ramp time. The remaining functions have their own positions, and the assignments differ between frames and between series, so read the legend inside the unit or the installation instructions for your catalog number instead of assuming an older chart still applies.

How do I convert a current-limit percentage into amps?

Multiply the motor's nameplate FLA by the percentage and divide by 100. A motor with 42 A on its nameplate at the 350% position gets a ceiling of 42 × 350 ÷ 100 = 147 A. Always reference the nameplate FLA, never the starter's frame rating, and treat the result as a setting target to confirm against the measured start current.

Is the kickstart pulse hard on the motor?

Used for its designed purpose, a short pulse to break a stuck shaft loose, it is a documented function rather than an abuse. The concern is repetition: each pulse runs the motor and the starter near 450% of FLA and adds heat with little accelerating progress if the shaft is already turning. When a load needs more than a momentary boost, the fix is the torque source, meaning the initial-torque position, the limit ceiling or the starter size, not a longer pulse.

Does soft stop brake the load?

No. Soft stop only shapes the voltage on the way down, at one to three times the selected starting time; the motor coasts once load torque exceeds motor torque at that reduced voltage, and inertia carries it from there. If the process needs the shaft stopped within a definite time, that requires a mechanical brake or a drive with controlled deceleration, because a ramp multiple cannot promise a stopping time.

Why does my starter act differently after I copied the switches from an older unit?

Two documented reasons: the switch assignments were revised between series, so identical positions do not produce identical settings on a newer frame, and the small 3–37 A frames shorten the start-time list, so a copied long-ramp position has no equivalent there. Note the frame and series marked on the label, then verify every position against the legend or installation instructions for that specific unit.

Keep reading

  • Selection guide

    Which soft starter control mode fits each load type

    Pumps get torque control with a controlled stop, fans and compressors get a current ramp with the limit near 3.5 times nameplate full-load current, and conveyors get a current ramp with soft deceleration. Choose the mode from the load's failure mode, then confirm the result with a measured start and stop.

    Motors and motor starters

  • Explainer

    Converting a 350 kVA soft start limit to starting current

    A 350 kVA soft start limit is about 421 A of line current at 480 V: divide 350,000 VA by √3 × 480 V. The figure is apparent power, so no power factor enters the conversion, and it carries no duration — that comes from the torque-speed margin. The 12.5 kV fuse is a coordination problem; motor protection belongs at 480 V.

    Motors and motor starters

  • How-to

    Setting a soft starter current limit without overheating the motor

    Set the soft starter current limit from the accelerating torque the load needs, not from the starter's duty figure. Estimate the limit as locked-rotor current times the square root of required torque over locked-rotor torque, check that current, dwell time and starts per hour against the starter's duty table, then verify every start with a measured peak current and acceleration time. At a 300% limit a typical design B motor develops only about a third of its full-load torque.

    Motors and motor starters