How a 3RW55 soft starter selects one control source

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A 3RW55 soft starter accepts start and stop commands from only one selected control source at a time. Treat the PROFINET port, the panel On/Off station and the High Feature HMI as mutually exclusive sources: only the selected one may request a start, and a fresh start action is required after every source change so a maintained run request left behind cannot restart the motor.

On this page
  1. What a control source is on a 3RW55
  2. Mapping the three requested sources
  3. The hazard: a run request left behind at transfer
  4. Selecting the source and transferring authority
  5. Network commands, feedback and loss of communication
  6. The decisions, in one place
  7. Questions asked

A 3RW55 soft starter answers to one control source at a time. The equipment manual says it in the operating-mode chapter: in Manual - local operation, master control rests with a source directly on the starter, and the two sources it names are the digital inputs and the 3RW5 HMI High Feature; the input-controlled and network operating modes instead hand the command to the assigned path. That single fact settles the three-way request — a PLC over PROFINET, a panel On/Off pushbutton station, Start/Stop on the High Feature HMI. Build it as three sources with explicit authority selection, never as three parallel start paths: only the selected source may request a start, every source change clears whatever run request the previous source left behind, and the next start needs a fresh operator action. The sections below do the mapping, the interlock evaluation and the commissioning order.

What a control source is on a 3RW55 #

A control source is the interface whose operating commands the starter accepts right now. Selecting it and issuing a start are separate acts: the operating mode names the master, and only the master's start and stop requests run the motor. A connected network cable proves a link and an illuminated HMI proves power; neither proves authority.

The documented modes line up like this. Manual - local operation gives master control to a source directly on the device and names exactly two: the digital inputs and the 3RW5 HMI High Feature. The input-controlled variants — Manual operation local - Input controlled and Automatic operation - Input controlled — put the wired inputs in command in either manual or automatic operation. Network command authority belongs to the network operating mode, configured through the PROFINET FDI V2.0 tooling that documents this starter family with PROFINET. Quote the mode names from the manual matched to your device and firmware revision, because the logic below depends on them.

Mapping the three requested sources #

The three requested paths land on the documented modes as follows.

Requested source Command path Operating mode that gives it authority What shows the authority took effect
PLC over PROFINET Control and status words in the cyclic process data The network operating mode, configured with the PROFINET FDI V2.0 tooling Starter status feedback follows accepted commands; bus diagnostics clean
Panel On/Off station Wired digital inputs Manual operation local - Input controlled, or Automatic operation - Input controlled Input indications track the buttons
High Feature HMI Start/Stop on the 3RW5 HMI High Feature Manual - local with the HMI as the direct source The HMI accepts its commands and shows local control

Wire the panel station to the digital inputs as the 3RW55 control wiring and overload setup sets out, and settle one design point before commissioning: the two local sources share Manual - local, so the panel station's run request should be enabled only while the HMI is not the commanding local source. One live local request at a time is your logic's job — the same one-at-a-time pattern as PLC motor interlock logic for three one-at-a-time motors.

Keep two vocabulary items apart. Selecting the control source decides who may command the starter. Selecting the starting mode decides how the voltage rises to line, and which soft starter control mode fits each load type is a separate decision with its own guide.

The hazard: a run request left behind at transfer #

The failure to design against is not wiring; it is a maintained request surviving a change of authority. Say the network holds command, the PLC run-request bit is TRUE, and the operator moves control to the HMI. The starter does gate commands by mode — an interface that is not the master does not run the motor — but a commissioning design treats that gating as the second line of defense, not the only one. The decision: a restart interlock. A start is permitted only when the selected source matches the requesting source, a fresh start action exists, and no fault is active; any source change clears the fresh-start flag, and no maintained request may ever set it.

The interlock evaluated with real values #

The variable names below are illustrative engineering names, not device parameters; device-side settings keep the names the manual gives them. The initial values show the moment of transfer — authority moving from the network to the HMI while the network's request is still present.

SourceSelected    : INT  := 2      // 1 = panel inputs, 2 = High Feature HMI, 3 = network
SourceRequesting  : INT  := 3      // source whose request is currently present
RunRequestNetwork : BOOL := TRUE   // maintained request left over from network operation
StartEdge         : BOOL := FALSE  // momentary operator Start press, edge only
FreshStart        : BOOL := FALSE  // set only by a Start edge, cleared by any source change
FaultActive       : BOOL := FALSE

StartPermitted := (SourceSelected = SourceRequesting) AND FreshStart AND NOT FaultActive;

Evaluation at transfer: 2 = 3 is FALSE, and FALSE AND TRUE AND TRUE = FALSE, so StartPermitted is FALSE. The leftover TRUE request cannot start the motor, and two independent conditions block it: the source mismatch and the cleared fresh-start flag.

Same selection, still no press: 2 = 2 is TRUE, but FreshStart is FALSE because a maintained request never sets it, so TRUE AND FALSE AND TRUE = FALSE. The starter stays stopped until someone acts.

The operator presses Start: the edge sets FreshStart TRUE for that scan, so TRUE AND TRUE AND NOT FALSE = TRUE and the start goes through. The only path to TRUE runs through a physical start action on the source that holds authority — that is the whole interlock.

The commissioning test that proves it #

Before any wiring change or terminal work for these checks, de-energize the control circuit, apply lockout and verify absence of voltage; nothing here authorizes live panel work. Then prove the interlock with the motor at rest and the load clear of people. Leave the network run request TRUE, select the HMI and press nothing: the starter must stay stopped. Step through every source change without pressing Start anywhere: the mode changes and no run command results. Press Start only on the commanding source: the starter runs, and a stop command returns it to rest. Any run outside those combinations sends you back to the logic, not to the starter.

Selecting the source and transferring authority #

Selection is a write, not a wiring change. The equipment manual lists the local input-controlled manual operating mode among the functions adjustable only via a user program, so in this arrangement the PLC or the engineering tool performs the change of authority; confirm the supported selection method for your installed starter, communication module and HMI from the operating documentation before assigning terminals or writing logic. Then use a stopped-motor transfer, every time:

  1. Withdraw the outgoing source's run request and let its logic go quiet.
  2. Confirm from the starter's status feedback that the motor is at standstill.
  3. Write the new source's authority and wait for the operating feedback that confirms the new master.
  4. Check the active-source indication against the request; the request and the acceptance are different facts.
  5. Allow only a fresh start action from the new source — the interlock does the rest.

A handover with the motor running is the case the documents behind this article do not cover for this starter family, so treat the stopped sequence as the default; if a process genuinely needs a live handover, the equipment manual for your firmware revision is the reference that settles it. The fresh-start requirement survives either way.

Network commands, feedback and loss of communication #

Configure the controller-to-starter link from the device description for the installed variant; the PROFINET FDI V2.0 package is the documented configuration route for this starter with PROFINET. The cyclic process data carry the control and status words. Parameter traffic — the read and write data sets used in the S7-1500 sample projects — changes settings; it does not hand over command authority or arbitrate between sources. Parameter ownership on a fieldbus is its own trap: at bus start a controller can take ownership of a soft starter's parameters, as the PROFIBUS parameter ownership problem at bus start describes, but owning the settings is still not commanding the motor.

Keep four signals conceptually apart: the mode-selection request, the run request, the starter's readiness and operating state, and the fault indication. A PLC output bit changing state proves only that the program issued a request; starter status feedback proves the starter accepted it. Test network command with Start and then Stop: feedback must follow the accepted commands, and a network start issued while a local source holds authority must produce no run.

Define the loss-of-communication response instead of inferring it from normal stopping behavior. When the controller CPU stops, its outputs take the stop response configured for it — substitute output values — and the 3RW55 CPU stop response and substitute output values walk-through shows what the starter then sees on each command bit. Network restoration is not a start permission: after a reconnect the logic re-selects the source, verifies the active-source indication and waits for a fresh start action, exactly as at any other transfer.

The decisions, in one place #

  • All three paths get wired and commissioned, but the operating mode names one master at a time; design the logic to that rule instead of assuming parallel start paths.
  • Every start passes through source match, a fresh start action and no active fault. Every source change clears the fresh-start flag, and no maintained request may set it.
  • Authority changes only with the motor stopped, verified at standstill, with the active-source indication checked before the next start.
  • Stop is common: the panel Off, the HMI Stop and a network stop all produce the same controlled stop in every mode, and the starter's protective trips stay active no matter which source holds authority.
  • Emergency stop stays outside this arrangement: IEC 60204-1 (2016 edition) treats emergency stop as a machine safety function separate from ordinary operational stops, so it belongs on its own hard-wired circuit that no operating mode can switch away. Confirm the stop category with the machine documentation and the local authority having jurisdiction.

Questions asked

What happens to a start request from the source that is not selected?

Nothing starts. The operating mode gives master control to one source, so a network start command sent while a local source holds authority is not executed, and the same holds in reverse. Treat the unselected source's request as a logic error to alarm on rather than as a second way to start: your interlock should require the source match and a fresh start action before any request counts.

Can momentary pushbuttons hold a run request between source changes?

A momentary button commands only while pressed, so any retention is logic you build: a seal-in contact, a latched bit or a maintained selector. The latched request is exactly the transfer hazard, because it is still set after the source change unless the change edge clears it. Build the interlock so a source change forces the fresh start action, and prove it with the motor stopped.

Can I switch control sources while the motor is running?

The commissioning path this article documents is a stopped-motor transfer: the outgoing run request is withdrawn, the starter reports the motor at standstill, the new authority is selected and verified, and only then is a fresh start allowed. A handover under load relies on behavior only the equipment manual for your firmware revision defines, so treat the stopped sequence as the default and read the manual before attempting one, and expect the fresh-start requirement to survive either way.

Where do I confirm the mode names and settings for my device?

In the equipment manual's operating-mode chapter and the functions chapter under the additional parameters area, matched to your installed device and firmware: the manual names the operating modes, the direct local sources and the conditions for changing them. Check the identification on the starter and any communication module first, because mode names and adjustable paths differ between revisions; a mode name quoted for one firmware generation is not guaranteed on another.

Keep reading

  • How-to

    3RW55 soft starter control wiring and overload setup

    Assign each control input and output function in the 3RW55 local menu, enter the motor nameplate full-load current so the electronic overload trips at 150% of it on its thermal characteristic, and connect the motor's PTC leads to the thermistor input, not as a dry contact. A 40 A motor trips at 60 A.

    Motors and motor starters

  • Explainer

    When one soft starter can start several motors

    Yes, one soft starter can start several motors, but only as NFPA 70, the NEC, 2023 edition, Section 430.87 permits: each motor keeps its own running overload protection, the branch contactors open and close only while the starter's output is at zero, and the permitted starts per hour is one thermal budget shared by every motor on its output. One starter per motor remains the default design.

    Motors and motor starters

  • Selection guide

    Matching a soft starter current range to its power structure

    Match the power structure before anything else: a solid-state soft starter covers 90–520 A and an internal-bypass unit covers 108–480 A, both rated 200–690 V AC at 50/60 Hz. Size the starter so the motor's full-load current sits inside the span for the structure you actually have, then set the start modes.

    Motors and motor starters