Variable frequency drives Published 6 min read By Current Intel engineering team

Short answer

There is no single hertz value at which every VFD-driven motor needs an external cooling fan. The deciding number is the motor manufacturer's constant-torque speed range: about 15 Hz (one quarter speed) for a small 1800 rpm TEFC motor like the 2 hp conveyor unit, falling to roughly 30 Hz for large machines. At 46 Hz continuous on a conveyor, a shaft-mounted fan is adequate if current stays at or below nameplate and a loaded temperature check passes.

On this page
  1. Why frequency alone never sets the limit
  2. The worked case: 2 hp conveyor motor at reduced speed
  3. What the constant-torque range means on the nameplate side
  4. How to verify a motor already running at reduced speed
  5. The decision, by case
  6. Questions asked

The threshold is not a fixed hertz number that applies to every motor. The value that decides is the motor manufacturer's constant-torque speed range: the lowest speed at which that specific motor, with its shaft-mounted fan, can carry full rated torque continuously without exceeding its temperature limit. For a small 1800 rpm TEFC motor, that range commonly reaches down to about one quarter speed, roughly 15 Hz on a 60 Hz motor. Large machines lose it much earlier: by the 200 hp class the full-torque range can be as short as 2:1, which puts the floor near 30 Hz. NEMA MG-1, Part 30, application consideration 30.2, defines this as the portion of the speed range in which the drive can maintain essentially constant torque, and requires the manufacturer to declare it.

For the conveyor case: a 2 hp, 480 V, 3.1 A, 60 Hz inverter-rated motor commanded to 46 Hz continuously does not need a blower on frequency grounds. 46 Hz is 77 percent of nameplate speed, well inside the constant-torque floor reported by the motor maker for this horsepower class. The decision rests on load current and a loaded temperature check, not on the speed reference.

Why frequency alone never sets the limit #

A shaft-mounted fan turns with the motor, so cooling air falls as speed falls, while the motor may still carry full torque-producing current. A common rule of thumb is that fan airflow varies with roughly the cube of shaft speed, so cooling capacity drops much faster than torque capability. The balance point between the two depends on frame size, enclosure (ODP versus TEFC), the fan design and the load: a lightly loaded conveyor at 20 Hz can run cooler than a fully loaded one at 45 Hz.

That is why the below-40 Hz rule you may have picked up is unreliable. It happens to sit near the constant-torque floor of large motors and near one quarter speed of small ones, so it looks right often enough to spread, but it is not a design rule. Treat the number the manufacturer publishes for your frame, enclosure and cooling type as the limit, and treat load and temperature as the test inside it.

Confirm any code-adjacent requirement with the authority having jurisdiction and the equipment documentation, since motor thermal ratings follow the manufacturer's data rather than a universal table.

The worked case: 2 hp conveyor motor at reduced speed #

Inputs, each with its source: 2 hp rating, 480 V, 3.1 A full-load current and 60 Hz nameplate from the motor nameplate; the continuous speed command from the drive's operating display; 1800 rpm base speed from the nameplate; the manufacturer's reported constant-torque floor for this horsepower class.

Rule in words: compare the commanded speed with the manufacturer's constant-torque speed range, then compare the shaft-fan's remaining airflow with the load actually carried.

Arithmetic, written out:

  • Speed ratio: 46 Hz / 60 Hz = 0.77, so the shaft turns at about 0.77 x 1800 rpm = 1380 rpm.
  • Speed margin over the constant-torque floor: the command minus the 15 Hz floor leaves 31 Hz of margin; the command sits at roughly three times the reported floor.
  • Remaining fan airflow, using the cube law: 0.77 cubed = 0.46, so the fan moves about 46 percent of its full-speed air at the command speed.
  • Load check to perform: measure running current and compare with the nameplate current value.

Result: at the commanded speed the motor runs at 1380 rpm, well above the constant-torque floor, with about 46 percent of full-speed fan airflow available.

Decision and threshold: keep the shaft-mounted fan and run the motor self-cooled, provided the measured current stays at or below nameplate current under the sustained conveyor load and a loaded winding-temperature check stays inside the manufacturer's insulation-class limit. Below the manufacturer's constant-torque floor, either reduce the allowed load torque, as described in the live coverage of VFD rated current versus motor full-load starting torque, or fit an external blower.

What the constant-torque range means on the nameplate side #

NEMA MG-1 Part 30 requires the manufacturer to state the constant-torque speed range for a motor used on a drive. In practice you find it in the motor catalog as a torque-versus-speed graph or a stated derate below a given speed, and it differs between ODP and TEFC frames of the same rating. Get the sheet for your exact frame rather than relying on horsepower-class rules of thumb; the one-quarter-speed figure for small 1800 rpm motors and the roughly 30 Hz figure near 200 hp are typical values, not guarantees.

If you are selecting the drive as well, the same motor data feeds the sizing: continuous and peak torque current decide the drive rating, as set out in the article on sizing a VFD from load torque and motor current.

How to verify a motor already running at reduced speed #

  1. De-energize, lock out and verify absence of voltage before opening any terminal box or panel.
  2. Record the nameplate: horsepower, voltage, full-load current, base speed, frequency, enclosure and cooling type.
  3. Obtain the manufacturer's continuous torque-versus-speed or derating sheet for that frame.
  4. Run the conveyor at its normal sustained load and speed command. Measure motor current with a suitable clamp or the drive's own output-current reading and compare it with the nameplate.
  5. Measure winding temperature using the motor maker's specified method and limit, with ambient and load recorded. A short no-load test does not represent all-day conveyor duty.
  6. Compare the measured operating point with the manufacturer's continuous envelope. If current is above rating or temperature exceeds the limit, reduce the load, reduce the duty, or add an external blower sized per the manufacturer's guidance, then repeat the loaded test.

Separate thermal causes from control causes. A conveyor that stops on a flow-control signal or an upstream stop has a logic reason, not a thermal one; check the drive's fault history and the control signal at the moment of the stop before blaming cooling. Load can also change at constant speed: a jammed or dirtier conveyor raises current and heating without moving the speed reference, the same mechanism that makes a blower motor draw double its full-load amps when the duct opens.

The decision, by case #

  • 2 hp, 1800 rpm, inverter-rated motor at 46 Hz continuous: self-cooled, no blower, provided current stays at or below the 3.1 A rating and the loaded temperature check passes.
  • Same motor below the manufacturer's stated constant-torque floor for this class, at full torque: reduce the permitted load torque or add an external blower.
  • Large machine, 100 hp and up, running below roughly 30 Hz at full torque: assume the constant-torque range has ended unless the catalog says otherwise; fit independent cooling or derate.
  • Light load at any speed below nameplate: the current measurement governs; a light load can stay self-cooled well past the full-torque floor.

The external blower requirement follows from load and temperature inside the manufacturer's declared constant-torque range, and frequency is only the first screen. For the conveyor example, the screen passes at the commanded speed and the blower stays off.

This article is not a go-ahead for live work: de-energize, lock out and verify absence of voltage before any measurement that opens the panel or the motor terminal box.

Questions asked

Is there a fixed hertz value where every VFD motor needs a blower?

No. NEMA MG-1 Part 30 defines the constant-torque speed range as a property of the specific motor and drive combination, and each manufacturer publishes that range in its catalog. Small 1800 rpm motors commonly hold full torque to about 15 Hz; large machines may derate below about 30 Hz. The manufacturer's curve for your frame and enclosure type governs.

Why does fan airflow drop faster than motor speed?

A shaft-mounted fan moves air roughly in proportion to the cube of shaft speed. At three quarters speed the airflow is about 0.43 of the full-speed value, so cooling falls off much faster than torque capability does. That mismatch is why load torque and measured winding temperature, not frequency alone, decide whether self-cooling is adequate.

What if the motor draws less than nameplate current at low speed?

Current below the 3.1 A nameplate in the conveyor example is good evidence but not proof: it shows the load is light, yet winding temperature also depends on duty cycle, ambient and enclosure. Verify with a loaded temperature measurement against the manufacturer's insulation-class limit before declaring the self-cooled motor adequate for all-day operation.

Does discolored motor paint mean the fan decision was wrong?

Discolored paint is a physical sign of sustained overheating, and on a self-cooled motor running at reduced speed it usually means the continuous load exceeded the cooling available at that speed. Investigate airflow, measure winding temperature and current under real load, and add an external blower or reduce load as the motor manufacturer's data directs.

Keep reading

  • Selection guide

    Choosing a line reactor or motor reactor for a VFD

    Pick the side first. A line reactor goes between supply and drive input, sized on drive input amps at 3% impedance for transient buffering or 5% for harmonic reduction; a motor reactor goes between drive output and motor, sized on motor FLA, for reflected-wave protection on long shielded leads. The two are not interchangeable.

    Variable frequency drives

  • Explainer

    Running a 450 kW DOL motor on a VFD: what to verify first

    A 3.3 kV, 450 kW motor will start and run on a correctly sized medium-voltage drive, but the Class F VPI insulation is not proven inverter-duty, so get the manufacturer's written withstand against the drive's output before connecting. On DOL, two motors draw 186 A running, 651 A with one starting, 1,116 A with both starting.

    Variable frequency drives

  • Explainer

    Running a standard 480 V motor on a VFD: what to check first

    Yes — a standard Class F 480 V motor can usually run from a matching 30 hp drive without an inverter-duty replacement. Keep the drive-to-motor lead at or under 100 ft or fit the output filter the drive maker's table names, confirm cooling at the lowest continuous speed, and reform the drive's DC bus capacitors if it sat unused for a year or more.

    Variable frequency drives