Short answer

Use the pair impedance spanning the supply winding and the actual faulted winding: P-S or P-T only after confirming from the nameplate which letter is the 22 kV terminal. If the third winding is connected and in the fault path, convert all three pairwise values to one base and build the star equivalent.

On this page
  1. Which winding pair carries the fault-current path
  2. What each pairwise impedance is
  3. Base data to check before calculating
  4. Worked example: fault at the low-voltage bus with an isolated 35 kV winding
  5. Building the full three-winding model
  6. The decision
  7. Questions asked

For a fault on the 22 kV side of a 110/35/22 kV three-winding transformer, use the pair impedance that spans the 110 kV supply winding and the winding that actually is the 22 kV terminal: P-S if S is 22 kV, P-T if T is 22 kV. Confirm that letter assignment from the nameplate before anything else, because the tertiary is not automatically the lowest voltage. If the third winding is connected and sits in the fault-current path, one pair value is not enough: convert all three pairwise impedances to a common base and build the three-branch star equivalent. An open, isolated third winding leaves only the source-to-fault pair in play. The three pairwise values are the (3×2)/2 = 3 short-circuit tests a three-winding transformer is defined by, as described in the documentation on modeling multi-winding transformers.

Which winding pair carries the fault-current path #

Trace the path from the 110 kV supply to the faulted terminal, and map the letters P, S and T to real terminals from the transformer data sheet. Then pick the case:

Confirmed assignment What to use Condition
22 kV is winding S P-S Third winding not connected
Faulted terminal is winding T P-T Third winding not connected
Third winding connected to a load or another system All three pairwise values Build the star equivalent

A recommendation to use P-T without the winding assignment is a coin flip: it is right only if the faulted terminal really is T. This continues the two-winding case covered in the live article on transformer fault current from percent impedance, where a single pair value is the whole story.

What each pairwise impedance is #

Every reported impedance voltage or percentage is a pairwise short-circuit test result: one winding shorted, another energized, the third open. P-S, P-T and S-T are three separate measurements, not three parts of one number. They cannot be added, and none of them alone represents the transformer when all three windings matter.

When all three windings must be represented, convert each pair value to one common base and form the equivalent star branches:

  • ZP = (ZPS + ZPT − ZST) / 2
  • ZS = (ZPS + ZST − ZPT) / 2
  • ZT = (ZPT + ZST − ZPS) / 2

These formulas require the three pairwise values on the same MVA and voltage base. The steps behind that conversion are worked through in a live article on the three-winding to two-winding equivalent circuit derivation.

Base data to check before calculating #

Record the rated apparent power and the voltage base behind each pairwise result, and confirm whether the utility gave you percent impedance or an impedance voltage as a test value. Convert with Zpu = Z% / 100 only after confirming the percent sits on your calculation base. Impedance base in ohms on a three-phase base is Zbase = VLL² / S3φ, and the ohmic value is ZΩ = Zpu × Zbase. Never combine pair values quoted on different bases.

Worked example: fault at the low-voltage bus with an isolated 35 kV winding #

Inputs: transformer 110/35/22 kV, 22 kV confirmed as winding T from the nameplate, 35 kV winding open. Example base values for illustration: 40 MVA rating, P-T impedance voltage 10 percent on that rating, upstream source impedance 0.02 pu on the same base.

The rule: with the third winding isolated, the fault sees only the P-T pair; form the Thevenin impedance and divide the phase voltage by it.

Arithmetic: ZPT = 10 / 100 = 0.10 pu. Zth = 0.10 + 0.02 = 0.12 pu. Zbase at the faulted bus = 22,000² / 40,000,000 = 12.1 Ω. Zth in ohms = 0.12 × 12.1 = 1.452 Ω. Isc = 22,000 / (1.732 × 1.452) = 8,747 A.

Result: about 8.7 kA at the faulted bus. Decision: if the 35 kV winding is later connected to a system, that single-pair number is no longer valid, and the study must be redone with all three pairwise values and the star branches. The decision also follows the source-impedance treatment in the live article on calculating low-side fault current with source impedance.

Building the full three-winding model #

When the tertiary is connected, the procedure is:

  1. Map the three voltage levels to the letters P, S and T from the transformer data.
  2. Convert all three pairwise values to one common base.
  3. Compute ZP, ZS and ZT from the star formulas above.
  4. Connect each branch to its real external network: source at P, and the tertiary branch to its actual load or system impedance.
  5. Form the Thevenin impedance at the faulted bus on that network and apply Isc = VLL / (√3 × |Zth|).

The ohmic value of any branch can be cross-checked independently with Zbase = VLL² / S3φ. How the pairwise test values are measured on a real unit is described in a knowledge-base article on measuring YnYn-D transformer leakage impedance Zps Zpt Zst.

The decision #

Isolated third winding: use the one pair that spans supply and faulted winding, P-S or P-T as the nameplate assignment decides. Connected third winding: all three pairwise values, common base, star branches, external impedances included. If the winding assignment or the test base stays unclear, get the connection diagram and test bases from the utility before releasing the short-circuit result; a result built on an unconfirmed letter mapping is not a result.

Questions asked

Which impedance do the P-S and P-T values each represent?

Each is a pairwise short-circuit test result between two windings with the third open, so P-S is the 110 kV to 35 kV pair and P-T the 110 kV to 22 kV pair when those are the terminal assignments. None of the three numbers alone is the complete transformer equivalent.

What happens if the 35 kV winding is not connected to anything?

An open, isolated winding carries no fault current, so the model collapses to the single pair that joins the supply winding to the faulted winding, and the third value drops out of the calculation.

Can the S-T value be left out when the tertiary is connected?

No. Every one of the three pairwise values feeds the star branch formulas, so leaving S-T out gives wrong branch impedances and therefore a wrong fault current at every bus.

Keep reading

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR

  • Troubleshooting

    Why three single-phase transformers don't add fault currents

    No. Three 75 kVA single-phase units wired as a bank behave as one 225 kVA three-phase transformer for fault duty: take the bank's secondary full-load current and divide by its percent impedance. The 15 kA you get by adding three 5 kA figures is not the three-phase value, because the drawing's figure was a single-phase contribution on a different voltage and fault basis.

    Protection: breakers, fuses and SCCR

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.