Which VFD runs a 10 hp vacuum pump on single phase
Short answer
Run the pump on a 230 V drive in the 15 hp class that its maker documents for single-phase input, qualified by current: the drive's single-phase continuous output current must be at least the motor's 28 A full-load current, and the input current sets the feeder. A static converter cannot carry a loaded vacuum pump, and a rotary converter works but its idler draws power the whole shift.

On this page
- Size by current, not by the horsepower tag
- Static, rotary or drive: which one carries a loaded pump
- What single-phase input changes inside the drive
- Worked example: sizing the drive and feeder for the 10 hp pump on 240 V single phase
- Commissioning the pump on the new drive
- The decision for each case
- Questions asked
Run the pump on a variable frequency drive from the 15 hp class, in the motor's 230 V voltage class, that its manufacturer documents for 240 V single-phase input — and qualify it by current: on single-phase input the drive's continuous output current must be at least the motor's 28 A full-load current. That is the whole answer for one dedicated pump motor. A static converter gets a motor spinning but cannot carry a loaded vacuum pump through a shift, and a rotary converter works but its idler draws current every running hour. This article compares the three routes, shows the input-current check that single phase forces on the design, and works the drive and feeder sizing for the pump.
Size by current, not by the horsepower tag #
Horsepower is shaft output; a drive is rated, wired and protected in amps. One drive maker's sizing guidance makes the point with a nameplate that reads 230/460 V and lists full-load amps of 13.4 on the low connection and 6.7 on the high one — the same motor, twice the current at half the voltage. No horsepower tag can stand in for that plate, so the pump motor's nameplate FLA is the number that enters the drive's motor data.
The code supplies its own current for conductor work: NFPA 70, the National Electrical Code, 2023 edition, Table 430.250 lists full-load currents for three-phase motors, and 430.6 says when the table value applies. Confirm the edition, local amendments and the nameplate with the authority having jurisdiction; the worked example below carries the figures for this pump.
Static, rotary or drive: which one carries a loaded pump #
A vacuum pump is a hard case for cheap conversion: it demands torque to accelerate and then runs loaded for hours, so a converter that only helps a motor break away fails quietly later. Three routes exist; two survive.
| Option | Starts the pump | Runs it loaded for hours | What decides it | Verdict |
|---|---|---|---|---|
| Static converter | Yes, on start capacitors | No — after start the motor sees one phase plus a run capacitor | Run-capacitor sizing for a single load point | Reject |
| Rotary converter | Yes | Yes | Idler and cabinet rating for starting and running current | Works, at the price of idler losses |
| VFD on single-phase input | Yes, on a controlled ramp | Yes | Continuous output current on single-phase input | The choice |
A static converter is built for briefly loaded machines, and the failure it causes on small pumps — current imbalance and overheating — only grows with a 10 hp pump pulling vacuum, as the article on why a static phase converter struggles on small pump motors shows. A rotary converter is legitimate when a whole machine must keep a three-phase bus; for one pump it is a lot of spinning iron, and its idler draws current whenever it runs, which the article on why rotary phase converter idle current is so high quantifies. One dedicated motor is exactly the load a drive is built for.
What single-phase input changes inside the drive #
On single-phase input, one rectifier leg and the DC link carry the entire input current instead of sharing it across three phases — the chain the article on how a VFD works through its rectifier, DC bus and inverter stages describes. The maker's single-phase rating therefore governs: some drives allow single-phase input at full output current, others publish a lower continuous current for it, and a drive with no documented single-phase rating is out, whatever its horsepower tag says. That document-driven derating, not a rule of thumb, is what the article on sizing a VFD for a three-phase motor on single-phase input works through.
Two more documented numbers belong in the specification. The first is the short-time overload current, commonly quoted for 10 s, which must cover the pump's acceleration. The second is ambient: documentation for one single-phase-input drive derates current by 4 % for each 1 °C above 40 °C up to 50 °C — a cabinet at 45 °C would cost 20 % of the rating — so read your drive's own curve and mount it out of the pump's hot exhaust.
Worked example: sizing the drive and feeder for the 10 hp pump on 240 V single phase #
Inputs #
- Motor: three-phase pump motor, 10 hp, nameplate 230/460 V, connected for 230 V (from the pump nameplate at the machine).
- Full-load current: 28 A, the Table 430.250 value for this size at this voltage; the nameplate FLA replaces it in the drive's motor data once you read it.
- Supply: 240 V single phase, measured at the panel.
- Drive frame: 15 hp class, documented by its maker for single-phase input.
- Conductor ampacities: NEC Table 310.16, 2023 edition, 75 °C column.
The rule, in words #
The drive's continuous output current on single-phase input must be at least the motor's full-load current. The single-phase input current is the output apparent power divided by the supply voltage — a floor, since rectifier losses and distorted input current push the real figure up, and the manual's input-current line replaces it. Conductors supplying the drive are sized at not less than 125 % of the drive's rated input current under NEC 430.122(A).
The arithmetic #
Output apparent power, three-phase:
S = √3 × V_LL × I = 1.732 × 230 V × 28 A = 11,154 VA ≈ 11.2 kVA
Single-phase input current, lossless floor:
I_in = S / V_supply = 11,154 VA / 240 V = 46.5 A
Feeder conductors at 125 % (430.122(A)):
1.25 × 46.5 A = 58.1 A, which 6 AWG copper (65 A at 75 °C terminals) covers.
Result and decision #
The drive is the 15 hp frame documented for single-phase input at the shop voltage, with a single-phase continuous output rating of at least 28 A and the input protection device its manual lists. The feeder estimate is 6 AWG copper, to be redone with the manual's input current before wire is pulled; if that figure times 1.25 lands above 65 A, go to 4 AWG.
Decision thresholds: a drive whose single-phase rating row shows less than the motor's full-load current fails — step up one frame. A drive with no single-phase rating anywhere in its documentation fails outright. Only if the manual's input current, at 125 %, exceeds the conductor you can pull does the supply, not the drive, become the problem.
Commissioning the pump on the new drive #
Lock out the drive's input circuit and test for absence of voltage before opening the drive cover or the motor terminal box — the DC bus holds a charge, so keep the wait time printed on the drive label. Parameter entry and the loaded run use the keypad with the door closed.
- Enter the motor nameplate data — voltage, full-load amps, frequency, rated speed — into the drive's motor data group; the parameter numbers differ by model, and the manual names them for yours.
- Set a first acceleration ramp; 10 s is a reasonable first setting for a pump of this inertia. If the drive clamps at its current limit during acceleration, lengthen the ramp until it accelerates cleanly.
- Check rotation against the pump's arrow, changing direction with the drive's direction setting or by swapping two output leads with the drive locked out.
- Load the vacuum table and read the drive's own output-current display: steady current should sit at or below the motor's nameplate amps, and a reading that climbs as the pump warms points at the pump or its cooling, not at drive size.
- Keep the output dedicated to this motor. A drive output is a synthesized motor supply, not a machine bus — transformers and other loads misbehave on it — which is why the article on why a VFD cannot power a whole machine as a phase converter rules it out for the rest of the machine; the article on which loads need a phase converter on a single-phase machine sorts what remains.
The decision for each case #
- One dedicated pump, as here: the single-phase-input VFD in the 15 hp frame. Hand the supplier four lines — documented single-phase input at the shop voltage, single-phase continuous output current at or above the motor's full-load current, a short-time overload rating that covers acceleration, and the listed input protection device.
- The whole machine plus the pump on one conversion: a rotary converter sized by its maker for the pump's starting current, accepting idler losses — or drive the pump separately and convert only the rest.
- A static converter: no, for a vacuum pump that runs loaded.
- A drive whose documentation never mentions single-phase input: no, without exception; choose a different model rather than trying it.
The input-current and conductor figures above are estimates to be checked against the governing code edition and the drive documentation before wire is pulled.
Questions asked
Do I program the drive with the nameplate amps or the NEC table amps?
The nameplate full-load amps go into the drive's motor data, because the drive fluxes and protects that specific motor. The Table 430.250 value is for conductor and protection sizing under the code's 430.6 rule; the two are usually within a couple of amperes, and where they differ each is used in its own place.
Why not buy a single-phase-input drive sized to the motor?
Compact drives built for single-phase input mostly top out around 3 hp. Above that size the practical route is a three-phase drive one frame up whose documentation also approves single-phase supply, because the larger frame is what carries the higher input current. A model whose manual never mentions single-phase input is not approved for it, whatever a listing claims.
What acceleration ramp should I set for the vacuum pump?
About 10 s is a reasonable first ramp; watch the drive's output current while the pump accelerates, and if the drive clamps at its current limit, lengthen the ramp until acceleration is clean. A pump that starts with its inlet open to atmosphere needs a longer ramp than one behind a closed valve, and the whole ramp must stay inside the drive's short-time overload rating.
Can the router's other three-phase loads share this drive's output?
No. A drive output is a synthesized supply for one motor or a matched motor group, with no neutral reference, and transformers, contactor coils and other loads misbehave on it. Keep the drive dedicated to the pump; the machine's remaining loads need their own conversion, typically a rotary converter sized by its maker.
Does the pump motor need an inverter-duty rating for this?
For fixed-speed operation over a short cable, a standard three-phase motor usually runs well on a drive, but confirm the motor documentation allows converter supply, because the switched waveform adds winding and bearing stress. Running far below base speed for long periods is the harder case: the shaft-driven fan slows with the motor and the motor overheats unless it is rated for it.