Why a 24/28 V contactor coil buzzes on a 24 V transformer

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A coil rated 24 V at 50 Hz but 28 V at 60 Hz must see 0.8 × 28 = 22.4 V at its terminals to pick up on a 60 Hz supply. The 96 VA transformer sags to 19.3 V during the coil's 250 VA pickup, so the magnet buzzes below its floor. Re-mount the contactor within 22.5° of vertical and fit an inrush-rated control transformer of at least 100 VA with a 28 V secondary.

On this page
  1. Why does the coil nameplate list two voltages and two frequencies?
  2. What is the minimum voltage that picks this coil in?
  3. Why does the secondary read 23.9 V sealed but collapse during pickup?
  4. How large a transformer does the pickup event need?
  5. Is the 14 and 16 AWG control wiring dropping the voltage?
  6. Does mounting the contactor on its side matter?
  7. Which secondary voltage should the replacement transformer have?
  8. What do I change, and in what order?
  9. Questions asked

The contactor and the pushbuttons are fine: the coil is underfed. The main contactor on a rotary phase converter here carries a coil dual-rated 24 V at 50 Hz and 28 V at 60 Hz, so on your supply the pickup floor is 0.8 × 28 = 22.4 V at the coil terminals. The 96 VA transformer feeding it collapses to 19.3 V while the armature is open, and a magnet that far under its floor can only buzz. Two changes fix it for good: mount the contactor within 22.5° of vertical, and replace the transformer with an inrush-rated control power transformer of at least 100 VA and a 28 V secondary. The measurements, the arithmetic and the mounting limit follow.

Why does the coil nameplate list two voltages and two frequencies? #

Because the coil is one inductance facing two line frequencies: reactance is 2πfL, so at 60 Hz the winding has 20 percent more reactance than at 50 Hz and needs the higher voltage to drive the same magnetizing current. Check it as volts per hertz: 24 V ÷ 50 Hz = 0.48 V/Hz, and the higher rating divided by the higher frequency lands within 3 percent of the same figure, so the two ratings hold flux, and therefore magnetic pull, constant. The same volts-per-hertz logic is behind how a 50/60 Hz dual-rated motor's nameplate holds the V/Hz ratio; the coil is asking for exactly what the motor asks for. Read the nameplate as a coil matched to your line frequency, and the supply stops looking adequate.

What is the minimum voltage that picks this coil in? #

The guaranteed pickup floor is 0.8 times the rated control voltage at your supply frequency: 0.8 × 24 V = 19.2 V at 50 Hz, but 0.8 × 28 V = 22.4 V at 60 Hz, and yours is the higher-frequency system, so the higher floor governs. IEC 60947-4-1 is the product standard covering electromechanical contactors and motor starters of this class; the operating band itself is manufacturer data, and the technical data for this family states 0.8 to 1.1 times the rated control voltage Us, with actual pickup somewhere between 0.5 and 0.8 times rated, so confirm the band for your frame. Design to the guaranteed end: a coil that happens to close at 20 V on a cool morning will not do it hot at low line. Your stalled reading sits 3.1 V under the governing floor, and that deficit is what the buzz is made of. When the coil voltage is proven adequate and the contactor still refuses to close, the mechanical and coil-side causes are worked through in why a motor starter coil has voltage but won't pull in.

Why does the secondary read 23.9 V sealed but collapse during pickup? #

Because pickup is a 250 VA event on a 96 VA transformer while the sealed coil draws 4.3 VA, a ratio near 58 to 1, so the well-behaved sealed reading says nothing about the instant that decides the start. With the armature open the iron circuit is broken by a wide air gap, inductance is low, and since reactance is 2πfL the coil takes a heavy inrush. As the armature seals, the gap collapses, inductance rises, and the current falls to the sealed value: the stable draw the coil settles at once the contacts have closed, the condition that uses the least power. A healthy pull-in spends only a few cycles at inrush, faster than a handheld meter display updates; the stalled reading was visible only because the armature hung open and held the coil at inrush long enough to average. That same event is why an interposing relay welds on contactor coil inrush when its contacts are rated too lightly.

Condition Meter reading Load on the transformer
Transformer unloaded 24.3 V none
Contactor sealed 23.9 V 4.3 VA
Energized, armature stalled open 19.3 V full coil inrush, sustained

Before any lead goes into the enclosure, open and lock out the feeding disconnect and test for absence of voltage at the points you will touch; NFPA 70E, 2024 edition, makes that verification part of establishing an electrically safe work condition, so confirm the method with your site's electrical safety program and the authority having jurisdiction. Then capture the real number:

  1. Clip the meter leads across the coil terminals, not the transformer lugs, and set fast minimum capture (an RMS meter with a minimum-capture mode or a scope).
  2. Close the enclosure, re-energize from outside, and press start.
  3. De-energize again before reading, and record the captured minimum; that value is what gets compared against the pickup floor.

How large a transformer does the pickup event need? #

A control power transformer of greater than 75 VA with a published inrush rating, which means a 100 VA unit in practice, carries this coil, while a transformer with no inrush rating must be sized to carry the pickup load continuously. A control power transformer is built with low impedance for exactly this duty: its datasheet publishes an inrush VA figure or a selection table pairing inrush VA with secondary regulation. A general-purpose, isolation or board-mount transformer is sized for its continuous load, often nothing more demanding than a DC supply, and may not hold voltage through a hard pull-in. The words on a listing prove nothing; the datasheet does. Your measured regulation tells the story: 24.3 V − 19.3 V = 5.0 V, a 20.6 percent collapse at pickup against a 0.4 V change sealed, and in load terms the pickup demand is 250 VA ÷ 96 VA ≈ 2.6 times the transformer's continuous rating.

Transformer type Minimum for this coil Why
Control power transformer with a published inrush rating greater than 75 VA; 100 VA in practice inrush capability is a multiple of the continuous rating
Transformer with no inrush rating 250 VA continuous the continuous rating must equal the pickup demand

Is the 14 and 16 AWG control wiring dropping the voltage? #

Only a little, if the run is short: pickup current is about 10 A, and each 10 ft of 16 AWG run costs roughly 0.8 V at that current, a minor term beside the transformer's 5 V collapse. The arithmetic: pickup current is 250 VA ÷ 24 V ≈ 10.4 A; NFPA 70, the National Electrical Code, 2023 edition, Chapter 9 Table 8 lists 16 AWG copper at about 4.1 Ω per 1000 ft, so a 10 ft run (20 ft of conductor) is 20 × 4.1 ÷ 1000 = 0.082 Ω, and the drop is 10.4 A × 0.082 Ω ≈ 0.85 V. On 14 AWG, about 2.5 Ω per 1000 ft, the same run drops half that. Treat these as estimates to check against the governing code edition and the actual route length, but the conclusion holds: keep the run short, prefer 14 AWG, and expect the transformer, not the wire, to own the sag.

Does mounting the contactor on its side matter? #

Yes: this frame is limited to 22.5° off vertical by its mounting diagram, and on its side gravity pulls the armature away from the magnet, so an underfed coil never closes. Rotating it so gravity helps closes it every time, and that is the tell, not the cure. Gravity is supplying the force the magnet cannot, and it does so in the orientation the diagram marks as not permitted; the buzz stops, the fault stays. The armature's weight is part of the magnet's design, which is why the permitted range exists at all, and one other common IEC line allows up to ±30°, so read your own frame's diagram rather than a rule of thumb. Mount it vertical whether or not the transformer is ever replaced.

Which secondary voltage should the replacement transformer have? #

Pick the 28 V secondary: at your 110 V summer low the lower one makes 22.3 V with no load at all, under the pickup floor before any inrush, and the higher one still holds 25.7 V after a 1 V sag. Secondary voltage scales directly with primary voltage: 24.3 V × 110 V ÷ 120 V ≈ 22.3 V. Run the requirement backward: to hold the floor at the coil with about 1 V of sag, the open-circuit secondary must reach 23.4 V, which needs a line of 23.4 ÷ 24.3 × 120 ≈ 116 V or better, and your line reaches 110 V, so the lower secondary cannot work year-round no matter how big the transformer. At that low line the higher secondary delivers 28 × 110 ÷ 120 ≈ 25.7 V, more than 2 V above the floor after sag, and at a full 120 V line the coil sees its rated voltage, inside the 1.1 × Us ceiling of 30.8 V. That is the transformer to buy: inrush-rated, 100 VA or more, with that secondary.

What do I change, and in what order? #

Two changes and one proof: re-mount the contactor within 22.5° of vertical, install the inrush-rated control transformer specified above with its higher secondary, and confirm the captured minimum at the coil terminals is 22.4 V or better.

  1. Lock out the feeder and verify absence of voltage before the enclosure is opened; read the old coil's nameplate while you are in there, because a coil marked only for the higher frequency at the lower voltage strengthens the case for the new transformer.
  2. Re-mount the contactor in the permitted range off vertical; the gravity-assist orientation stays retired for good.
  3. Install the replacement and size its primary and secondary overcurrent protection for the new unit; the fusing logic for a transformer secondary is covered in how to fuse a dual-output 115/230 V transformer secondary.
  4. Verify on a summer afternoon at your worst line: a captured minimum of 22.4 V or better at the coil, and a clean close from the vertical mounting on every press.
  5. Keep the contactor and the pushbuttons, because neither was ever the fault.

Questions asked

Why did jabbing the start button quickly seem to help?

Point on the wave. The flux an AC coil builds in its first half cycle depends on where on the sine wave the control contacts happen to close, and a quick, clean press also avoids the bounce a slow one produces. Both effects matter only when pickup force is already marginal, so the button was innocent, but the observation was telling you the margin was close to zero.

What should the old contactor's coil marking show when I pull it?

Read voltage and frequency together. The same dual rating confirms the coil was never mismatched, only starved. If it is marked for 60 Hz at the lower of the two voltages, its pickup floor is 19.2 V and the sag alone explains every symptom you saw. Either way the work is identical: correct the mounting first, then replace the transformer.

Would a DC coil and a DC power supply sidestep the whole problem?

Only the frequency half of it. The pickup energy still arrives through the same transformer, and a rectifier fed from the undersized unit inherits the same voltage collapse when the coil energizes, so the transformer sizing does not go away. A DC conversion adds a supply and a coil change to a problem one correctly sized control transformer already solves.

What does an inrush VA rating on a transformer datasheet mean?

It is the secondary load the transformer can deliver for the few cycles a coil needs to seal while keeping its secondary within a stated regulation band, exactly the duty your present unit fails. Match it against the sum of every coil that can pull in at the same instant; a panel energizing two or three contactors together needs those inrush figures added. A listing with no such figure is the one to pass over.

Is the 192 VA transformer I found worth trying instead?

Only if its datasheet publishes an inrush rating that covers the coil's pickup demand, which as a true control transformer at that size it very likely does. Without an inrush figure it is merely a bigger plain transformer: better sag, no guarantee. Its secondary is the lower voltage, which still fails your summer low-line test, so the voltage choice matters more than the extra capacity.

Keep reading

  • Troubleshooting

    Why a motor starter coil has voltage but won't pull in

    Voltage across A1 and A2 with no current flowing proves only that the wiring is intact, not that the coil can pick up. Log the coil voltage during the failed closing attempt: most of these faults are a supply or wiring sag below the coil's pickup window, or a latched overload state that the reset button does not clear. Replace the starter only when the voltage stays inside its window and the unit still refuses to close.

    Motors and motor starters

  • Troubleshooting

    Fixing AC contactor chatter on a loaded 80 HP motor start

    Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.

    Motors and motor starters

  • Troubleshooting

    Why a single-phase motor growls and pulls 5-6x FLA but won't start

    A growl with slight shaft movement at roughly 5-6 times FLA means the motor is energized but has no starting torque, so the start circuit is not in circuit or the stator is damaged. The decisive test is a lead-to-lead resistance matrix on the isolated motor, because external capacitors and relay wiring create continuity paths that mislead.

    Motors and motor starters