How-to
Why a -5% transformer tap overshoots voltage at light load
Short answer
Do not drop to the -5% tap yet. With the primary supply constant, a -5% high-voltage tap multiplies the secondary voltage by 1/0.95, taking a 4300 V light-load bus to about 4526 V, 156 V above the ANSI C84.1 ceiling of 4370 V for a 4160 V nominal. Hold the present tap and change it only when staged load additions pull the bus down to about 4050 V, where the new tap lands near 4263 V, mid-band.

On this page
Leave the tap where it is for now. The study's -5% recommendation describes the plant with every load connected; at today's light load the same connection would put the medium-voltage bus about 156 V past the top of the ANSI C84.1 Range A band and hold the transformer core about 5% above rated flux for as long as the supply stays constant. The workable sequence is the reverse: keep the present tap, bring loads on in stages, log the bus voltage after each step, and move to -5% only when the logged trend reaches the bottom of the band. The sections below give the arithmetic behind that trigger, the staged procedure for an off-circuit or on-load tap changer, and the ratio test that closes the job out.
The band a medium-voltage bus has to hold #
ANSI C84.1, in the 2006 edition cited for these figures, defines Range A service voltages: the band a North American utility plans to hold in normal operation. For a nominal 4160 V system, Range A runs from 4050 V to 4370 V. Your light-load reading of 4300 V sits at 103.4% of nominal, so it is legal, with 70 V of headroom under the ceiling. IEC 60038 (2009 edition) is the IEC-side catalogue of standard system voltages from 1 kV up to 35 kV, and it is the reference where IEC practice applies; ranges differ by country, edition and local amendment, so confirm the governing figure with your utility, the authority having jurisdiction and the equipment documentation. For the background behind how ANSI C84.1 builds its ranges, knowledgebase article on the ANSI C84.1 voltage standard walks through it.
What the -5% tap actually does #
High-voltage taps exist to correct a supply that sits off nominal. The -5% connection takes 5% of the turns out of the primary winding, so with the supply held at nominal the volts per turn rise, and the secondary voltage, the core flux density and the magnetizing current rise with them: by 1 ÷ 0.95, about 5.3%. The design intent runs the other way — that same connection is meant for a supply sitting 5% below nominal, where it brings flux and secondary voltage back to rated. Held on a full nominal supply, it overfluxes the core by about 5.3% and lifts the secondary by the same factor with no change in load.
Before assuming any of these directions, confirm which winding carries the taps; the nameplate tap chart is the record, and how a machine transformer tap chart lays out one leg's connections shows the way one is read. The reason the study wants -5% is the other end of the same physics: at full load, transformer and feeder impedance pull the bus down, and calculating voltage drop through step-up and step-down transformers works that arithmetic through both windings. Full load needs the lift; light load does not.
The -5% tap on a 4300 V light-load bus #
Inputs, each with its source:
- Measured bus voltage at light load: 4300 V, read at the medium-voltage switchgear with part of the plant's load connected.
- Nominal system voltage: 4160 V, the system design value.
- Governing band: 4050 V to 4370 V, the ANSI C84.1 Range A service voltages for this system.
- Tap under consideration: -5% on the high-voltage winding, with the primary supply assumed constant at nominal.
- Tap factor: 1 ÷ 0.95 = 1.0526, derived from the tap designation itself.
The rule in words: secondary voltage follows volts per turn, so connecting a tap with 5% fewer primary turns multiplies the secondary voltage by 1.0526 for as long as the supply holds constant.
The arithmetic:
- Today, before any change: 4300 V against the nominal value gives 1.034, so the bus runs at 103.4% of nominal, and 4370 V − 4300 V leaves 70 V of headroom.
- On the -5% tap: 4300 V × 1.0526 = 4526 V.
- Against nominal: 4526 V divided by the nominal value gives 1.088, about 108.8%.
- Against the band: 4526 V − 4370 V = 156 V above the ceiling.
Result: the -5% tap at today's load puts the bus near 4526 V, roughly 156 V past the Range A ceiling, with the core overfluxed by the same 5.3%.
Decision: hold the present tap. The change becomes correct when the loaded bus falls to the band floor, because the floor value × 1.0526 lands mid-band after the change, with 107 V of headroom under the ceiling. Trigger on the floor, not the ceiling.
Holding the tap until the loads arrive #
Run the additions as a logged, stepped process:
- Record the present tap position and the primary supply voltage at the transformer terminals, and compare the supply with the value the study assumed — a supply different from the study's shifts every prediction below.
- Log the bus voltage with today's connected load and confirm it sits inside the band before anything else is switched on.
- Add load in stages. After each step, let the system settle, record the bus voltage and the transformer loading at the same measurement point, and confirm the reading before the next stage. If the stages come faster than handheld meter rounds allow, an industrial panel PC at the switchgear front, trending the bus between steps, keeps the record continuous.
- Set the trigger: when the trend of the logged steps predicts the next stage will pull the bus down to the band floor — or the study's full-load condition arrives first — schedule the tap change.
- De-energize the transformer, lock out and tag the supply, and test for absence of voltage on both windings before anyone opens the tap compartment; an off-circuit tap changer is never moved with the winding live. Move the link to the -5% position per the tap chart and check the position against the chart's markings. If the transformer has an on-load tap changer instead, no outage is needed: change one step at a time while the secondary voltage is on the low side, and leave the control settled in the new position rather than letting it hunt back.
- Run the turns ratio test on the new position before the transformer goes back (next section).
- Re-energize and confirm the bus reads inside the band at the current load.
Proving the ratio before re-energizing #
With the transformer isolated and the tap in its new position, run a turns ratio test. The nameplate ratio at the rated tap is the reference, and the value to expect on the -5% tap is 0.95 times that rated ratio, because 5% of the primary turns are out of circuit. Confirm the measured ratio agrees within the tolerance your test set or your site procedure specifies. This is the check that catches a misrouted tap link — the kind of error a visual look inside the compartment can miss — before the bus ever sees it. Re-energize only once the ratio checks out, then confirm the bus voltage under load against the band.
Traps that catch tap changes #
- Direction first. Confirm the taps sit on the high-voltage winding; on a unit tapped on the low-voltage side, the same -5% designation moves the secondary voltage the other way.
- The study's tap belongs to the study's scenario. A partially loaded plant has a different optimum — that is exactly what the staged trigger handles — so re-check the study at the actual load before treating -5% as permanent.
- The band travels with the standard. The Range A pair used here is ANSI C84.1 for a North American medium-voltage system; IEC 60038 and local utility declarations govern elsewhere, and editions get amended, so put the governing numbers past the authority having jurisdiction for your site.
- Judge the trend, not one reading. The supply itself swings through the day; log at the same point and at comparable load, or a single reading can flatter or damn a tap position.
Questions asked
Will the raised bus voltage hurt the connected loads?
Check each load's nameplate and data sheet against the ceiling, because tolerance depends on the load class. General-purpose polyphase induction motors are rated per NEMA MG-1 to deliver rated performance across roughly plus or minus 10% of nameplate voltage, though higher voltage brings higher torque and higher inrush current. Lighting, electronic supplies and control power each carry their own narrower tolerances, so no single figure clears the whole bus.
What voltage range do the standards set for a 4160 V system?
ANSI C84.1 defines two ranges: Range A for normal sustained operation and Range B for infrequent, correctable excursions. For a 4160 V nominal system, Range A service voltage runs 4050 V to 4370 V, which is the band this article's arithmetic uses. IEC 60038 lists standard system voltages on the IEC side, and some jurisdictions declare service tolerances as wide as plus or minus 6%; confirm the governing figure with your utility and the authority having jurisdiction.
How do I predict when the bus will reach the tap-change point?
Plot the logged bus voltage against connected load after each staged step. The decline is close to linear over a useful range, so fit the last few readings and extrapolate: when the line crosses the band floor at the load stage you expect to add next, schedule the change. Re-measure after every step instead of trusting the extrapolation past the last recorded point, because load composition changes the slope.
What does overfluxing do to the transformer itself?
Core flux density is proportional to volts per turn, so a -5% tap held on a constant nominal supply runs the core about 5% above rated flux. Magnetizing current, core noise and heating all rise, and the margin to saturation narrows. The nameplate and the manufacturer's documentation state the permitted continuous and short-time overexcitation; the connection has to stay inside those figures for as long as it is held ahead of the load.


