Explainer
Why a delta bank keeps its 1.9 percent impedance
Short answer
Three identical single-phase transformers at 1.9 percent impedance, connected closed delta, give a bank impedance of 1.9 percent on the bank's own kVA base, because the ratio is normalized to a base that grows with the bank. An open delta has no single symmetric value: rate the bank at 57.7 percent of the closed-delta rating and compute fault current winding by winding in ohms.
On this page
- What impedance does a closed delta bank of three identical units have?
- Where does the nameplate impedance number come from?
- Why doesn't adding two more windings change the percentage?
- How much capacity does an open delta bank lose?
- How do you calculate fault current on an open delta bank?
- What happens when the three transformers don't match?
- When does the result stop being safe to trust?
- Questions asked
Three identical single-phase transformers, each with 1.9% impedance on its nameplate, connected closed delta, give the bank an impedance of 1.9% on the bank's own three-phase kVA base. The percentage does not add, divide or average when you combine equal units, because it is a normalized ratio and the kVA base it is normalized to grows with the bank. An open delta behaves differently: removing one winding destroys the electrical symmetry, so the bank has no single impedance percentage, and its fault duty has to be solved winding by winding in ohms. This article covers where the nameplate number comes from, why the closed-delta result never changes, what the open delta does to capacity and to fault current on each line, and where the arithmetic stops being safe to trust.
What impedance does a closed delta bank of three identical units have? #
Three single-phase transformers at 1.9% impedance, connected closed delta, form a bank with 1.9% impedance on the summed three-phase kVA base: three 25 kVA units make a 75 kVA bank whose fault calculations use the nameplate percentage unchanged.
The percentage on the nameplate describes the voltage drop across one winding at rated current, as a share of rated winding voltage. In a delta bank each winding still sees the full line-to-line voltage and carries one unit's share of the load, so nothing about an individual winding changes when two more are wired beside it. What grows is the bank's rating — three times the unit kVA — and the nameplate percentage rides on that larger base without moving. For fault duty the useful form is the inverse: a bolted three-phase secondary fault behind a stiff source draws roughly the nameplate ratio inverted times rated line current, and the worked example below puts that at 4,748 A for a 75 kVA, 480 V bank.
Where does the nameplate impedance number come from? #
The impedance percentage on a transformer nameplate is a measured value, not a design output: the factory short-circuits the secondary winding, applies reduced voltage until rated current flows, and reports the applied voltage as a percentage of rated voltage.
That short-circuit test is one of the tests defined in the IEC 60076 transformer standards, and IEC 60076-5 addresses how short-circuit withstand is evaluated for a given design. There is no design formula that replaces the measured figure, so the nameplate or the factory test report is the authoritative value for every calculation in this article. Two practical points when you read it: the value is quoted at a reference temperature, so units tested at different times can differ slightly without being defective, and the percentage is quoted on the unit's own kVA base, which is what makes the closed-delta arithmetic in the next section work.
Why doesn't adding two more windings change the percentage? #
Percent impedance is winding ohms divided by a base impedance of voltage squared over kVA, and when three equal units go into delta, both the ohms in the circuit and the base they are divided by grow together, so the ratio comes out the same as one unit's.
Concretely: each winding's ohmic impedance is its percentage times V²/S_unit. For a balanced three-phase fault, the delta of three equal winding impedances converts to an equivalent wye of one third that value per phase, while the per-phase base impedance on the bank's rating is also one third of what a single-unit calculation would use on line-to-line voltage. Dividing a one-third by a one-third returns the original ratio. The system sees the same percentage on a base three times larger, which is why three units never make three times the impedance — or one third of it. That trap is covered in more depth in why three single-phase transformers don't add fault currents.
Worked example — illustrative values, not a recommendation; confirm against your own nameplates:
- Inputs: three identical single-phase units, each 25 kVA, 480 V secondary winding, nameplate impedance 1.9%.
- Winding ohms: 0.019 × (480 V × 480 V) ÷ 25,000 VA = 0.019 × 9.216 Ω = 0.175 Ω per winding.
- Rated winding current: 25,000 VA ÷ 480 V = 52.1 A.
- Winding fault current behind a stiff source: 480 V ÷ 0.175 Ω = 2,741 A, about 52.6 times the rated winding current.
- Closed-delta line fault current: √3 × 2,741 A = 4,748 A.
- Cross-check on the bank base: bank rating 75 kVA, rated line current 75,000 VA ÷ (√3 × 480 V) = 90.2 A, and 90.2 A ÷ 0.019 = 4,748 A. The two routes agree.
These are estimates for a source with no impedance of its own; a real service adds utility, transformer and conductor impedance in series and pulls the number down.
How much capacity does an open delta bank lose? #
Two of the three units, reconnected as an open delta, deliver √3 times one unit's rating, which is 57.7% of the closed-delta bank: the 75 kVA example becomes a 43.3 kVA bank when one transformer is removed.
The mechanism is current, not voltage. In open delta the line current equals the winding current at full load — there is no third winding to share a phase — so both remaining units sit at rated winding current when the bank delivers its full open-delta output. Loading the bank above that figure overheats both survivors, because winding heating follows current squared. The same asymmetry that caps capacity also makes motor starting the hardest case on an open bank, which is what what decides if an open delta bank can start a 25 HP motor works through. Note too that the open bank delivers 86.6% of the sum of its two nameplates — the loss is not proportional to the winding removed.
How do you calculate fault current on an open delta bank? #
An open delta has no single symmetric impedance percentage on the bank rating, so solve the two windings in ohms: behind a stiff source each winding delivers about 52.6 times its rated winding current, and the common line, fed by both windings, carries √3 times that, about 91.1 times.
Each winding still limits its own current to winding voltage divided by winding ohms — 2,741 A in the worked example — but the three lines do not carry it equally:
| Line | Fault current in the example | Basis |
|---|---|---|
| The two lines fed by a single winding each | 2,741 A, 52.6 times rated winding current | winding ohms, winding voltage ÷ winding ohms |
| The common line fed by both windings | 4,748 A, √3 × 2,741 A and 91.1 times rated winding current | vector sum of the two winding currents |
Taking a single symmetric percentage on the open-delta rating misses that spread entirely. The assumptions behind the numbers are: a source with negligible impedance, identical units, a bolted fault, and open delta on both the primary and secondary sides. Upstream impedance reduces all three values, and the reduction is worked step by step in transformer fault current from percent impedance at the terminals and in calculating low-side fault current with source impedance. Voltage drop under normal load is unbalanced the same way, differing between the three phase pairs.
One safety step belongs here: before opening any terminal compartment or splice box on the bank to compare measured currents or drops, de-energize it, lock it out and verify absence of voltage with a tested meter.
What happens when the three transformers don't match? #
Unequal units break the tidy closed-delta result: the lowest-impedance unit takes more than its share of both load and fault current, so convert every unit to ohms, or to one common kVA base, before combining anything.
The conversion to a common base is Z_new = Z_old × (S_base ÷ S_unit) × (V_unit ÷ V_base)², with Z, S and V in consistent units. Once converted, unequal impedances in a delta drive circulating current inside the loop and unequal load sharing between units, so a single percentage no longer describes the bank — solve the delta network phase by phase. In service, mismatched units show up as line-to-line voltage drops that differ between the three phase pairs at a known load current, so comparing those drops against each unit's nameplate current is the cheapest field check.
When does the result stop being safe to trust? #
Stop and involve the transformer manufacturer's engineering group or the serving utility before energizing when a computed fault current exceeds the interrupting rating of a fuse or breaker in the path, when the bank runs open delta or with unequal units, or when measured voltage drops disagree with the calculation.
The code side is concrete: NFPA 70, the National Electrical Code, 2023 edition, requires installed equipment to be protected against the available fault current where it is located and calls for that value to be determined and marked on service equipment — confirm exactly what your authority having jurisdiction enforces and what the equipment labels state. Every figure in this article is an estimate built on the stiff-source assumption; the authoritative inputs are the nameplate and factory test report, and the duty at the actual terminals is lower once source and conductor impedance are added. If the duty at a device exceeds its rating, do not energize the bank; send the nameplates, the test-report impedance values and the upstream source data for review before re-energizing.
Questions asked
What happens if I add the three impedance percentages together?
You get 5.7%, which overstates the bank impedance and makes the computed fault current roughly one third of the real value. The nameplate percentage is a normalized ratio on each unit's own kVA base, so three equal units in closed delta stay at 1.9% on the bank's summed base.
One unit fails - what does the bank deliver as open delta?
Capacity falls to 57.7% of the closed-delta bank, the square root of three times one unit's rating; in the 25 kVA example that is 43.3 kVA. Each remaining winding runs at rated current at that output, so sustained load above it overheats the two surviving units.
Can the closed-delta percentage be used for open-delta fault duty?
It hides the line asymmetry. Under the stiff-source assumptions, the common line carries about 91.1 times rated winding current while the other two lines carry about 52.6 times, so the open bank must be modeled as two winding impedances in ohms and each line solved separately.
Do slightly different nameplate percentages or test temperatures matter?
Small differences unbalance the bank even in closed delta: the lower-impedance unit loads first and the loop can carry circulating current. Convert each unit to ohms on its own winding voltage before combining, and compare line-to-line voltage drops between phase pairs at a known load current as the field check.