Troubleshooting
Why a line module buzzes with regenerative feedback enabled
Short answer
Treat a buzz that continues after pulse enable as an enable-sequence or line-component problem, not a normal condition. Wire the module's EP input so it switches together with the 400 V AC mains contactor, confirm the matched line filter and line reactor by order number, and keep regenerative feedback enabled: disabling it lets the DC link rise during deceleration and the motor module can drop the motor.
On this page
- Is a buzz from the line module a fault or a normal sound?
- What does the EP input do on a Smart Line Module?
- When must EP switch relative to the 400 V AC contactor?
- Which line filter and line reactor match a 10 kW Smart Line Module?
- What should I check before re-enabling the drive?
- Can I run with regenerative feedback disabled?
- How do I re-commission and confirm the fix?
- What is the decision for each finding?
- Questions asked
A buzz from a Smart Line Module that continues after pulse enable is a commissioning symptom, not a normal operating sound. The two documented causes to eliminate are the enable sequence and the line components: the module's EP input must switch together with the 400 V AC mains contactor through the same disconnect, and the line filter and line reactor must match the module's power class by order number. A sound only during precharge is a different finding — a comparable installation reports exactly that, with quiet running afterward. Whatever the timing shows, regenerative feedback stays enabled: the disable switch silences the feed-back path but lets the DC link climb during deceleration, and the motor module can then disconnect its motor while the machine is still moving.
Is a buzz from the line module a fault or a normal sound? #
Sort the symptom by timing: a sound only while precharge runs matches a comparable installation that is quiet in normal operation, while a buzz that continues after the module has enabled is not documented as normal for this module family anywhere in its commissioning material. Precharge is the controlled charging of the DC link capacitors at power-up, so a brief noise there comes from a defined operating state. The reported machine enables and runs correctly, and the sound appears when EP closes and disappears the moment regenerative feedback is switched off — an observation worth recording, because it points the search at the feed-back mode rather than at a loose part or a failing component.
What the available documentation does not contain is any statement that a continuous buzz is expected, any identification of the vibrating element, or an acceptance limit for the sound. So the timing classification comes first, and the wiring checks in the rest of this article settle the rest.
What does the EP input do on a Smart Line Module? #
EP is the module's pulse enable: it gates the line-side power pulses and, with it closed, the module can feed braking energy back to the supply, so the enable input and the regenerative function live in the same circuit. The enable practice for this module family is that EP is wired through the mains switch or another disconnector. That placement is what makes the sequence self-enforcing: a contactor that opens for any reason takes the pulses away with the mains, so pulses cannot exist on a disconnected power stage.
When EP arrives from a control output on its own timing instead, the module sits with the mains applied but not pulsing until a second command lands — the arrangement the corrective guidance targets on the reported machine. This is wiring, not a parameter: there is no setting value that repairs a pulse enable that closes late.
When must EP switch relative to the 400 V AC contactor? #
They are one switching event, not two steps: the enable practice for this module family states 400 V AC ON equals EP ON, with EP wired through the mains switch or another disconnector so the contactor itself carries the pulse enable. The reported power-up applied the control supply, then the mains, then EP as a separate step, then the motor-module pulse enables — and the correction from the drive-side guidance is a single line: the mains closing and EP are the same event.
Electrically that means EP comes from a contact of the mains switch or disconnector, not from a control output that closes afterward. How the control commands that closing still matters, and the activate and deactivate steps for this machine belong to the SINUMERIK 828D commissioning documentation, so make the wiring match what that document describes.
Which line filter and line reactor match a 10 kW Smart Line Module? #
Match by order number, not by appearance: on the reported line-up the filter is 6SL3000-0HE21-0AA0 and the reactor is 6SL3000-0CE21-0AA0, both marked for the 10 kW Smart Line Module at 3 AC 380–480 V, 50/60 Hz, and both were installed on the machine. Verify both components by their own nameplates before looking anywhere else, because presence alone proves neither the match nor the wiring.
| Component | Order number | Nameplate data as reported |
|---|---|---|
| Line filter | 6SL3000-0HE21-0AA0 |
Matched to the module's power class; 3 AC 380–480 V, 50/60 Hz |
| Line reactor | 6SL3000-0CE21-0AA0 |
Matched to the module's power class; 3 AC 380–480 V, 50/60 Hz |
| Smart Line Module | 6SL3130-6AE21-0AB1 |
3 AC 380–480 V, 50/60 Hz input; 600 V DC, 17 A, 10 kW output; booksize |
| Double Motor Module, two of them | 6SL3120-2TE13-0AA4 |
600 V DC input; 3 AC 400 V, 3 A/3 A output; booksize |
Worked class check. Multiply the module's DC-side rating from its nameplate: 600 V DC × 17 A = 10,200 W, which lands in the 10 kW class. The filter and reactor carrying that class at the supply's voltage and frequency are the correct pairing, and the two order numbers above show exactly that marking. This is a nameplate cross-check, not a load calculation. If your module's nameplate differs — a larger module is the comparable case in the record — the pairing changes, and it comes from that module's configuration documentation, not from this article.
Matched parts still have to sit where the module's connection diagram puts them, so check that arrangement and the tightness of every termination before the next power-up. A class-matched component installed against the diagram is the documented expectation; anything else is a standing candidate cause for the sound.
What should I check before re-enabling the drive? #
De-energize, lock out and verify absence of voltage at the module's power terminals before touching anything here; NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers that lock-and-verify practice, and the checks below are wiring and nameplate work done under it. Confirm the edition and any local amendments with your authority having jurisdiction and with the drive documentation.
- EP source. A contact of the mains switch or another disconnector feeds EP, verified at the terminals, so the enable cannot close later than the mains poles.
- Contactor tracking. With the line-up locked out, exercise the mains contactor and confirm the EP circuit opens and closes with it, not on its own timing.
- Component match. Filter and reactor order numbers against the module's power class, using the nameplate cross-check above.
- Layout and terminations. Filter, reactor and module in the arrangement the connection diagram shows, with terminations tight.
- Control supply order. The 24 V DC control supply present before the mains closes, as the documented sequence requires.
- Setting state. Regenerative feedback left enabled in the drive object's configuration, whatever the sound is doing.
Can I run with regenerative feedback disabled? #
Do not: with feed-back disabled, braking energy has nowhere to go on this line-up, the DC link rises during deceleration and the motor module can disconnect its motor while the machine is still moving, which is the collision the warning about this setting describes. The setting removes the sound because it removes the operating mode the sound is tied to — the feed-back of braking energy — so it is symptom management, not a correction.
On this line-up there is no other destination for that energy. A braking resistor would be a designed addition and its own commissioning task; setting a GS20 drive for braking resistor deceleration stops shows one on a different drive family. A shared-bus group absorbs deceleration energy internally only when one supply and one filter group serve the whole DC bus, and this machine has neither alternative.
So the feed-back path through the module is the only path, and it stays enabled. The disable switch does not fix the buzz cause either — the sound returns the moment the setting comes off, and the enable-sequence work above is the actual fix. If a future machine will never regenerate, that is a selection-time decision for the machine designer, not a parameter change on the installed drive.
How do I re-commission and confirm the fix? #
Repeat the power-up with the corrected wiring and record what each step does: control supply first, mains and EP together at the mains switch, module ready in the drive diagnostics, then the motor-module pulse enables from the control, noting the sound at precharge and again at running.
- Apply the 24 V DC control supply and confirm the drive objects report ready in the control.
- Close the mains switch so the mains poles and EP close as one event, as rewired.
- Let precharge finish and note the sound; a short noise here matches the comparable installation's experience.
- Run an axis through a deceleration with regenerative feedback enabled and watch the module status and the DC link reading in the drive diagnostics; the trip threshold for that reading lives in the module's own documentation, not in this article.
- Confirm no motor module drops its motor and no DC-link overvoltage fault appears.
- If the buzz persists with corrected wiring and verified components, record when it starts and stops, capture the diagnostics, and take that record to the drive manufacturer's support channel.
What is the decision for each finding? #
Decide by finding: precharge-only sound means run the machine; continuous sound means correct the EP wiring and verify the line components before the next power-up; and the disable-regenerative-feedback switch stays off in every case on this line-up.
- Precharge-only noise, quiet at running: within the documented experience of this module family — commission and run.
- Continuous noise after EP closes: work the two documented causes, the enable wiring through the mains disconnect and the component match. If both check out, the timing record and diagnostics go to the drive manufacturer's support, because the documented causes are then exhausted.
- Noise that only the disable setting removes: the setting stays off. The observation is diagnostic; the risk it masks is a rising DC link and a dropped motor during deceleration.
Questions asked
Is a short noise at power-up normal on this module family?
A comparable 16 kW installation is reported quiet in operation with a sound only while precharge runs, so brief precharge noise fits the documented experience of this module family. No installation in the record shows a sound that continues after the module is running, which is why a persistent buzz remains a symptom until the enable wiring and the line components are verified.
Why not fit a line module without regenerative capability instead?
A module built without a feed-back path is the manufacturer's matching choice for a machine whose axes never return braking energy to the supply, and it removes the regenerative function from the design deliberately. That choice is made when the machine is specified. Switching the disable setting on an installed Smart Line Module is not that decision; it only removes the path while keeping the module that was chosen for having it.
What does it prove when the buzz stops under the disable setting?
It ties the sound to regenerative operation or to the state of its enable, which narrows the search to the enable circuit and the line components around the module. As a diagnostic it is genuinely useful. As a correction it is not, because the same setting that removes the sound removes the only path the deceleration energy has on this line-up.
Which document governs the activate and deactivate steps for this line-up?
The commissioning documentation of the installed control, on this machine the SINUMERIK 828D, together with the module's own operating instructions. The command mechanism is control-specific: a comparable line-up run from a Simotion control activates its line module through a function block, so a generic power-up order is no substitute for the activate and deactivate description belonging to the control actually installed.

