Explainer
Why a PLC PWM output cannot speed-control a three-phase motor
Short answer
No PLC output can speed-control a three-phase motor: a 5 to 20 ms scan is about three orders of magnitude too slow for the 2 to 16 kHz three-phase switching the motor needs. Put a VFD on the motor and send it a speed reference: a 0-10 V or 4-20 mA analog output, a fieldbus command, or a PWM pulse train filtered to an analog level.

On this page
- Can a PLC PWM output drive a three-phase motor directly?
- Why does the motor need three variable frequencies instead of one switched wire?
- What sits between the PLC and the motor in a working system?
- Which speed reference should the PLC send to the drive?
- How does a PWM pulse train become an analog reference?
- How do you scale the PLC signal to a motor speed?
- What else must be wired before the drive runs the motor?
- Questions asked
A PLC cannot speed-control a three-phase induction motor from its own outputs, and no output module changes that. The program scan runs every 5 to 20 ms, while the motor needs three voltage waveforms switched at a 2 to 16 kHz carrier: the two rates sit about three orders of magnitude apart. The working architecture is a variable frequency drive (VFD) on the motor with a speed reference sent from the PLC: a 0-10 V or 4-20 mA analog output, a fieldbus command, or a transistor output's PWM pulse train filtered back to an analog level. Below is the timing arithmetic, the choice between those references, and the scaling math on a worked 460 V, 60 Hz motor.
Can a PLC PWM output drive a three-phase motor directly? #
No. A typical program scans every 5 to 20 ms, while a three-phase motor needs switching decisions on three output legs every 62.5 to 500 µs, the period of the 2 to 16 kHz carrier a VFD uses, and a PLC output point carries signal current, not motor amps.
Run the numbers. A 4 kHz carrier has a 250 µs period; with a 10 ms scan, 10 ms ÷ 0.25 ms = 40 carrier periods pass between updates of the output, and even a 1 ms periodic task gets one update for every four carrier periods. The power side fails separately: NFPA 70, the National Electrical Code, 2023 edition, gives 14 A as the full-load current of a 10 hp, 460 V three-phase motor in Table 430.250, the table used to size motor branch circuits, and that current must be switched through a power bridge, not a 24 V DC signal point. PWM is the right idea in the wrong place.
Why does the motor need three variable frequencies instead of one switched wire? #
Because torque in an induction motor comes from a rotating magnetic field: three currents spaced 120 electrical degrees apart at the commanded frequency, with voltage held proportional to frequency below base speed so flux and torque capability stay constant. That is a coordinated output on three wires, not a pulse width on one.
Halving the frequency halves the voltage with it: on a 460 V, 60 Hz design the drive outputs roughly 230 V at 30 Hz, which is normal behavior, and the meter reading that looks like a fault is explained in why a VFD shows low output voltage and the motor has no torque. PWM is exactly the tool the drive uses internally; the difference is that it runs on a three-leg insulated-gate bipolar transistor bridge at the carrier rate with current sensing and dead-time management between legs, hardware a PLC output module does not have. A single PLC output switching 24 V DC varies one duty cycle on one wire, and a three-phase motor fed that way produces no rotating field at all.
What sits between the PLC and the motor in a working system? #
A VFD, sized to the motor's nameplate current, plus two PLC signals: a run command into one of the drive's digital inputs and a speed reference into its analog, pulse or network input. The drive rectifies the supply into a DC bus and chops that bus into the three-phase waveform at whatever frequency the reference requests, holding the volts-per-hertz pattern the motor needs.
The drive also carries the motor's protection: its electronic overload, programmed to the nameplate full-load amps, serves as the motor overload device that NFPA 70, 2023 edition, Article 430 requires for motor circuits and that IEC 60204-1 requires on machines, where the drive's documentation lists that function; confirm the arrangement with your authority having jurisdiction. Where the motor is critical or its cable runs long, protecting a motor fed by a VFD with a protection relay covers adding a dedicated relay at the motor. If the supply is single-phase rather than three-phase, the drive itself must be sized for that input, and the derating arithmetic is in sizing a VFD for a three-phase motor on single-phase input.
Which speed reference should the PLC send to the drive? #
Commit in this order: the analog voltage reference when the PLC and the drive share one enclosure, the current loop when the reference wire leaves the cabinet, and a fieldbus when you also want status, faults and diagnostics back over the same pair.
| Reference | Fits | Watch out for |
|---|---|---|
| 0-10 V analog output | Same cabinet, short run | Drop and induced noise; wiring guidance keeps these runs to roughly 20 m |
| 4-20 mA analog output | Between cabinets, long or noisy runs | The elevated zero: a broken wire reads below 4 mA, which the drive can flag as a fault; set its input jumper or burden resistor for current |
| Fieldbus, for example Modbus RTU over RS-485 | The PLC already networks its drives | Command mapping and drive network settings must be configured; status words come back for free |
| PWM pulse train | No analog module, but a transistor output exists | About 100 usable steps and a nonlinear speed map; needs an RC filter unless the drive has a pulse input |
The pulse-train row is the fallback, so check the drive's I/O list first: a drive with a dedicated pulse-train reference input takes the unfiltered signal directly and the filter disappears from your design.
How does a PWM pulse train become an analog reference? #
With one resistor and one capacitor: the field guideline is 10 kΩ and 1 µF across the drive's reference input, with the resistor chosen equal to or just above the drive's stated input impedance so the filter does not load the source.
The arithmetic shows why it is only a guideline. The PWM instruction in this scheme runs near 100 Hz, and the time constant is τ = RC = 10 000 Ω × 1 µF = 10 ms, exactly one 10 ms period, so the capacitor has no time to smooth. Peak-to-peak ripple is roughly V × D(1 − D) × T/τ; at half duty across the full reference span that is 10 V × 0.25 × 1 ≈ 2.5 V, far too rough for a reference. Raise the capacitor to 10 µF and τ becomes 100 ms: ripple falls to a tenth of that, about 0.25 V, 2.5 % of span, and a step command settles in roughly 5τ = 0.5 s, sluggish but fine for a speed trim on a fan or conveyor.
Expect about 100 usable steps and a nonlinear map. One reported field setup of exactly this method, with the pulse train at 100 Hz, held the drive from about 3 Hz at 1 % duty to 120 Hz at 100 % duty, with about 2 Hz for each added percentage point of duty at the bottom of the range and about 0.5 Hz at the top; anything needing finer steps or better linearity is out of this method's reach, so choose the analog or fieldbus route instead. Generation takes a transistor output toggled from a fast periodic task; a mechanical relay output cannot switch at that rate and would wear out trying.
How do you scale the PLC signal to a motor speed? #
Linearly: with the drive's maximum frequency set to the motor's nameplate hertz, the drive's output frequency is the reference fraction times that maximum, and shaft speed follows 120 × f ÷ poles minus slip.
Worked example, hypothetical, with every input stated: a motor nameplated 460 V, 60 Hz, 4 poles, 1750 rpm; the drive's maximum frequency parameter set to 60 Hz; the reference source set to the voltage input. Target: 1350 rpm on the synchronous scale. Frequency: f = 1350 × 4 ÷ 120 = 45 Hz. Output voltage from the PLC: 45 ÷ 60 × 10 V = 7.5 V. If the analog module's raw count range is 0 to 32767 for the full voltage span, a module-specific figure you read from its data sheet, the count value is 0.75 × 32767 = 24575. The shaft will turn slightly under 1350 rpm because of slip; enabling the drive's slip compensation or sensorless vector mode recovers most of that error. Treat the result as a commissioning estimate and confirm it against the drive's scaling parameters and the motor data.
What else must be wired before the drive runs the motor? #
Three things beyond the reference: a run command from a PLC digital output to the drive's start input, the drive's fault relay contact back to a PLC input, and the motor's nameplate data entered into the drive before it is enabled.
Commission in order: enter nameplate voltage, frequency, full-load amps and pole count; start and stop from the keypad and confirm rotation; then switch the command and reference sources to the PLC terminals and verify 0 %, 50 % and 100 % references against the drive's displayed frequency. Wire all of it dead: de-energize and lock out the circuit, wait the discharge interval the drive manual states for its DC bus, and verify absence of voltage with a rated instrument before touching any terminal; NFPA 70E, 2024 edition, sets those work-practice requirements, so follow your site's procedure. If the drive runs from the keypad but ignores the PLC reference, the causes are worked through in why a VFD ignores the analog speed reference from the controller.
Questions asked
Do I still need a separate overload relay with the drive?
No, as long as the motor runs only through the drive: the drive's electronic overload, programmed with the nameplate full-load current, serves as the motor's overload protection under NFPA 70 Article 430 and IEC 60204-1. Add a separate thermal overload only on a bypass path that can start the motor across the line, and interlock the bypass and drive contactors so they can never close together.
Can one PLC analog output set the speed of two drives?
Yes, when both motors should track the same command: wire the voltage output in parallel to both drives' reference inputs and give each drive its own run command. Check the paralleled input impedance against the analog module's load rating in both manuals, and remember the two drives will ramp and trip independently of each other.
How fast must the PLC update the speed reference?
Much more slowly than the motor needs its switching: a 20 ms scan still refreshes the command 50 times a second, while drive ramps and motor inertia respond over hundreds of milliseconds. A normal periodic task is enough for analog or fieldbus references; only the pulse-train method is scan-sensitive, because one output must keep toggling near its carrier rate.
Is the drive's internal PWM the same as a PLC pulse train?
No. A PLC pulse train is a slow reference signal that is filtered back to a DC level before the drive reads it. The drive's own power stage then switches at its carrier setting, commonly 2 to 16 kHz, to build the actual motor waveform. One carries information at signal current; the other carries motor current at supply voltage.

