Troubleshooting
Why a pressure switch in the seal-in path stops compressor cycling
Short answer
A pressure switch wired in series with the contactor coil cannot coexist with the Start seal-in: at cut-out the switch opens, the holding contact opens with the coil, and every low-pressure restart waits for a fresh Start press. Keep the switch outside the holding path and hold run permission in a retained Ready circuit — NC Stop and Start seal the Ready relay, whose contact feeds the contactor coil through the pressure switch.

On this page
- What each symptom tells you
- The three-wire circuit the pressure switch has to live with
- Why a switch inside the seal-in path cancels every cycle
- The fix: a retained Ready circuit gating the contactor
- Read the coil voltage from the starter, not from the motor
- Setting the overload for the 5 hp, 230 V single-phase compressor motor
- De-energize, then prove each contact
- Questions asked
A compressor that stops on pressure and then will not restart on falling pressure almost always has its pressure switch wired into the seal-in path of the magnetic starter. The switch opens at cut-out, the contactor coil loses current and the holding contact opens with it; when pressure falls and the switch closes again, Start and the holding contact are both open, so the machine sits until an operator presses Start. The decision is simple: the pressure switch belongs in series with the contactor coil but outside the holding path, and the run permission belongs in a retained Ready circuit that Start seals in and Stop cancels. The sections below sort the symptoms, show both placements, wire the Ready circuit, read the coil voltage and work the overload setting for this install's 5 hp single-phase compressor motor.
What each symptom tells you #
- The motor runs only while Start is held. The holding contact is missing or not in parallel with Start. NEMA magnetic starters normally carry one normally open auxiliary contact intended for exactly this duty; it has to be landed in parallel with the Start contact, or the coil releases the moment the button returns.
- It stops at cut-out and will not restart at cut-in without a fresh Start press. The pressure switch sits in the same series path as the seal-in. That is the placement this article fixes, and the switch itself is usually healthy.
- Nothing happens with the receiver below cut-in. An open NC Stop, a pressure-switch contact that never closes, a tripped overload contact or a coil supply mismatch each stop the coil on its own. Prove them one at a time with the circuit dead, the way the last section sets out.
- The motor fights its start or snaps hard. The pump is accelerating against trapped head pressure, so check the unloader before anything electrical. Raising the overload to survive that start hides a mechanical fault, which is exactly the case in why raising a magnetic overload setting won't fix a hard start.
- The coil hums, chatters or drops out mid-run. Suspect control voltage before the coil itself; the pull-in and voltage checks in why a motor starter coil has voltage but won't pull in sort that out.
The three-wire circuit the pressure switch has to live with #
A momentary station gives you two contacts: a normally open Start and a normally closed Stop. Stop sits in series from the control supply, Start sits between Stop and the coil, and the contactor's normally open auxiliary contact bridges Start. Press Start, the coil pulls the armature in, the auxiliary closes, and coil current keeps flowing past the released button; that bridge is the seal-in, or holding, contact. The overload relay's normally closed trip contact stays in series too, so a trip drops the coil rather than interrupting the motor leads under load.
NEMA magnetic starters normally ship with one normally open auxiliary contact reserved for that bridge. Confirm the location and the terminal markings in the starter's own documentation; on an unfamiliar starter, the identification steps in identifying unknown terminals on a NEMA size 1 motor starter land the right terminals in a few dead-circuit meter checks.
Why a switch inside the seal-in path cancels every cycle #
Wire the pressure switch in series with the coil — before the parallel block or after it, the result is the same, because coil current and holding current both flow through it. At cut-out the switch opens, the coil drops out and the auxiliary opens with it. At cut-in the switch closes again, but Start is released and the auxiliary is open, so nothing energizes. Every pressure stop then costs a fresh button press.
That placement is a valid manual-rearm station: an operator authorizes each run, and a pressure switch in the circuit does not turn it into an automatic one. What it must not become is a pressure switch moved in parallel with Start as an easy fix. The seal would then hold the contactor closed past cut-out and the pump would run dead-headed against its relief valve.
The fix: a retained Ready circuit gating the contactor #
Keep the seal alive in a second device and let the pressure switch gate only the contactor. A small control relay or an auxiliary contactor does the job, as long as its coil matches the control supply and its contacts carry the contactor coil load per the device's documentation.
- Ready circuit: fed from the supply side of NC Stop — normally open Start in parallel with a normally open auxiliary on the Ready relay, feeding the Ready relay coil back to the other control line. Start seals Ready in; Stop cancels it.
- Contactor branch: also fed from the supply side of NC Stop — a normally open Ready relay contact in series with the pressure switch, the overload's normally closed trip contact and the contactor coil. Put the overload contact ahead of both branches so a trip drops Ready as well and a tripped motor is not re-picked on the next cut-in; the operator clears the fault and presses Start again.
At cut-out only the contactor drops; Ready stays sealed, and at cut-in the Ready contact and the closed pressure switch pick the contactor up on their own. A Stop press or a supply interruption drops Ready, so nothing restarts when power returns until an operator presses Start — the behavior momentary three-wire control exists to provide. NFPA 79, the electrical standard for industrial machinery, applies to machines operating at 1000 V or less and carries restart provisions to that effect; confirm the requirement that governs your machine with the authority having jurisdiction and the machine's documentation.
Read the coil voltage from the starter, not from the motor #
The motor's power-circuit voltage tells you nothing about the coil. Read the marking on the coil itself or the starter's rating plate: voltage, supply type and frequency. Control circuits commonly run at a lower voltage than the motor — 120 V AC from a control transformer, or 24 V as in many small compressor panels — provided the coil, any indicator lamps and the transformer share one rating and the transformer's capacity covers the connected load as the manufacturer's documentation requires. A coil fed below its marking chatters or fails to pull in; fed above its marking, it overheats.
Setting the overload for the 5 hp, 230 V single-phase compressor motor #
The install's motor is 5 hp, single-phase, 220 V on the nameplate, 60 Hz; the paperwork gives no nameplate amperes or service factor, so the example stands in the table current and shows both service-factor branches. Redo the two multiplications from your own nameplate.
Inputs:
- 5 hp, single-phase, 220 V nameplate, 60 Hz — this install.
- Full-load current stand-in: 28 A, the NFPA 70 (National Electrical Code), 2023 edition, Table 430.248 value for a 5 hp single-phase motor at 230 V, the column that covers 220–240 V single-phase supplies. The code sends overload settings to the motor nameplate and reserves table currents for conductor and branch short-circuit sizing, so treat that 28 A as an estimate.
- Service factor: unknown here; NFPA 70, 430.32(A) draws the line at 1.15.
Rule in words: NFPA 70, 430.32(A) caps the overload pickup at 125% of nameplate full-load current for a motor marked with a service factor of 1.15 or higher, or a temperature rise of 40 °C or less, and at 115% for every other motor rated more than 1 hp.
Arithmetic:
- 115% branch, service factor 1.0 (illustrative): 28 A × 1.15 = 32.2 A
- 125% branch, service factor 1.15 or higher: 28 A × 1.25 = 35.0 A
Result: an overload pickup of 32.2 A with a service factor of 1.0, or 35.0 A with 1.15 or higher — whichever branch the nameplate you read calls for.
Decision: fit the heater whose range in the starter's published heater table contains that ampere value, in the starter size already mounted. The same table current also sizes the branch conductors at 125% of full-load current under NFPA 70, 430.22, and the second line above already gives that minimum ampacity: 35.0 A. Check the result against the nameplate and the governing code before fitting anything.
De-energize, then prove each contact #
Isolate the starter, lock out and verify absence of voltage at the line terminals before the cover comes off; NFPA 70E, 2024 edition, sets the safe work practices for that verification, and your authority having jurisdiction and site procedure govern the details. Bleed the receiver below the switch's cut-in setting and vent any trapped pump head pressure before touching the pressure-switch contacts. Then prove each contact with the circuit dead:
- Start, momentary normally open: open when released, closed when pressed.
- Stop, momentary normally closed: closed when released, open when pressed.
- Pressure switch: continuity at the cut-in pressure, open at the cut-out pressure; record both settings from the switch's marking and confirm the contact really changes across them.
- Overload trip contact: closed in the normal state, opens when the trip or test lever is pressed.
- Holding auxiliary: normally open with the contactor at rest, closes only when the contactor operates.
With the contacts proven, the coil fed at its marking and the heater matched to the nameplate arithmetic, the closing decision is the one the article opened with: pressure switch in series with the contactor coil and outside the holding path, run permission sealed in a Ready circuit that Stop can cancel, and a manual-rearm series placement only where an operator is meant to authorize every cycle.
Questions asked
Can the compressor cycle automatically without a second relay?
Yes, by dropping the seal-in entirely. Feed the coil through the NC Stop, the pressure switch and the overload trip contact with no Start bridge, and hold the circuit with a maintained selector or toggle instead of a momentary button. The contactor then follows the pressure switch on its own, but after any supply interruption the compressor restarts the moment power returns, which momentary three-wire control exists to prevent. Accept that only where an unexpected restart is genuinely harmless.
Why does the overload trip contact open the coil circuit instead of the motor leads?
The heaters sit in the power legs and do the sensing, but the trip contact only needs to break the coil's small control current. Opening the coil lets the contactor's main contacts interrupt the motor current, which is what those contacts are built and rated for, and it keeps the trip circuit's wiring and contacts small. Put it in series so a trip also drops the Ready circuit and the motor is not re-picked on the next cut-in.
What makes the motor snap loudly right after it starts?
Usually the motor's own centrifugal start switch: it connects the start winding for acceleration and clicks out near full speed, once per start. A hard snap with the pump loading up immediately points at the unloader instead — if it is not venting the pump's discharge, the motor accelerates against trapped head pressure. Restore the unloader before touching the overload or the control wiring.
Can the green Start button's lamp double as a status light?
Yes, but decide which state it shows before wiring it. A lamp in parallel with the contactor coil lights only while the compressor is actually running and goes dark at every cut-out; a lamp on the Ready circuit stays lit through pressure cycling and shows the station is armed. Feed it at the voltage marked on the lamp and keep its circuit separate from the contact block that carries the Start command.
