Why a six-lead lathe motor won't start on a VFD
Short answer
The lathe's start button closes a contactor that lands the stationary motor on an output the drive is already producing, so the motor never sees the drive's ramp and its locked-rotor current trips the protection. Identify the six-lead winding from the nameplate diagram, connect it once, and give start and stop duty to the drive's run command.

On this page
- What the trip sequence already tells you
- Why a start button on a running VFD output always trips
- The current when a 3 hp, 220 V motor lands on a running output
- What leads 1, 2, 3, S1, S2 and S3 can be
- Tracing and identifying the winding safely
- Rewire the lathe so the drive owns the start
- The decision for each case
- Questions asked
The lathe start button is the fault, not the drives. It closes a contactor that lands a stationary motor on an output the drive is already producing, and a rotor standing still at full frequency pulls a locked-rotor-class demand that trips the protection before anything can accelerate. Underneath that sits a second problem: the six tagged leads, 1, 2, 3, S1, S2 and S3, belong to an unidentified winding — a two-speed consequent-pole motor or a star-delta motor whose links were moved into the panel — and no lead gets connected until the nameplate diagram settles which it is. Connect the winding once, per the diagram, then give start and stop duty to the drive's run command.
What the trip sequence already tells you #
Three devices could be acting, and each one says something different:
- The drive's own trip, shown as a code on its display. An overcurrent-style trip means the drive saw current far above its limit the instant the contactor closed. Read the fault history and the manual's fault table for the L200 before naming a cause.
- A thermal overload relay in the lathe panel, marked by a flag or reset lever on the relay. It trips on heating, so it acts seconds after the connection, which matches a short rolling sound and then a trip.
- An upstream breaker or fuse, which drops the whole machine rather than just the motor circuit.
The reported order, contactor movement then a brief roll then a trip with the shaft still, is the signature of a motor energized but not accelerating: stator current turns into heat instead of torque. One more fact is already on the table. Both drives start the mill without trouble, so drive capacity is not the deciding difference; the mill's motor is wired to its drive and commanded on together with it, while the lathe's motor arrives on a finished output.
Why a start button on a running VFD output always trips #
The sequence on this machine runs the drive first: its output builds, and the lathe's start button then closes a relay or contactor in the casting that connects the motor. The motor misses the drive's ramp entirely and lands at whatever voltage and frequency the output is carrying that instant. At standstill an induction motor near rated voltage behaves like a transformer with a shorted secondary and draws roughly six times its running current, so the drive's electronic overcurrent protection or the thermal relay acts within seconds. Holding the button while the drive comes up changes nothing, because the contactor still closes under an active output.
There is a second cost. Opening or closing a contactor on an active drive output steps voltage and current into the drive's output stage and is hard on it. Drive manufacturers document that a contactor between the drive and the motor must not be used for ordinary start and stop duty; where a contactor must exist, for isolation, maintenance or a bypass, it needs the manufacturer's approved sequence and interlocks. The distinction between where a contactor belongs on a drive and where it does not is exactly what the page on VFD input contactor versus output contactor works through.
The current when a 3 hp, 220 V motor lands on a running output #
The case machine supplies the motor data; NFPA 70, the National Electrical Code, 2023 edition, supplies the table value. That code's Table 430.250 lists full-load currents for three-phase motors at nominal system voltages, used to estimate motor-circuit current when the nameplate is not at hand. Confirm circuit sizing with the local authority having jurisdiction and the equipment documentation.
- Motor: 3 hp, three-phase, nameplate supply 220 VAC, as reported for this lathe.
- Table full-load current: 9.6 A, the value NEC Table 430.250 lists for a 3 hp three-phase motor at 230 V nominal.
- Actual supply: 220 V, the voltage this machine runs on.
The rule: table current scales inversely with the voltage the motor actually sees, so I_actual = I_table × V_nominal ÷ V_actual. The arithmetic:
9.6 A × (230 V ÷ 220 V) = 2208 ÷ 220 = 10.0 A
Estimated running current is about 10 A, and it is an estimate; the nameplate rated current for the connection actually used governs the protection setting. At the moment the contactor closes with the rotor standing still, a general-purpose design draws roughly six times that, near 60 A; the nameplate code letter and the NEC locked-rotor tables give the exact figure for a specific motor.
Decision: the drive and the motor circuit are sized on that running current, and a 60 A-class step on a live output sits far outside what the electronics accept, so a trip in the first fraction of a second is the designed response, not a drive defect. Command the run with the motor already connected, from zero speed, and the demand stays inside the drive's current limit through the whole ramp. That is the threshold separating the two cases: trips with the motor connected dead point at wiring, settings or load; trips when the motor lands on a live output are the expected result.
What leads 1, 2, 3, S1, S2 and S3 can be #
Tagged leads are not an identified winding. Three readings fit a machine like this, and the nameplate picks between them:
- A two-speed consequent-pole motor: a single winding, usually marked with the delta and double-wye symbols on the plate, run series-delta for low speed and parallel-wye for high speed. On the high-speed connection the interior lead group gets bridged together; the diagram shows which group is the line connection and which is the bridge, and the S markings alone do not say. The page on two-speed motor wiring with six power leads explains why all six conductors are power leads rather than grounds or extras.
- A star-delta motor with its links moved out of the terminal box: a single-speed winding with all six ends brought to the panel, where the starter makes the wye or the delta connection. If the original starter hardware in the casting is gone or idle, the winding currently has no connection at all.
- A dual-voltage single-speed motor, where the two plate voltages tell you which leads pair up — that reading is what the page on six leads and two plate voltages covers.
Do not energize only leads 1, 2 and 3 as an experiment or bridge the S-marked leads on a guess. A wrong choice can leave part of a winding out of the circuit: low torque, high current and heat, the same trip with a cause that now looks like a bad motor.
Tracing and identifying the winding safely #
Before anything is opened, lock out every supply feeding the machine — the line side, any separate control supply and the drive's DC bus, waiting out its discharge time per the manual — and verify absence of voltage at the motor leads with a meter rated for the supply. A dark display and a stationary shaft are not proof of isolation.
- Photograph and record before disconnecting anything: the full nameplate, including voltages, speeds, current per connection and connection symbols, plus any diagram inside the terminal cover and the present lead dress in the casting.
- Trace the power path from the drive's output terminals to the six leads: find every contactor, relay, overload element and terminal block, and establish what the lathe's start button actually closes and which device has been tripping.
- With the motor leads fully isolated from both the drive and the line, measure resistance between every lead pair and record the matrix. The pattern shows how many separate windings exist and which leads share them; interpret it together with the diagram, because resistance alone does not give polarity or the pole-changing connection.
- If the plate is missing or the matrix does not match either standard arrangement, determine the lead polarity and the connection from the measurements before applying power. The page on determining three-phase motor lead polarity with unidentified leads covers that procedure.
- Check the mechanical side a free shaft does not cover: this shaft turns by hand and the carriage, cross slide and head are disengaged, so inspect the belt and any spindle brake or interlock that could still hold the load.
Rewire the lathe so the drive owns the start #
- Choose the connection from the nameplate. For a delta/double-wye two-speed motor on a drive, the commonly recommended connection is the high-speed one, which means the interior lead group is bridged per the diagram; the plate, not guesswork, decides which leads get bridged.
- Connect the motor once and leave it connected: hard-wired from the drive output through whatever disconnect and overload the design keeps, with the power-side start contactor out of the circuit path.
- Turn the existing buttons into control devices. Their contacts can stay as operators, but they should feed the drive's run and stop control terminals, which the L200 manual documents with their low-voltage supply, instead of switching motor power. Check each button's contact arrangement and rating for control duty first.
- Set the drive's motor protection to the nameplate rated current for the connection now wired, reading the setting names from that same manual rather than reconstructing parameter identifiers. A two-speed plate lists a current per speed and connection, so the setting must match the one in use.
- Any contactor that must remain for isolation or maintenance gets interlocked so it can only change state with the drive's output inhibited, following the manufacturer's approved sequence.
- Keep the protective functions intact: guards, emergency stop and restart prevention stay wired and tested, because a drive's stop command is not a substitute for the machine's safety functions.
Run the first test with the tool clear of the work and the guards closed, and watch the drive's output-current monitor through the ramp. Current should rise during acceleration and settle near the running current at speed; a jump straight to the drive's limit means stop and recheck the connection.
The decision for each case #
- The trip is the drive's own overcurrent code: the connection event caused it. Rewire start and stop to the run command as above; the drive is not undersized, because the same unit accelerates the mill.
- The trip is a thermal overload relay in the motor circuit: same cause. After rewiring, set that relay, if it stays in the circuit, to the nameplate current of the connection used and let the drive's electronic motor protection carry everyday duty.
- The winding cannot be confirmed from the plate or the measurements: no power until it is. A guessed connection turns a wiring problem into a burned winding.
- Still trips with the motor connected dead and the settings correct: recheck the connection and the load or brake first, then the ramp and current settings in the manual. With the sequence right, the drive that runs the mill runs this lathe.
Questions asked
Why does the same VFD start the mill but not the lathe?
On the mill the motor is wired to the drive output and the run command brings voltage and frequency up from zero together, so current stays inside the drive's limit. On the lathe the drive ramps an empty output first, then the start button's contactor lands the stalled motor on it, and the motor pulls a locked-rotor-class demand the instant it connects, which trips the protection.
Can a contactor stay between the VFD and the motor?
Only with the drive manufacturer's approved sequence and interlocks, so it never opens or closes while the output is active, and so the drive is fully disconnected before anyone starts a motor from the line in a bypass arrangement. For everyday start and stop duty, drive manufacturers advise against a contactor on the output side; the run command does the starting.
How do I tell a consequent-pole two-speed winding from a star-delta motor with remote links?
The nameplate decides first: two speeds with delta and double-wye symbols point to a consequent-pole single winding, while one speed with delta and wye connection symbols points to a winding whose links live in the starter. A resistance map between every lead pair then confirms how many windings exist and which leads share them. Without the plate, identify polarity and the connection from measurements before applying power.
What current do I enter for the drive's motor protection?
The nameplate rated current for the connection actually wired; a two-speed plate lists a current per speed and connection, and the setting must match the one in use. Until the plate is in hand, a table estimate of about 10 A for this 3 hp, 220 V motor is a sizing check only, never a protection setting.
Should the lathe's start and stop buttons be removed?
Not necessarily. Their contacts can usually stay as operators, but they should feed the drive's control terminals instead of switching motor power; check each contact's arrangement and rating for low-voltage control duty first. If a power contactor must remain for isolation, interlock it to the drive manufacturer's approved sequence so it cannot change state on an active output.