Short answer

Six leads are the two ends of three stator windings. Measure the supply, match it to a plate voltage line, and connect exactly as the plate diagram shows: wye ties the three winding ends together and lands supply on the starts, delta ties each end to the next start. A six-lead wye/delta pair sits 1.732 apart; a 230/460 pair means the plate diagram, not a rule, decides.

On this page
  1. What six leads actually are
  2. Read the plate before you touch a lead
  3. The 1.732 arithmetic, worked
  4. What each wrong connection looks like
  5. Tie and land the leads
  6. When the plate breaks the pattern
  7. Prove the connection before you trust it
  8. The decision for each case
  9. Questions asked

Six leads in a three-phase terminal box are the two ends of three stator windings, brought out so one motor can be connected in wye or in delta. The plate decides which: measure your supply, find the plate voltage line it matches, and tie and land the leads exactly as the plate's connection diagram shows. Keep one number in mind, 1.732. A six-lead dual-voltage motor's two voltages sit that far apart, 230 V delta against 400 V wye on an IEC-style plate, because wye divides the line voltage by the square root of three across each winding while delta applies it in full. A 2:1 pair such as 230/460 on six leads is the exception where the diagram alone decides.

What six leads actually are #

Every stator winding has a start and an end. Six leads means the manufacturer brought all six ends into the box instead of joining them inside the frame. NEMA practice numbers them T1 through T6 — NEMA MG 1, Motors and Generators (2021 edition), is the standard behind that numbering — and in the common pairing the windings run T1 with T4, T2 with T5, T3 with T6. IEC-built machines carry letters fixed by IEC 60034-8 (2007 edition) on terminal markings and direction of rotation: U1 and U2 are the two ends of one winding, V1 and V2 of the next, W1 and W2 of the third.

Whichever system your motor uses, the plate diagram is the authority. Lead positions inside the box are not standardized, and a shop repair can scramble them. Six wires on a single-phase frame is a different machine, usually two-speed windings, covered in identifying leads on a six-wire two-speed single-phase motor.

Read the plate before you touch a lead #

Work down the plate in this order:

  • Voltage lines. Two voltages mean a dual-voltage motor, and your measured supply must match one of them.
  • Connection diagram or table. It names which leads join at each voltage and which land on L1, L2, L3.
  • Frequency and phases. For across-the-line running, the supply hertz must equal the plate hertz.
  • FLA for each voltage. Two voltages give two currents, and the ratio between them identifies the winding family.
  • Starter notes. One run voltage plus a wye-delta note means the starter, not you, changes the connection.

The pattern worth recognizing: on a six-lead machine the two voltages sit in ratio 1.732 — a 230/400 or 400/690 plate — because they are the same winding voltage connected two different ways. A 2:1 pair like 230/460 is normally built with series and parallel winding groups, which need nine or twelve leads; the nine-lead case is covered in wiring nine-lead dual voltage motor leads to a VFD. If a six-lead plate shows 230/460 anyway, the plate diagram overrides the pattern.

The 1.732 arithmetic, worked #

Two formulas carry the whole decision:

  • Wye: volts per winding = line-to-line volts / 1.732
  • Delta: volts per winding = line-to-line volts

Example, with every input stated: a plate reading 7.5 kW, 230 delta / 400 wye, 22.0 A at the low line, 12.5 A at the high line, three-phase 50 Hz, and a measured supply of 397 V line-to-line.

Wye: 397 V / 1.732 = 229.2 V across each winding. Each winding is rated 230 V, so it runs at 229.2 / 230 = 0.997, a fraction of a percent below rating. Good.

Delta: 397 V would sit across each winding, 397 / 230 = 1.73, about 173% of rating. The iron saturates and current runs several times FLA even unloaded. Not survivable.

Decision: wye. One joint ties the three winding ends together; the supply lands on the three starts.

The plate currents confirm the family. At equal output power, line current is inversely proportional to voltage, so 12.5 A × (400 / 230) = 21.7 A, which is the printed 22 A rounded. When your two FLAs sit about 1.73 apart you have this wye/delta case; when they sit 2.0 apart, the motor uses series and parallel groups and carries nine or twelve leads, not six.

What each wrong connection looks like #

What you see What it means
Current high and noisy, frame heating within minutes even unloaded Delta tie on the wye line: roughly 173% of rated volts per winding
Spins unloaded, then stalls or overheats once load arrives Wye tie on the delta line: roughly 58% of rated volts per winding
Line currents far apart while the supply voltage is balanced A winding end reversed inside a joint, or ends of different windings tied together
Runs normally but backwards Phase sequence only; the ties are fine

The low-voltage mistake is the quiet one. Torque capability scales with the square of the voltage across the winding, so 0.578 squared is 0.33: about one-third of the torque the motor was built to deliver. It will run a conveyor empty and stall when product lands on it. Backwards rotation is not a tie error at all — swap any two supply conductors and nothing else; why any two phase swaps reverse a three-phase motor explains the mechanism.

Tie and land the leads #

Lock out the circuit and verify absence of voltage at the motor terminals before the box comes open. NFPA 70E, 2024 edition, sets the de-energized-work practices behind that step in the United States; your site procedure and the authority having jurisdiction decide the exact sequence.

  • Wye: one joint joins the three winding ends — the T4, T5 and T6 group on common NEMA numbering, U2, V2 and W2 on IEC motors. Insulate the joint completely, keep it clear of the box wall, and land L1, L2 and L3 on the three starts.
  • Delta: three joints, each tying one winding's end to the next winding's start — for example U2 to V1, V2 to W1, W2 to U1. Each joint also carries a supply conductor, so nothing in a delta box floats free.
  • Either way: rated lugs and connectors, the manufacturer's torque value, and joints routed so vibration cannot rub the insulation against the frame.

When the plate breaks the pattern #

  • 230/460 on six leads. Occasionally a part-winding or builder-specific scheme brings a 2:1 pair out on six leads. Tie exactly what the plate diagram shows and nothing else; if the diagram is missing, the motor stays off until the manufacturer's drawing arrives by model and serial number.
  • One voltage plus a wye-delta starter note. All six leads land on the starter's contactors per the starter diagram; the run connection is the plate's, and no leads are tied in the motor box. The starter makes the transition.
  • Tags gone. With the motor isolated, a continuity meter finds the three pairs: each winding reads low resistance between its own two ends and open to the other four leads, and the three readings should match. Pairing alone does not tell a start from an end, so run the identification procedure in identifying wires on an unmarked three-phase motor before tying anything; the resistance background is in what a multimeter shows about three-phase motor winding resistance.
  • Plate missing or illegible. Stop. Lead count alone does not identify a connection; the manufacturer's diagram by model and serial number does.

Prove the connection before you trust it #

Before first power, test insulation resistance from each winding to the frame and between windings, using an insulation resistance tester — a megohmmeter — at the test voltage the motor documentation names. IEEE 43, 2013 edition, is the recommended practice for insulation resistance testing of rotating machinery; the pass value comes from the motor documentation.

On first run, unloaded, measure all three line currents: they should sit close to one another and well below the plate FLA for your voltage line. Under normal load, current should be at or below that FLA, with line-to-line voltage at the motor terminals near the plate value. Current above FLA at normal mechanical load, with the supply voltage right, sends you back to the joints.

The decision for each case #

  • Plate voltages 1.73 apart and the supply equal to the high line: wye — one joint on the three winding ends, supply on the three starts.
  • The supply equal to the low line: delta — three end-to-start joints, each carrying a supply conductor.
  • 230/460 shown on six leads: tie only what the plate diagram shows; no diagram, no power until the manufacturer's drawing arrives.
  • One run voltage with a wye-delta starter note: all six leads go to the starter, which makes the connection change.
  • Tags gone: pairs by continuity, starts and ends by the identification procedure, then tie per the plate.
  • Plate illegible: the manufacturer's diagram by model and serial number decides, never the lead count.

Questions asked

Can I connect a 230 delta / 400 wye motor in wye to a 480 V supply?

No. Wye on a 480 V line puts 277 V across each winding, about 120% of the 230 V rating. NEMA MG 1 designs general-purpose motors to carry rated load through roughly plus or minus 10% voltage variation, and 120% sits outside that band: the iron saturates, current and temperature climb, and the winding fails. Feed it from a drive programmed for the plate volts and hertz, or from a transformer, instead.

Does a six-lead wye/delta motor work on a variable frequency drive?

Yes. Choose the plate connection for one voltage, tie it once as the diagram shows, and land the three supply leads on the drive's output terminals. The motor's connection never changes after that: speed and direction are the drive's job, and changing the tie points is never part of it. Enter the plate volts and hertz as the drive's base settings so the motor sees the pair it was built for.

Must the supply frequency match the plate hertz?

For across-the-line running, yes. The plate pairs its voltage with its frequency, and separating the pair shifts the air-gap flux, which moves torque and heating. A 50 Hz motor on a 60 Hz supply at full voltage loses one sixth of its flux and torque capability with it. On a drive, the plate pair becomes the drive's base voltage and base frequency settings, and the motor runs as built.

How closely should the three winding resistances match?

The absolute value scales with motor size, so it is not a selection number; the useful check is that all three readings match one another. One clearly low reading points to shorted turns, and an open pair means a broken winding or a failed crimp. Measure lead to lead with the same meter on the same range, and expect every lead to read open to the frame before power.

Can wire colors identify the leads?

No. Wire colors are not standardized across motor builders, and a shop repair inside the box can mix them with the originals. Trust the lead tags and the plate diagram; when tags are gone, identify the windings by continuity and polarity tests and re-tag every lead before tying anything. A color chart copied from a different motor is the fastest way to reverse a winding.

Keep reading

  • How-to

    Reconnecting a 12-lead 575 V delta motor to 480 V wye

    Reconnection follows the standard 12-lead map whether the winding is concentric or lap: jumpers 4-7, 5-8 and 6-9 come off, leads 4, 5, 6, 10, 11 and 12 tie into one star point, and pairs 1-7, 2-8 and 3-9 land on the lines. Series delta at 575 V puts 287.5 V on each group; parallel wye at 480 V puts 277 V, about 3.6 percent low. Make the move only when the nameplate lists the wye connection at the new voltage.

    Motors and motor starters

  • How-to

    Identifying leads on a six-wire two-speed single-phase motor

    No standard assigns colors to U, Um, V, Vm, W and Wm on a two-speed single-phase motor; the machine's winding diagram and rotary-switch contact schedule are the only authority. Map the six leads de-energized with an ohmmeter, land them per the schedule, and fit the specified run capacitor — 30 µF on the 230 V motor recorded here, where a 40 µF substitute ran rough on low speed.

    Motors and motor starters

  • How-to

    What a multimeter shows about three-phase motor winding resistance

    With the motor locked out and the star or delta links removed, measure U1-U2, V1-V2 and W1-W2. Three near-equal readings, continuity on every winding and no continuity between windings or to the frame pass the test. There is no fixed pass value in ohms: the correct resistance scales with the motor's size, so the comparison between the three readings decides.