Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

The starter is not tripping on overload; starting current pulled its input voltage below the operating range it protects, so it removed output. The drop comes from locked-rotor current flowing through the upstream transformer, conductors and connections, and it exists only while the motor accelerates. Measure the starter input with minimum capture during a real start, compare the lowest value against the starter's documented range, and correct the supply-side drop instead of raising any protection setting.

On this page
  1. What starting current does to the voltage at the starter
  2. Read the indication before you reset
  3. Static checks before the motor runs
  4. Catch the sag while the motor accelerates
  5. Worked example: how far a start pulls the voltage down
  6. Locate the drop and fix the supply
  7. What not to change
  8. Questions asked

A motor that disconnects one or two seconds after the start command, with no short-circuit or overload indication, has usually been let go by the starter, not by the load: starting current pulled the voltage at the starter input below the range the starter is set to protect, and the unit removed output. It presents like an overload trip because it happens under starting load, but the overload setting has nothing to do with it. The diagnosis is to measure that input voltage during a real start and find where the drop lives.

What starting current does to the voltage at the starter #

When the motor draws locked-rotor current, that current flows through the upstream transformer, the feeder conductors and every connection between them, and each impedance takes its share of volts. The voltage at the starter terminals is the source voltage minus those upstream drops, so the sag exists only while the current flows and disappears the instant the starter cuts out — which is why a reading taken before or after the start looks healthy.

A soft starter needs adequate input voltage for its thyristor gating and control electronics, not just for the motor. A soft starter handbook lists the operational voltage span of the main circuit for this class of equipment at 200 to 690 V AC, but the number that decides the stop is your model's own documented operating-range floor and its configured undervoltage trip — read both from the manual for the specific starter. One manufacturer's FAQ for the ATS22 documents that when the supply falls to zero, that starter trips immediately, overriding its undervoltage time delay. Where a separate control supply is fed through its own small transformer from the same feed, control voltage can collapse even when the power circuit survives the sag.

Read the indication before you reset #

Cycle nothing yet. The front LEDs, the display text and the fault history carry the state you need, and cycling power can erase it. Attempt one controlled start and record every colour, steady state and flash pattern from the command through the disconnect, then match what you saw against the fault table in the starter's manual — LED colour alone is not a code. The pattern separates three cases:

  • A voltage-related stop indication: the starter detected a supply condition outside its limits, which points at the measurements below.
  • The start command disappears before the output does: an interlock or the control circuit requested the stop, so trace the command chain first.
  • An overload or short-circuit indication: keep the diagnosis open and verify current and the motor circuit with the manufacturer's test procedure before trusting a visual inspection.

If the event has been logged as a fault or alarm rather than a clean stop, the same read-before-reset discipline applies when diagnosing a soft starter fault or alarm before resetting it. The warning state can be part of this picture too; read what the LED is telling you before changing settings, as in the article on the warn-failure LED before changing Ie and CLASS.

Static checks before the motor runs #

Measurements land on energized terminals: only a qualified person, using the protective equipment and work practices NFPA 70E, the 2024 edition, requires, should take them. Inspecting terminations happens only after lockout and verified absence of voltage. Then:

  • Input at rest, every line-to-line pair: each reading should match the installation's rated supply and sit inside the starter's documented operating range. A low reading before the start points upstream, not at the motor.
  • Phase balance: the pair readings should be comparable. One depressed pair sends you to that path's fuse or breaker pole, splice or terminal — and an asymmetric drop can resurface later as a phase loss fault after a voltage change.
  • Control supply, where the starter uses a separate one: within the range its documentation gives. A healthy power input does not rule out a collapsing control supply.

A normal set of static readings does not clear the supply, because the damaging drop may exist only while starting current flows.

Catch the sag while the motor accelerates #

Measure directly at the starter input during the start attempt, with a true-RMS meter in minimum-capture mode or a power-quality recorder. A display that updates about once a second can miss the event entirely. Watch four things:

  • The captured minimum at the starter input across acceleration. If it falls below the starter's documented operating range or its configured undervoltage threshold just before the stop, the supply is the cause.
  • The same minimum, captured at the upstream feeder or the source. A stable source beside a depressed starter input puts the drop in the protective device, connection or conductor between them.
  • All applicable input pairs. One pair dropping alone means an asymmetric supply-path fault; all pairs dropping together means common source impedance or total source loading.
  • The start command, at the same time. It should stay asserted until after the starter stops; if it falls first, the voltage event is a consequence of the stop, not its cause.

Worked example: how far a start pulls the voltage down #

These are illustrative example inputs, not a universal answer. Take a 480 V three-phase supply, a 500 kVA transformer at 5.75% impedance, a 100 hp motor with a nameplate full-load current of 124 A, locked-rotor current estimated at six times full-load — 744 A — and 150 ft of 250 kcmil copper feeder, at a starting power factor of 0.35 lagging.

Transformer: rated secondary current is 500,000 VA ÷ (√3 × 480 V) = 601 A, so the transformer's share of the drop is 5.75% × (744 A ÷ 601 A) = 7.1%, or 0.071 × 480 V = 34 V.

Feeder: 250 kcmil copper runs roughly 0.085 Ω per 1000 ft of resistance and 0.060 Ω per 1000 ft of reactance in steel conduit. At a 0.35 power factor the effective impedance per conductor is (0.35 × 0.085 Ω) + (0.937 × 0.060 Ω) = 0.086 Ω per 1000 ft. Over 150 ft: 744 A × 0.086 Ω × 0.150 = 9.6 V line-to-neutral, which is √3 × 9.6 V = 16.6 V line-to-line.

Total drop 34 V + 16.6 V ≈ 51 V, so the starter input sits near 480 V − 51 V = 429 V, about 89% of nominal. That is an estimate: read the motor's actual locked-rotor data, measure the impedances that matter on your installation, and check the result against the governing code. Whether 429 V stops your starter is decided by its own operating-range floor and undervoltage setting — the 200 to 690 V AC class span describes where the power circuit can operate, not where your trip is set.

Locate the drop and fix the supply #

Compare the simultaneous source and starter-input captures from the same start, and correct loose or damaged terminations using the equipment manufacturer's connection procedure after isolation; replace a failed protective-device pole once you have confirmed it. Then compare the installation against its design: conductor size and length, transformer capability, and everything else running during the start. High source impedance and simultaneous large loads are the recurring causes of a start-only sag — the same source-impedance arithmetic used when estimating transformer energization voltage sag applies here, because both events are large currents through one impedance. Lengthening the ramp or lowering the current limit reduces the drop in proportion to the current it allows, buying margin on a marginal supply while stretching acceleration time and motor heating; on a badly undersized transformer or feeder it is a workaround, not a fix.

What not to change #

Do not raise the overload setting, the instantaneous setting or the undervoltage threshold to keep the starter alive on a sagging supply; masking a voltage problem with protection settings leaves the motor heating on low voltage and hides the supply fault. The article on why raising a magnetic overload setting won't fix a hard start covers why that move fails, and it fails here for the same reason. Power factor correction capacitors will not fix it either, as the article on capacitors and motor starting sag explains. And if the overload path really is tripping — the sag genuinely leaves the motor too little torque and it stalls — that is a different failure, and the article on why a soft starter overload trip during start means a stalled motor takes it from there. Restore the original protective settings after the repair, and repeat the start with the instrument still connected before you call it fixed.

Questions asked

Why does the motor run fine uncoupled but stop on a loaded start?

An uncoupled start draws a fraction of the current and produces almost no voltage drop, so the fault cannot show itself. The sag appears only when the motor accelerates the real load. Repeat the capture with the machine connected and the coupling in place; a test that skips the load tests the wrong condition.

Will a longer ramp or a lower current limit fix the stop?

The voltage drop is roughly proportional to the starting current, so halving the current limit roughly halves the transformer and feeder drop, while roughly doubling acceleration time and the heat generated in the motor and the starter. That can buy margin on a marginal supply, but it is not a cure for an undersized transformer or feeder; fix the supply path first.

What kind of meter catches a start-only voltage sag?

A true-RMS multimeter with a fast minimum-hold function, or better a power-quality recorder, retains the lowest value during the start. A meter whose display updates about once a second can read normal before and after the event while missing the sag that caused the stop. Record at the starter input and at the source at the same time.

How low can the voltage go during a motor start?

The National Electrical Code, 2023 edition (NFPA 70), sets no numeric limit on voltage dip during starting. The binding numbers are the starter's documented operating range, its configured undervoltage threshold, and the hold-in voltage of any contactor coils fed from the same sagging feed. Measure the dip and compare each of those against it, then confirm with your local authority having jurisdiction and the starter documentation.

Does every sag trip the starter immediately?

Not necessarily. Many starters apply a configurable undervoltage time delay, so a short shallow sag rides through it. One manufacturer's FAQ documents that when its starter's supply falls to zero, the trip is immediate and overrides the delay. A short, deep sag can therefore stop the motor faster than the configured delay suggests.

Keep reading

  • Troubleshooting

    Why an autotransformer starter fails after a voltage sag

    A voltage sag deeper than the contactor's hold-in voltage and longer than its dropout time opens the starter while the run command stays on. The coil picks the contactor back in hundreds of milliseconds later, into a coasting motor whose residual voltage is out of phase with the restored supply. That reconnection transient through the autotransformer tap winding wrecks it; the fix is residual-voltage-supervised restart logic, not a new transformer.

    Motors and motor starters

  • Troubleshooting

    Why a soft starter barely improves utility bus voltage dip

    On a fixed-impedance screening calculation, cutting starting current from 600% to 400% scales a 10% utility-bus dip to about 6.7%, so a modeled 2-point gain signals a study-method or data problem, not a soft-starter fault. A 10% dip on a shared medium-voltage feed also exceeds the roughly 5% planning ceiling utilities apply at the point of common coupling. Keep the starter for the motor and the mechanical train; fix the study, then the supply, before ruling the starter out.

    Motors and motor starters

  • Troubleshooting

    Soft starter overload trip when a generator fails

    The overload trip is the starter's thermal protection responding to real motor heating caused by the voltage sag, extended acceleration or a mechanical reload, not a starter fault. Find and fix the supply disturbance and load condition; raising the setting removes protection the motor still needs. Most starters store trip events, not voltage records, so capture the disturbance with a power-quality recorder.