Troubleshooting
Soft starter warn failure: read the LED before changing Ie and CLASS
Short answer
Decode the warn or failure LED pattern against the operating instructions for the starter's complete order number before changing anything. Set Ie to the nameplate rated current for the connected winding arrangement, 128 A in the example rather than the 109 A the pump draws running, and set CLASS one step above the measured acceleration time after the motor data confirms it tolerates the longer current. Raising Ie above nameplate or dropping it to the running current both mis-set the overload.

On this page
An intermittent warn or failure indication on a soft starter is a symptom reading, not a settings verdict. The LED pattern tells you which internal state the starter reached, and the operating instructions written for the starter's complete order number are what decode it. Ie and CLASS then decide whether the electronic motor overload behaves correctly through a legitimate start. Set Ie to the nameplate rated current for the winding arrangement actually connected — 128 A for the 75 kW pump motor in the worked example, not the 109 A it draws while running — and set CLASS one step above a measured acceleration time, then find the varying condition that produces the warning. The sequence below runs decode, set, measure, decide.
Record the indication before you reset anything #
On most starters a warning flags a condition while operation continues, and a failure flags one that interrupts or blocks it — but the exact split, and every color and flashing pattern, is defined in the starter's operating instructions, not by habit. Copy the complete order number from the starter label first: a shortened type designation will not pull the right instruction set, LED table and rating data. With the indication present, record:
- Which LEDs are lit, which are steady, which flash, and whether the pattern changes over time.
- When it appears: during acceleration, during loaded running, immediately after the start command, or only after repeated starts.
- Whether the run command stays active and the motor keeps turning, or the starter stops the pump.
- How long the starter ran before the indication appeared.
- Any stored fault or trip history entries, with timestamps, before anything is cleared.
Photograph the indicator panel during the event. Work the record through the same sequence as diagnosing a soft starter fault or alarm before resetting it: the pattern and its timing decide whether this is a starting problem, a thermal problem or a load problem, and that decision tells you whether the overload settings are involved at all. A bare note that the failure light came on deletes the exact information the LED table needs.
Set Ie from the nameplate, not the running current #
Ie sets the reference current for the starter's electronic motor overload, and on most models it scales the other current-based protections too. The reference belongs to the motor, not to the process: the nameplate states a rated current for a stated supply voltage and winding connection, and the value to enter is the row matching what is actually wired in the terminal box. Dual-rating nameplates carry one current per voltage-and-connection pair, so confirm the connection links before entering anything.
In the example, the pump motor's nameplate row for the connected supply gives 128 A and the pump draws 109 A per line while running. That ratio is 109 / 128 = 0.85, so the pump sits at 85% of the motor's rated current at this process point. The number describes one operating condition; it does not set the protection. Enter the running current as Ie and every legitimate excursion above it — colder product, a throttling change, a supply dip raising current at the same shaft load — becomes a nuisance trip inside the motor's own rating. Enter more than the nameplate current to silence trips and a real overload heats the winding before the overload model reacts.
Decision: Ie equals the nameplate rated current for the connected arrangement. It is the same discipline as setting overload relays from motor nameplate full-load current, applied to the soft starter's electronic version of the same protection.
What CLASS sets and what it does not #
CLASS selects the overload trip class: how fast the electronic overload reacts to a heavy multiple of its set current. IEC 60947-4-2, the IEC product standard for AC semiconductor motor controllers and starters, defines the classes by maximum trip time at 600% of the set current, and soft starter overload documentation states the same definition: Class 10 trips within 10 seconds at 600%, Class 20 within 20 seconds, Class 30 within 30 seconds. Some models add intermediate or extended electronic classes; the instruction list for your order number names the ones your starter has. Confirm the definition against the edition in force at the installation and the equipment documentation, and with the authority having jurisdiction where a local code adopts the requirement.
CLASS is not a current setting — that is Ie — and it is not a fixed allowance in seconds for every start. Below the 600% test point the overload integrates heating and takes longer than the class number to trip; above it, sooner. The class number is a characterization point, not a start duration. The time-current shape behind the numbers is the same as for a contactor-and-overload assembly, and reading overload relay trip classes and curves walks through that curve work in detail.
Pick the class from a measured acceleration time #
Measure from the start command to stable speed on a typical start, current limit left where it is, then repeat on a cold start and on the heaviest process condition you can create. That measured time selects the class.
Worked example: the pump reaches stable speed 8 seconds after the start command. Against Class 10, that start consumes 8 / 10 = 80% of the 10 seconds the class permits at 600% of the set current. Keep a start under roughly 80% of its class time so ordinary variation — supply sag, colder product — cannot push it past the trip point. An 8-second start is therefore the practical edge of Class 10, and the pump belongs in Class 20.
Confirm two things before stepping up a class: the motor's thermal data must cover the longer heavy-current duration the higher class permits, and the starter's permitted starting duty must allow the resulting starts. If the motor data does not reach the class the start needs, the start itself is the fault — reduce the demand instead of widening the protection. The mechanism is covered in why a large motor stalls when the soft starter hits current limit, and setting a soft starter current limit without overheating the motor covers the limit adjustment.
| Measured acceleration time | Class to set | Confirm before you set it |
|---|---|---|
| Up to about 8 seconds | Class 10 | Starts repeatable at the set current limit |
| About 8 to 18 seconds | Class 20 | Motor thermal data covers the longer duration |
| About 18 to 28 seconds | Class 30 | Motor data and starting duty both cover it |
| Longer than about 28 seconds | None — fix the start | Current limit, supply voltage, pump load |
Decision, case by case: acceleration up to about 8 seconds, Class 10; up to about 18 seconds, Class 20; up to about 28 seconds, Class 30; beyond that, no class is the answer, the start is.
Chase the condition that makes it intermittent #
A settings change cannot explain a warning that comes and goes; a varying condition can. Measure during a start that actually shows the indication, not only during a clean cold start:
- All three line currents, on a true-RMS clamp rated for distorted waveforms. During phase-controlled acceleration the current flows in chopped, non-sinusoidal pulses and an average-responding meter underreads; once the bypass contacts carry the current the waveform is sinusoidal again and an ordinary true-RMS reading holds.
- Phase balance while running. A difference between phases with no load explanation points at the supply or a connection.
- Supply voltage phase to phase at the starter terminals while the motor starts. A sagging supply stretches acceleration and stacks heat into motor and starter together.
- Start count and intervals around the events. Thermal accumulation shows up on the second or third start of a duty cycle, not the first, so log starts and cooling gaps across a full day of normal operation.
- The pump's operating point around the events. Throttling changes, colder or thicker product, and any scraping or binding raise shaft load and line current together.
- Power connections. With the circuit de-energized, locked out and tested for absence of voltage, torque-check the terminals and look for discoloration.
That last bullet is the safety boundary for the whole list: open nothing in the starter enclosure or the motor terminal box until the circuit is de-energized, locked out and verified dead, and keep live current measurement to qualified personnel following the plant's approved procedure.
The decision, in order #
- Record the LED pattern and the complete order number, and decode the indication in the matching operating instructions. If the flagged cause is not motor overload, follow that path and leave the overload settings alone.
- Confirm the connected winding arrangement and supply voltage against the nameplate, then set Ie to the rated current for that arrangement — the nameplate value used throughout this article.
- Measure acceleration time at the set current limit on typical, cold and worst-case starts, and pick the class from the table above after the motor's thermal data covers it.
- Correct the varying condition the measurements point at — supply, load, duty cycle or connections — instead of raising a setting to hide the warning.
- Change one setting at a time, record the old and new value, and repeat the same test so the result tracks the change.
- Accept the repair on a normal run indication, acceleration inside the documented limits and no recurrence of the warn or failure pattern across a full duty cycle.
Questions asked
Why does the warn or failure indication only appear sometimes?
Because the conditions behind it move: supply voltage under start, product temperature and thickness, cooling time since the previous start, and thermal accumulation across a duty cycle all shift the current and the heating. A warning tied to those conditions shows up on the hard starts and skips the easy ones. Measure current, acceleration time and the indication moment during an event, and log the start count across a full day of normal operation.
Can I raise the trip class to stop the warning from coming back?
Only when the motor's thermal data covers the longer heavy-current duration the higher class allows. The class widens how long the overload tolerates a heavy current; if the winding cannot absorb that heating, the motor becomes the part that limits the start. When the motor data does not reach the class, shorten or soften the start instead through load, supply voltage or the current limit, and treat the warning as pointing at a cause, not a setting.
The nameplate shows two rated currents for two voltages. Which one is Ie?
The row that matches the supply voltage and the way the windings are actually connected in the terminal box. Each pair on a dual-rating nameplate belongs to one connection, and entering the other row skews the overload reference by the ratio between the two currents. Open the terminal box only after the circuit is de-energized, locked out and verified dead, then read the connection links and take the matching current.
What if the indication returns after both settings are verified correct?
Then the settings were never the cause, and the LED table should have said so. A pattern that flags starter overtemperature, phase loss or a supply fault keeps appearing no matter how the overload is configured. Follow the specific cause the instructions name for that pattern: measure the supply and phase currents during an event, check the starter's cooling clearances and duty cycle, and go to the manufacturer's support with the complete order number and the recorded pattern when the documented path runs out.