Why a soft starter trips a bypass failure fault after start

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

On a bypass-equipped soft starter, a stop about five seconds after the start command that reports a status or bypass failure is usually the ramp-up check, not a broken bypass: the ramp ended before the motor reached speed. Record the LED pattern, confirm the decoded fault, then raise the start voltage or ramp time until the motor accelerates inside the ramp, and only condemn the bypass after supply, control and acceleration checks pass.

On this page
  1. Record the indication and the found settings first
  2. Why the trip lands on the ramp end
  3. Worked example: torque against the ramp
  4. Power and control checks before blaming the bypass
  5. The decision, case by case
  6. Questions asked

A soft starter that spins the motor and then trips with a status or bypass failure indication about five seconds after the start command reaches the start input (terminal IN (1) on the unit behind this symptom) is usually reporting an unfinished start, not a broken bypass. The Siemens SIRIUS 3RW30/3RW40 operating instructions document a motor ramp-up detection that stays active in every start mode, and it judges the start at ramp end: a motor still below speed at that moment gets no handover to the bypass, and the starter trips with the fault. That timing is the diagnosis. Record the indication, prove the supply and the start circuit, then correct the start voltage and ramp time until the motor accelerates inside the ramp, and condemn the bypass only when a verified-clean start still ends in the decoded fault.

Record the indication and the found settings first #

Before any setting moves, establish whether you read a decoded diagnostic or an interpretation of a lamp. The 3RW30/3RW40 instructions name BYPASSED and FAILURE status LEDs and signal a successful start through the BYPASS output and the STATE / BYPASSED LED, so the printed legend on your unit decides what the trip means. One documented trap: a flashing red FAILURE LED is not a described state for the 3RW40, and the manufacturer's published support entry written for exactly that report concludes the lamp was most likely the flashing overload LED. Read the legend before you accept "bypass failure" as the message.

Record before changing anything:

  • Every LED at rest, through the ramp and at the trip: label, color, steady or flashing, repeat pattern.
  • The decoded fault text or code and the stored fault history, where the unit or its display provides them.
  • The complete order number and rating markings from the nameplate, so the instructions you open match the installed unit.
  • The settings as found: initial voltage, ramp time, current limit, control mode. Photograph them before anything moves.
  • The measured stop delay from the leading edge of the start command.

If the pattern decodes to overload, phase loss or anything other than the ramp and bypass monitoring, follow that path in the manual instead of this one; the same indication-first discipline is set out in Diagnosing a soft starter fault or alarm before resetting it.

Why the trip lands on the ramp end #

Through the ramp the starter holds reduced voltage on the motor and raises it toward full across the programmed ramp time. Ramp time programs the voltage profile; it does not schedule the motor. At ramp end the ramp-up detection asks whether the rotor is actually at speed, because handing a still-slow motor to the bypass applies full voltage at high slip; the starter refuses the handover and signals status/bypass failure instead. Measure the stop delay and put it beside the programmed ramp time: a stop that lands on ramp end points at acceleration, and a stop at an unrelated moment points at the supply, the start circuit or the load.

Which way a given start falls is decided by the induction-motor torque law: torque at the motor follows the square of the voltage reaching its terminals. Every setting correction below rests on that law.

Worked example: torque against the ramp #

All numbers here are example inputs for checking the method, not factory defaults; the torque law is general physics. Motor: 30 kW, 400 V, three-phase, nameplate full-load current 58 A, driving a centrifugal fan. Settings as found: initial voltage 50%, ramp time 5 s, current limit set to four times nameplate current, 4 × 58 A = 232 A.

Torque at the setting: (0.50)² = 0.25, so the motor has about 25% of its full-voltage torque while the ramp holds that fraction. A fan's demand rises with the square of speed, so the load torque overtakes that margin before the motor is halfway to speed; the rotor stalls below speed, the current limit holds the line current at 232 A for the rest of the ramp, and ramp end arrives with the motor still slow. The bypass fault follows.

The fix uses the same arithmetic: 70% initial voltage gives (0.70)² = 0.49, about 49% of full-voltage torque, enough for this fan to break away and accelerate. The confirming sign is current leaving the 232 A plateau and falling toward the 58 A nameplate before ramp end, at which point the handover succeeds and the fault stays clear. The limit value is a setting with its own procedure: Setting a soft starter current limit without overheating the motor.

Compound a weak supply and the setting loses more: a 10% sag puts 360 V on the 400 V motor, so the 50% setting delivers 0.50 × 360 V = 180 V, which is 45% of rated, and torque falls to (0.45)² ≈ 0.20, about 20% of full-voltage torque. Stated the other way, a 10% sag costs 19% of torque (0.90² = 0.81). A diagnosis that ignores the sag over-credits the setting.

Power and control checks before blaming the bypass #

De-energize, lock off and verify absence of voltage with a tester you have just proven on a known live source before opening the starter covers or the motor terminal box; live measurements during a start belong to qualified people using instruments rated for the circuit.

With the covers off, then through a controlled start where safe access allows:

  • Supply through the start: a sag deepens the torque loss by the square of the drop, as the example above shows.
  • Terminations: line and motor conductors on their designated terminals per the wiring diagram, no loose lug, discoloration or heat marks. One dropped phase collapses torque.
  • Motor connection: star or delta as the nameplate requires for your supply voltage.
  • Start command integrity: monitor the input through the whole ramp. A permissive or auxiliary contact that opens partway produces a stop that looks identical from the front of the panel.
  • The driven machine: coupling made up, brake released, no jam, and the process not holding the shaft.

Settings and their permitted ranges come from the instructions for your order number; editions and options differ between units.

The decision, case by case #

Recorded indication What it points to Decision
Stop delay matches the programmed ramp time; motor turns slowly or stalls Acceleration unfinished at ramp end; ramp-up monitoring tripped, not a failed bypass Raise the initial voltage in steps and re-test once; extend the ramp time only when the current limit pinned the current for the whole ramp
Flashing red lamp read as FAILURE Not a documented 3RW40 state; the manufacturer's support answer to that exact report points to the flashing overload LED Re-check the legend, then follow the overload path in the manual
Decoded supply or phase fault mid-ramp Supply or termination problem Correct wiring with power isolated, confirm the supply through a start, then attempt again
Clean supply, valid command, proven acceleration, still a decoded bypass fault Bypass element or its monitoring inside the starter Manufacturer's documented fault procedure or an authorized repair channel; never bridge power terminals or add an improvised contactor

Commit the call this way: when the trip lands on ramp end, you are looking at an acceleration problem, and the fault should clear on the first start whose current falls toward nameplate before ramp end. Raising the initial voltage is the lever, and its effect on breakaway is worked through in Why a soft starter start voltage decides if the motor breaks away. Only a start with verified supply, a command that stays valid to ramp end and measured near-full-speed acceleration, still ending in the decoded fault, puts the starter itself in the dock; that unit goes to the manufacturer's repair channel, never onto a bridged terminal board.

Questions asked

Does a bypass failure fault mean the bypass inside the starter is damaged?

Rarely on the first occurrence. On starters with ramp-up monitoring, the same message appears whenever the motor has not reached speed by the end of the ramp, because the starter then refuses the handover to full voltage. The bypass element carries current only after that handover, which makes it the last suspect in the chain. Condemn it only when supply, control wiring and measured acceleration have all passed and the starter still reports the fault.

Why does the trip time match my ramp time setting so exactly?

The ramp-up check runs at the end of the programmed ramp, so a stop caused by unfinished acceleration lands on that moment almost exactly. A thermal overload behaves differently: its trip time grows with how far the current exceeds its setting, and it can trip during running, not just at ramp end. Matching your measured stop delay to the ramp setting is the fastest way to separate the two.

How should I raise the start voltage without cooking the motor?

Step the initial voltage up in increments of about 10% of rated and make one start per change, watching the current. The motor is accelerating only once current leaves the current-limit plateau and falls toward nameplate before ramp end; if it stays pinned, raise the voltage further rather than the ramp time alone. Limit attempts, because each stalled start heats the rotor quickly, and respect the starter's allowed starting rate.

Can I install a contactor around the starter to keep the motor running?

No. Bridging the starter's power terminals or adding an improvised bypass contactor defeats its protection and its short-circuit current rating. The starter's internal bypass closes only after a valid ramp, and an external contactor, where the application truly needs one, belongs to the starter manufacturer's documented scheme with its own overload protection and coordination, wired and commissioned to that scheme.

Keep reading

  • Troubleshooting

    Fixing a soft starter phase loss fault after a voltage change

    Set the soft starter's mains voltage parameter to 400 V and its motor rated current to the pump's 400 V nameplate value. The phase-loss monitor compares each phase with the programmed reference; at 400 V on a 690 V setting every phase reads about 42% low, past the documented 15% drop threshold, so the starter trips loss of phase even with all phases present.

    Motors and motor starters

  • Explainer

    Why a single-phase soft starter can't fix a heavy fan start

    No setting rescues this start: the single-phase ATS01-type soft starter ramps voltage over a documented 1 to 5 seconds, and at fixed frequency 60% voltage leaves only 36% torque, so a heavy fan sits near stall at near-locked-rotor current until the overload or the supply fuse operates. The fix is a three-phase motor on a VFD sized for the single-phase supply, with acceleration set to 20 to 30 seconds.

    Motors and motor starters

  • Troubleshooting

    Diagnosing a motor pulsating in soft starter bypass

    Confirm from the single-line that the bypass contactor shunts the SCR stack; once it is closed and carrying the motor, the pulse is coming from the supply, the bypass path or the load, not the starter electronics. The two reported voltages put the unbalance at 2.2% or worse, above the 1% derating threshold of NEMA MG-1-2011, and a synchronized capture of voltages, currents and shaft motion tells which side leads each reversal.

    Motors and motor starters