Why AC servo motors are three phase and where the brake goes

Variable frequency drives Published 9 min read By Current Intel engineering team

Short answer

A three-phase axis motor with a rear encoder is a closed-loop AC servo: its drive synthesizes the three phases, brakes the axis electrically on every stop, and handles the returned energy on its DC bus. A mechanical holding brake is not a stopping device — it only secures gravity-loaded axes such as a Z axis, is usually a factory-built motor option, and runs on a dedicated 24 V DC circuit.

On this page
  1. Why is a CNC axis motor three phase?
  2. Can a three-phase servo motor run straight from the shop supply?
  3. How does a servo drive stop the motor without a DC brake?
  4. Where does the braking energy go?
  5. Does a CNC Z axis need a holding brake?
  6. Why is a servo motor with a brake longer than one without?
  7. How is a servo holding brake powered and controlled?
  8. What should you check before powering an unknown servo axis?
  9. Questions asked

Three AC axis motors, three-phase on the nameplate, an extra shaft out the back of each for an encoder, matched drives in the cabinet, and no DC brake anywhere on the machine: that is not a wiring mistake, it is a standard servo CNC. The three phases come from the axis drive, not from the incoming supply, and the drive brakes every axis electrically on every stop, so no separate stopping brake is needed anywhere. A mechanical brake exists only where gravity can move an axis once torque is gone — normally the Z axis, often built into the motor itself or into the machine structure. The sections below give the mechanism, one worked example with the arithmetic, and the decision for each axis.

Why is a CNC axis motor three phase? #

Because the drive, not the supply, makes the three phases: an AC servo motor is a permanent-magnet synchronous machine whose stator takes three phase currents synthesized by the servo amplifier, phase-locked to rotor position by the rear encoder, so it produces controlled torque at any speed, including zero.

An AC servo motor is a permanent-magnet synchronous machine: permanent magnets on the rotor, three windings on the stator. The drive rectifies the incoming supply to a DC bus, then inverts that bus into three phase currents whose amplitude, frequency and phase angle follow the rotor position the rear encoder reports. Three phases are the standard choice here because the winding set cancels torque ripple and keeps the power stage working efficiently, but the phase count is not what makes the machine a servo — the encoder is.

Closed-loop control on rotor position is what lets the drive produce positive torque, negative torque and holding torque at standstill. That is also why the motor, encoder and drive are matched as a set: a servo motor without its encoder cannot be commutated, and a drive without its configured motor data cannot regulate the axis. The nameplate phrase three phase describes the winding, never a line connection.

Can a three-phase servo motor run straight from the shop supply? #

No. The three phases on a servo motor's nameplate come from its own drive: the inverter stage sets voltage, frequency and phase angle against the encoder, and connecting the motor to the incoming supply can damage the motor, the drive or both.

Follow the terminals and the architecture becomes obvious: the machine's incoming supply lands on the drive's input, and the drive's motor output terminals land on the motor. Everything between them — rectifier, DC bus, inverter, commutation from the encoder — exists precisely so the motor never sees the raw supply. A permanent-magnet rotor dragged around at a fixed line frequency cannot follow it: without encoder-driven commutation the motor cogges, overheats or pushes energy back at the supply stage, and none of that is a controlled machine.

Direction never comes from swapping phases at the motor either; it comes from the motion command and the drive configuration, so reversing an axis is a parameter or command change, not a wiring change. Before opening a motor terminal box or a drive cover for any of this, de-energize the machine, lock it out and verify absence of voltage with a tested meter — that step, not the machine's history, is what makes the inspection safe.

How does a servo drive stop the motor without a DC brake? #

The drive commands negative torque: closed-loop control lets the amplifier hold torque, speed and position through a profiled deceleration to exactly zero speed, which is why an encoder-equipped servo axis needs no injection or friction brake to stop on command.

DC injection and other drag-to-rest methods belong to line-start induction motors, where nothing has to land on a coordinate — AC motor braking methods for single and three phase motors covers that world. A servo stop is torque-controlled from commanded speed down through zero, then the drive transitions to holding the position actively, so the axis settles where the program asked it to settle.

Machine standards name these states: IEC 60204-1 (2016 edition) sorts stop functions into category 0, immediate power removal; category 1, a controlled stop followed by power removal; and category 2, a controlled stop with power retained. The profiled servo stop is the category 1 or 2 path, and the power-off brake is what makes a category 0 power removal end with the axis held. Confirm the categories your machine actually assigns with its documentation and your local authority having jurisdiction.

Where does the braking energy go? #

Into the drive's DC bus: a decelerating axis turns its motion into electrical energy that charges the bus, and the drive bleeds that energy off through its regen circuit or braking resistor; a 0.2-second stop of a small axis returns roughly 25 joules.

Worked example, with example inputs rather than a measured machine: total inertia at the motor shaft J = 0.0005 kg·m² (0.0002 from the motor, 0.0003 reflected from the load), deceleration from 3000 rpm to rest in 0.20 s, on a 2 kW-class axis.

  • Speed: 3000 rpm × 2π ÷ 60 = 314.2 rad/s
  • Deceleration rate: 314.2 ÷ 0.20 = 1571 rad/s²
  • Braking torque: T = J × 1571 = 0.0005 × 1571 = 0.79 N·m
  • Rating check: at 314.2 rad/s a 2 kW motor is rated 2000 ÷ 314.2 = 6.4 N·m, so the braking demand is about 12 percent of rating
  • Energy per stop: E = 0.5 × 0.0005 × 314.2² = 24.7 J

The braking torque lands well inside the motor's rating and the returned energy is a modest pulse for a drive's regen circuit, so a profiled electrical stop is ordinary duty for such an axis. If that same stop trips a bus overvoltage fault instead, the regen path is the suspect — braking hardware missing, undersized or open-circuited, or a deceleration set too aggressive — and why a VFD DC bus overvoltage fault appears at random walks that diagnosis.

A vertical axis adds its descents to the energy budget: every powered downward move on the Z returns gravitational energy to the bus as well, which is why regen capacity is checked against the machine's actual cycle. On multi-axis machines the drives normally share one supply and one regen/filter group, so the budget is common, as DC bus sharing on servo drives: one supply, one filter group explains.

Does a CNC Z axis need a holding brake? #

Usually yes: any axis that gravity can move when servo torque is gone needs a holding brake, a counterbalance or a self-locking screw, and on a typical vertical machining axis that means a spring-applied brake that engages on power loss; horizontal axes normally need none.

The two duties are different, and the drive only covers one of them. During motion and at commanded rest, servo torque carries the load; the moment torque disappears — power off, drive fault, emergency stop — something static must catch the head. That static catch is the holding brake's whole job, and on servo machines it is sequenced: the drive releases the brake only after it has the load under torque, and reapplies it only after motion has reached zero.

Verify a Z axis in that order, with the head mechanically supported first: enable the servo with no motion command and confirm holding torque, watch the brake release on a short jog, command a stop and watch the brake apply at zero speed, then disable and confirm the load stays put.

If the machine has no brake circuit at all, look for the other two answers: a counterbalance cylinder or counterweight, or a self-locking screw. The measurement that decides it is simple: with torque removed and the load restrained, does the axis move under gravity? If yes, fit or verify a holding brake or counterbalance; if no, the axis is correct as built — and the same rule clears every horizontal axis on the machine.

Why is a servo motor with a brake longer than one without? #

The brake is a separate spring-applied unit mounted at the back of the motor, so a brake-built motor extends past the encoder; in the field, brake-built axis motors often measure roughly 60 to 70 mm longer than the same frame without one.

Brake-built motors carry the brake as a factory-installed unit behind the encoder, so it adds axial length and usually its own pair of coil conductors or a second connector; it is not a bolt-on accessory, and servo manufacturers document it as a factory option only. Length is therefore an inspection clue, not an identification method: frame dimensions differ between series and revisions, so read the motor code on the label and the drive's configured motor data to establish what is installed. Roughly 60 to 70 mm of extra length is a fair field rule of thumb for a brake-built frame, nothing more precise than that. The general effect is familiar: built-in options extend the motor behind the flange, the same reason covered by why replacement brushless DC motors are often longer when a factory option carries into a replacement.

How is a servo holding brake powered and controlled? #

Through its own low-voltage circuit: servo motor brake coils are 24 V DC units that manufacturers specify a dedicated supply for, energized to release and de-energized to apply, sequenced so the brake never opens before the axis has torque.

The coil is energized continuously while the axis is enabled — releasing the brake costs power the whole time the machine runs, which is why a failed 24 V DC supply or coil shows up as a stalled, faulted axis rather than a falling one. Manufacturers of these brakes specify a dedicated supply for the brake coil alone, not shared with other control loads, with suppression across the coil and the drive or machine relay sequencing apply and release against servo state. Match every connection to the machine's documentation before first power: an unidentified brake coil never gets connected across a supply on guesswork, because the apply and release sequence is part of the axis's safety behavior.

What should you check before powering an unknown servo axis? #

Identity, wiring and feedback, in that order: read the motor code and the drive's configured motor data, confirm the drive's motor outputs feed the motor and the encoder its own port, and only then enable with motion inhibited; every mismatch shows up later as a fault or unstable motion.

  1. Record each motor's code, ratings and encoder type from its label, and confirm the drive's configured motor data matches before applying power; a generic winding description is not the installed rating, and the nameplate and drive data decide the connection.
  2. With the machine still locked out, confirm the motor leads land on the drive's motor output terminals in the documented order and that nothing ties the motor side to the incoming supply.
  3. Inspect the rear encoder: shaft, coupling, connector seating and cable shield. The drive commutates from that signal, and a loose coupling or damaged feedback cable shows up as unstable or hunting motion rather than a clean trip — why a drive-controlled motor runs unstably and how to trace it covers that trace.
  4. Identify the brake circuit before first power: coil conductors, the relay or drive output that sequences it, and the coil's own supply.
  5. Enable with motion inhibited, confirm no feedback diagnostic, jog slowly in both directions, command a stop from a low speed, disable, and confirm a gravity-loaded axis remains held.

Pass all five before raising speed or load, and record any diagnostic the drive displays before cycling power, because the code separates feedback, motor-matching and brake-sequence causes faster than any guess.

Questions asked

Can I add a holding brake to a servo motor that was built without one?

No. On these servo lines the holding brake is a factory-installed option on the back of the motor, not a bolt-on accessory, and the manufacturers document it that way. Order a brake-built motor code when the motor is replaced, or mount a brake in the machine mechanism, and match the drive's brake-control output to whichever arrangement the machine uses.

Why does a Z axis click a moment after the drive disables?

That click is the spring-applied brake engaging. The brake is designed to hold with its coil dead, so it snaps on whenever the drive removes torque — at disable, on a fault, or at power loss. Silence after a disable is the bad sign: it means the brake coil, its 24 V DC supply or its sequencing relay did not drop out, and the axis is relying on servo torque with no backup.

What happens if the encoder cable is damaged mid-move?

The drive loses rotor position and can no longer commutate, so it trips on a feedback fault and removes torque rather than continuing blind; on a gravity axis the power-off brake then engages. Treat the axis as tripped, not as runaway, and read the code in the drive's fault history before touching wiring or parameters, because feedback faults, motor-matching faults and brake-sequence faults can share symptoms.

Do the X and Y axes ever carry brakes?

Rarely. A horizontal slide cannot fall, so the absence of a brake there is correct design rather than an omission. The exceptions are mechanisms that can drift without torque: a tilted table, a counterbalanced ram with a failed counterweight, or a vertical arrangement on a gantry. Those get a brake, a counterbalance or a self-locking screw, judged by the same gravity test as any vertical axis.

Keep reading

  • Troubleshooting

    Why intermediate circuit voltage goes out of permitted range

    An intermediate circuit voltage out of permitted range fault means the drive's DC bus left the window its own documentation defines. The timing names the cause: a bus that sinks on acceleration points to the incoming supply, a bus that spikes on deceleration points to regenerative energy, and a slow drift points to aging DC bus capacitors or a failing supply unit. Fix the side the timing names.

    Variable frequency drives

  • Explainer

    DC bus sharing on servo drives: one supply, one filter group

    A shared DC bus collapses the AC side to exactly one protected mains supply for the whole network, caps drives at six per passive line filter, and limits total motor cable behind that filter as PWM frequency rises. Size the single breaker and filter on the group's continuous current, not the nameplate sum.

    Variable frequency drives

  • Troubleshooting

    VFD output phase loss fault: tracing the broken phase

    An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.