Why CT ratio and phase error calculations miss test data

Protection: breakers, fuses and SCCR Published 5 min read By Current Intel engineering team

Short answer

A turns-ratio calculation predicts only the ideal secondary current and will not match ratio and phase error test data. The calculation that does match uses the complex excitation current (magnetizing plus core-loss phasors) at the secondary voltage Es = Is × (Zb + Rs + jXs), iterated until Is = Ip/Kn − Ie converges.

On this page
  1. Why the ideal model fails
  2. The phasor model that does agree
  3. Worked example
  4. Reading the mismatch pattern in your test data
  5. Pitfalls that break the model quietly
  6. The decision
  7. Questions asked

Your CT error spreadsheet disagrees with the test sheet because a turns-ratio calculation models a transformer that does not exist. Real ratio and phase error come from excitation current flowing through a complex secondary circuit, and only a model that includes both will follow measured data. Accuracy classes in IEC 61869-2 are defined against a stated burden and current, so the calculation has to reproduce that exact operating point, not the nominal ratio.

Why the ideal model fails #

An ideal CT would deliver Is = Ip/Kn exactly. The real secondary winding must induce a voltage Es to push current through its own impedance and the connected burden, and producing that voltage requires excitation current Ie in the core. That current is subtracted from the ideal secondary ampere-turns, so the secondary current is always short and always displaced. The error is small only because Ie is small compared with Is, and it stops being small when Es rises: higher burden, higher current, or a core pushed toward saturation all make the discrepancy grow. If your sheet assumes the ideal case, every deviation in the test data looks like a mystery.

The phasor model that does agree #

Refer the primary current to the secondary side:

Ip' = Ip / Kn

The secondary current balance is:

Is = Ip' − Ie, where Ie = Im + Ic

Here Im is the magnetizing component (quadrature, mostly reactive) and Ic the core-loss component (in phase with Es). They are phasors: a single excitation-current magnitude cannot produce both error components. The secondary voltage that drives Ie is:

Es = Is × (Zb + Rs + jXs)

Zb is the complete external burden including leads, and Rs + jXs the secondary winding impedance. Ie is read from the complex excitation characteristic at the calculated Es, and Es depends on Is, so the loop is iterative. The why CT saturation at the knee point cuts secondary current article covers what happens to that characteristic above the knee.

Define the error signs explicitly:

  • Ratio error (%) = 100 × (|Kn·Is| − |Ip|) / |Ip|, so positive means the scaled secondary magnitude exceeds the primary.
  • Phase error = angle(Is) − angle(Ip'), after reversing Is if your polarity convention requires it.

If the test bench reports the opposite sign, change the reporting equations, not the circuit model.

Worked example #

A 600/5 A toroidal bushing CT, Kn = 120, at Ip = 3000 A. The connected burden is 0.40 Ω at power factor 0.9, so Zb = 0.36 + j0.174 Ω (angle 25.8°). Winding impedance is Rs = 0.05 Ω, Xs = 0.02 Ω. Total secondary impedance Z = 0.41 + j0.194 Ω, |Z| = 0.454 Ω at 25.3°.

Iterate, with Ip' = 3000/120 = 25 A as the reference phasor at 0°:

  1. Start with Is(1) = 25 + j0 A. Es = 25 × (0.41 + j0.194) = 10.25 + j4.85 V, |Es| = 11.34 V.
  2. Read the complex excitation current at 11.34 V from the measured characteristic; say the data gives Ie = 0.020 − j0.080 A for this core (example values for a single point on that curve).
  3. Is(2) = 25 − (0.020 − j0.080) = 24.980 + j0.080 A.
  4. Recompute Es with Is(2): |Es| = 24.980 × 0.454, magnitude about 11.34 V, unchanged at this precision, so Ie and Is have converged.

Errors from the converged phasor:

  • |Is| = 24.980 A, Kn·|Is| = 2997.6 A, ratio error = 100 × (2997.6 − 3000)/3000 = −0.08%.
  • angle(Is) = atan(0.080/24.980) = +0.18°, so the phase error is +0.18° under the convention above.

The core-loss component (0.020 A) is what makes the ratio negative; the magnetizing component (0.080 A) is what makes the phase positive. Change the burden angle and both move, which the ideal model cannot show. Transformer saturation curve: magnetizing vs excitation current covers how those two components separate on the excitation characteristic.

Reading the mismatch pattern in your test data #

Compare trends before touching any constant:

  • A nearly constant ratio offset at every current point is a scaling problem: wrong effective ratio, turn count, polarity, or instrument channel scaling. Fix the ratio or the convention, not the core model. A bushing CT ratio test that reads high is one signature of this.
  • Error that grows with burden means the secondary impedance in the sheet is incomplete. Put in the full complex burden, including lead resistance and the winding impedance on the correct side of the ideal transformer.
  • A phase trend with the wrong sign is a polarity or angle-unit conflict between the test bench and the sheet.
  • Ratio fits but phase does not: the burden angle or the core-loss component is wrong. Only complex excitation data fixes this.
  • High-current points diverging sharply means Es has entered the nonlinear region of the excitation curve, and you need measured excitation data at that voltage, not a straight-line extension. The checking a 600/5 CT ratio article covers the ratio-verification side of that bench work.

Calibrate the winding resistance from a measurement at a stated winding temperature; copper resistance rises about 0.4 percent per kelvin, which changes Es and therefore Ie at every point.

Pitfalls that break the model quietly #

  • Treating rated burden as a resistance when the connected load is not resistive. Equal burden magnitudes at different angles give different phase and ratio errors.
  • Interpolating only the excitation-current magnitude. Interpolate the real and imaginary components separately, or the phase information is gone before you start.
  • Mixing frequencies within a row. Reactances and the excitation characteristic all depend on frequency; hold one frequency per calculation.
  • Fitting a correction factor to individual test rows. A fitted table reproduces existing tests but cannot predict a new turn count, core, or burden. Keep every empirical adjustment tied to a physical term in the model.

One safety note: never open the secondary of an energized CT to measure anything; all resistance and excitation measurements are made with the primary de-energized or the secondary shorted, and confirm the procedure against your plant's electrical safety rules before opening a CT terminal.

The decision #

Build the spreadsheet on the complex equivalent circuit: Kn, winding Rs and jXs, the full complex burden with leads, and a complex excitation curve read at the iterated Es. If that model still misses the test data, read the trend table above: constant offset means fix the ratio or scaling, burden-dependent error means fix the impedance, phase-only mismatch means fix the burden angle or core-loss data, high-current divergence means nonlinear excitation data. Only after the physical model follows the measured trends is an empirical correction worth adding.

Questions asked

Why can I not use excitation-current magnitude alone in the error calculation?

A magnitude carries no angle, so it cannot be split between the magnetizing component, which drives phase displacement, and the core-loss component, which drives ratio error. One scalar value fitted to a ratio reading will then contradict the phase reading at the same point. You need the active and reactive excitation components separately, from the excitation test or a complex excitation model.

Which standard defines the accuracy the calculation is compared against?

IEC 61869-2 defines accuracy classes for inductive current transformers in terms of ratio error and phase displacement at rated current with a stated burden, plus limits for errors after transients where applicable. A calculation is checked against the class limit for the named burden; a different connected burden is a different operating point and needs its own comparison.

Does secondary winding temperature change the calculated errors?

Yes. Winding resistance rises with conductor temperature, roughly 0.4 percent per kelvin for copper, which raises the secondary voltage Es and therefore the excitation current. Calibrate the winding resistance from a measurement at a stated temperature or correct it with the conductor relationship your design process adopts, and note the temperature beside every calculated point.

Keep reading

  • Explainer

    Reverse current injection with a CT: burden voltage decides

    A CT multiplies current only into a burden that is nearly a short circuit. Into 1,200 Ω, 100 mA forces 120 V and 12 W at the output, which reflects as 75 MΩ and 30 kV on the 250-turn winding, beyond any 400 µA source and any CT core or insulation. Lower the burden to ohms or less, where secondary injection is standard practice, or drive the load from a 60 Hz source that supplies the voltage and power directly.

    Protection: breakers, fuses and SCCR

  • Comparison

    What current-only motor protection can and cannot detect

    Three per-phase current amplitudes support overload, phase loss, current unbalance, stalled acceleration and short-cycling protection, and nothing else. Undervoltage, ground fault, winding temperature and mechanical overloads such as high head pressure need their own inputs: a voltage measurement channel, a core-balance current transformer, and temperature or pressure sensors.

    Protection: breakers, fuses and SCCR

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR