Why current dissymmetry in parallel drives follows the power blocks

Variable frequency drives Published 8 min read By Current Intel engineering team

Short answer

The high-current reading moved to the opposite drive when the power blocks were exchanged, so the unequal load sharing lives in the transferred assembly or its current-measurement path, not the motor or one fixed phase. Measure all four conductors per phase on both drives at matched load, and treat the alarm as a real sharing difference until the totals say otherwise.

On this page
  1. What the dissymmetry alarm compares
  2. The currents that came with this fault
  3. Checking 108 A and 173 A against a 20% dissymmetry threshold
  4. Why the current-sensor swap did not close the case
  5. Measuring the parallel cables
  6. The decision for each case
  7. Questions asked

Two drive sections feeding one motor should split the current between them, and when they do not, the drive's dissymmetry alarm names the split without naming the cause. In the case behind this article, the loaded current sat low on one section and high on its partner; after the power blocks were exchanged between the two cabinets, the high reading moved with the blocks. That one result localizes the fault to the transferred assembly and everything moved with it — power modules, current sensors, gate driver boards and their connectors — and clears the motor, the output cables and any single fixed phase. What follows: what the alarm actually compares, a worked check of the measured currents against the installation's dissymmetry threshold, why a current-sensor swap did not close the case, and the measurements that decide the rest.

What the dissymmetry alarm compares #

Two drive sections in parallel each carry part of one machine. Here the machine is a dual-winding compressor motor, one section per winding group, and each drive checks its own section's current against its partner's. When the difference passes the dissymmetry threshold parameter — set to 20% in this installation — the drive raises a parallel-circuit current dissymmetry alarm and names a phase in its detail value. One manufacturer's parallel-drive module guide words the same condition as a current imbalance between the power units, which is precisely the comparison to keep in mind. Treat the alarm's named phase as a hint, not a verdict.

Keep two different questions apart. Phase balance inside one section is not the same as matched contributions between sections: three similar phase readings on one section prove nothing about its share against its partner. This is also a different animal from two separate motors on one drive, whose setup questions live in why a drive needs summed motor data for two motors in parallel.

Log the work done just before the alarm first appeared, because each item is a test variable: the control interface boards in both cabinets had been exchanged, the gate driver board revisions differed between cabinets, and one section's power stage had been rebuilt with new power semiconductors. None of that is a known-good baseline.

The currents that came with this fault #

Each section feeds the motor through four 4/0 cables per phase. The readings below are reported clamp measurements of one of those four cables per phase, taken with the compressor loaded (pumping air) and unloaded (idling near 700 rpm). Loaded readings:

Phase Left cabinet before exchange Right cabinet before exchange Left cabinet after exchange Right cabinet after exchange
U 108 A 173 A 188 A 108 A
V 116 A 174 A 193 A 109 A
W 112 A 174 A 190 A 110 A

Unloaded, every measured cable sat between 53 A and 55 A, in both cabinets, before and after the exchange. Three observations carry the diagnosis:

  • Within one cabinet, the three phases sit within 8 A of each other, loaded or unloaded, so no single phase carries the story.
  • Unloaded, the two cabinets agree within about 2 A, and the machine also ran uncoupled to full speed with no alarm — the split only breaks under load.
  • Loaded, the high reading changed cabinets exactly when the power blocks did.

The direction is informative too: the rebuilt power stage read low in both cabinets, and the untouched blocks read high in both. A substitution result that clean outweighs most of the rest of the record — the behavior belongs to the blocks, not to the positions.

Checking 108 A and 173 A against a 20% dissymmetry threshold #

The inputs, each with its source:

  • Left cabinet, phase U, one measured 4/0 cable, compressor loaded: 108 A (reported clamp reading from the table above).
  • Right cabinet, same phase, same state: 173 A (reported clamp reading).
  • Dissymmetry alarm threshold: 20%, the installation's setting.
  • Working assumption: the four parallel cables of the phase share equally, so each section's total phase current is 4 times the single cable reading. Equal sharing is exactly what four clamp readings must confirm, so treat the totals as provisional until then.

The rule in words: dissymmetry between the two sections is the difference between their phase currents divided by the average of their phase currents. The drive's own normalization is not stated in the material at hand, so this example uses difference over average and reads it against the 20% setting.

The arithmetic:

  • Left section, phase U: 4 × 108 A = 432 A
  • Right section, phase U: 4 × 173 A = 692 A
  • Difference: 692 A - 432 A = 260 A
  • Average: (432 A + 692 A) / 2 = 562 A
  • Dissymmetry: 260 A / 562 A = 0.46, that is 46%

The per-cable numbers give the same percentage because the factor of 4 cancels: 65 A of difference over a 140.5 A average is again 46%.

Result: the two sections run about 46% apart on this phase, roughly 2.3 times the 20% setting. The split would have to close to under about 112 A of difference on a 562 A average before the alarm stays quiet.

Decision: with currents like these, the alarm reports a real sharing difference, not a nuisance. If four-cable totals at matched load later bring the difference under that threshold while the alarm still stands, the power circuit is inside the setting and the measurement chain becomes the suspect.

Why the current-sensor swap did not close the case #

Swapping the current sensors of two phases in one cabinet moved the alarm's named phase — and then, across roughly ten compressor load-and-unload cycles, the named phase alternated between the two swapped channels. Read that honestly:

  • One steadily wrong sensor should take the alarm with it and hold it on one channel.
  • An alternating name means the indication tracks operating state: an intermittent reading path, or a real current distribution that shifts each time the machine loads and unloads.

The reported cable currents back that up: within a cabinet the phases measured within 8 A of each other, so no large single-phase imbalance shows even in the one measured cable. A drive's imbalance decisions are only as good as the currents it measures — the same principle that makes a VFD motor lost fault trip on phase imbalance when the currents the drive sees go uneven.

Decision: stop attributing this to one dead sensor. Capture each alarm event with the phase it names plus clamp readings taken at that same moment, and let a dozen such event records pick between an intermittent measurement path and a shifting sharing pattern.

Measuring the parallel cables #

One safety note first: opening a cabinet or a power section is de-energized work — lock out, wait the drive documentation's DC-link capacitor discharge time, and verify absence of voltage before touching a terminal. NFPA 70E, 2024 edition, covers safe electrical work practices; confirm the governing details with your authority having jurisdiction and the drive documentation. The clamp readings themselves are taken on live output cables with the drive running, under the site's energized-work rules and with meters rated for the job.

Then, in order:

  1. Clamp all four cables of each phase, in each cabinet, one pass per cable, at a matched load state. Expect the four to sit within a few percent of each other; one high or low cable moves the investigation to that cable and its lugs. Unequal sharing traces to the resistance of each path — length, routing, lug contact — and lug torque is the part you control; the torquing 4/0 aluminum conductors guide shows how to reach spec without damaging the wire.
  2. Compare cabinets at matched operating points taken minutes apart. The high-side readings before and after the exchange were not equal to each other, so magnitudes only compare at the same load and speed.
  3. Sum the four cable readings per phase and run the threshold arithmetic from the worked example above.
  4. Read the drive's own reported phase currents at the same moment and set them beside your clamp totals: agreement points at real unequal contribution, disagreement at the sensing chain.
  5. Inventory exactly what moved with the blocks — power modules, current sensors, gate driver boards, busbars, connectors — and what stayed: motor windings, output cables, control assignments. The differing gate driver revisions and the rebuilt power stage belong in that record.
  6. Any further exchange of blocks or boards follows the drive manufacturer's parallel-operation service documentation, which states what must match between sections running in parallel.

The decision for each case #

  • Loaded current follows the exchanged blocks, as it did here: the fault lives in the transferred assembly or the measurement hardware that moved with it. Work that inventory; the motor, the output cables and any one fixed phase are cleared.
  • Four-cable totals confirm a split beyond the threshold at matched load: a real sharing problem in the power path. Keep tearing down the transferred assembly; the blocks that read high in both positions are first in line.
  • Four-cable totals land inside the threshold while the alarm stands: the measurement chain is the suspect — sensors, gate and signal boards, connectors, revision mismatches.
  • The named phase alternates across load cycles: one fixed sensor fault is ruled out as the sole cause. Log events with currents and find the operating state at which the name flips.
  • Unloaded currents equal but loaded split: load-dependent sharing. Compare both cabinets at several load points and matched speed, and expect the split to widen with load.

Questions asked

Does a passed motor identification run or a clean uncoupled run clear the power blocks?

In this case a passed motor identification and an uncoupled run to full speed without the alarm only prove the drive-motor pair works light. The split between the two power sections appears when the machine pumps, because that is when each section carries real load. A clean no-load result neither clears nor condemns the power blocks; it just says the fault is load-dependent.

Can raising the dissymmetry threshold stop the alarm?

No. The threshold only sets when the drive reports the condition. With measured currents about 46% apart, the alarm reflects a real difference in load sharing or in the current measurement, and raising it hides the symptom while the cause stays. Find which of the two it is first; only then decide whether the setting was simply too tight for a normal operating spread.

Why did the alarm name a different phase after the sensor swap?

A single failed sensor should move the alarm to one fixed channel and keep it there. When the named phase alternated between two channels across roughly ten load cycles, one steady sensor fault no longer explains it: the reading chain is intermittent, or the real current distribution drifts with each load change. Log the named phase with the currents at each event before replacing parts.

Is multiplying one cable reading by four a valid way to get the phase total?

Only after equal sharing is established. Parallel conductors share according to the resistance of each path, including length, routing, lug condition and torque, so one conductor can carry noticeably more than its partners. Clamp all four cables of the phase, compare them, and sum them. If they agree within a few percent, multiplying one reading by four then gives a fair estimate of the phase total.

What measurement decides between the power blocks and the measurement chain?

Compare the drive's own reported phase currents with independent clamp totals taken at the same moment and load. Agreement means the drive is seeing the real unequal sharing, and the power path deserves the teardown. Disagreement means the drive's numbers are the problem, and the current sensors, their signal boards and every connector moved during the block exchange move to the top of the list.

Keep reading

  • Troubleshooting

    Why F07900 motor blocked torque plateaus at the current limit

    A torque plateau that matches the configured current limit times the motor's torque constant is proof of current saturation. F07900 reports a motor held at the torque limit below the blocked-speed threshold for more than 0.2 s; in the worked case the computed ceiling lands within two percent of the traced plateau. No parameter raises what the hardware cannot deliver, so the fix is a larger Motor Module selected from the motor's torque-current curves.

    Variable frequency drives

  • Explainer

    VFD rated current vs motor full-load starting torque

    Yes, a 4.3 A drive can start this motor at full load, but the decision is torque, not the ampere ratio. It needs a constant-torque duty rating, a 150% overload reserve, and sensorless vector or direct torque control to hold about 7.5 Nm against a 5 Nm load from standstill.

    Variable frequency drives

  • Explainer

    What decides whether a 3 HP VFD can run a 1/4 HP motor

    A 3 HP drive runs a 1/4 HP motor only when the motor's full-load current lands inside the drive's adjustable motor-current range, which on many drives reaches down to roughly one-quarter to one-sixth of the drive rating. At about 8:1 by current the quarter-horsepower motor sits below that band; at 4.5:1 a 1/2 HP motor sits inside it. The overload and current limit take the nameplate FLA, because the drive's own overcurrent trip protects only its power stage.

    Variable frequency drives