Troubleshooting
Why a VFD motor lost fault trips on phase imbalance
Short answer
A VFD motor lost fault means the drive's continuous phase-loss monitor found one output phase open or materially below the others. Compare all three phase-to-phase readings at the drive terminals and again at the motor terminals: balanced at the drive but not at the motor puts the defect in the cable, terminations or fuses between them, and imbalance already at the drive points to the output connection or winding. Fix the circuit; do not disable the alarm.

On this page
- What does a motor lost fault on a VFD mean?
- Why does the motor lost fault trip only some starts?
- Can you trust phase-to-phase voltage readings at a VFD output?
- Where is the fault if the drive reads balanced and the motor does not?
- How do you check the motor cable, terminations and fuses safely?
- When is the drive itself at fault?
- Should you disable the motor lost alarm to keep running?
- Questions asked
A motor lost fault is the drive telling you the motor circuit is broken or unbalanced, and the repair is decided by comparing the three phases at two points: the drive output terminals and the motor terminals. Balanced readings at the drive but not at the motor put the defect in the cable, the terminations or a fuse between them; imbalance already at the drive output points at the output connection or the winding. This article gives the trip logic, a measurement procedure that works on a PWM output, a worked imbalance calculation, the safety step that comes before any cover comes off, and the decision that separates a branch fault from a drive fault.
What does a motor lost fault on a VFD mean? #
A motor lost fault means the drive's phase-loss protection measured one output phase at zero or materially below the other two: one motor phase is open, disconnected or far enough out of balance that the drive stopped to protect the motor from overheating.
The monitor runs continuously on the three output currents. A phase current near zero reads as phase loss; a phase sitting materially below the other two reads as excessive imbalance. The trip is protective, not a nuisance: on an open phase the motor keeps turning on the remaining paths, torque drops and the energized windings carry more than their share, which is the mechanism described in what happens when a three-phase motor loses one phase. Before you assign a cause, pull the drive's fault history: it logs the operating point at each trip, and the fault table in your model's manual states exactly which condition this message asserts.
Why does the motor lost fault trip only some starts? #
The timing of the trip points at the failure mode: a fault on every start, immediately, means a hard open such as a missing link or blown fuse, while a trip that appears only under load or vibration points at a high-resistance joint.
Record the pattern before each reset: before the drive enables, at the instant of movement, during acceleration, at steady load, or only when the load changes. A joint that passes a low-current continuity test can still fail under motor current, and a conductor that opens when it flexes or heats will hide from a bench check. If two motors share one drive, an output contactor that never closed produces exactly this picture; that wiring case is covered in running two motors on one VFD with output contactors.
- Every start, immediately: a hard open — blown fuse, missing link, a lug that never made contact, an unplugged connection.
- At one speed or load only: a high-resistance termination that fails under current; expect heat discoloration at the bad joint.
- With vibration or after long running: an intermittent conductor at a gland, a drag chain or another flex point.
- Two motors on one drive: one output contactor not pulled in looks like a lost phase.
Can you trust phase-to-phase voltage readings at a VFD output? #
An ordinary averaging meter reads a PWM output poorly, so use a true-RMS instrument rated for drive output waveforms and treat the three readings as a comparison, not as absolute voltages; at a fixed speed the pattern matters more than the number.
The output is a switched waveform, not a sine wave, and a meter built for sinusoidal power can misreport both the magnitude and the ratios between phases; the reference method for characterizing a drive is a multi-phase power analyzer that captures the switched waveform on the input and output sides at once. For this fault you do not need absolute accuracy: you need three readings taken with the same instrument, at the same speed and load, compared with each other and with the same three readings at the other end. For the current readings at those two points, the choice of clamp is its own subject, covered in measuring VFD and soft starter current with the right meter.
Where is the fault if the drive reads balanced and the motor does not? #
Take phase-to-phase readings at the drive output terminals and again at the motor terminals at the same speed: readings that match at the drive but not at the motor put the defect in the cable, terminations or fuses between the two points.
The comparison number is percent imbalance, computed as 100 × (largest deviation from the average) / average, using the three phase-to-phase RMS voltages in volts taken at one speed. Worked example with illustrative inputs — a true-RMS meter rated for drive output, the motor at fixed speed, and readings at the motor terminals of 462 V, 478 V and 470 V:
- Average = (462 V + 478 V + 470 V) / 3 = 470 V
- Largest deviation = 470 V - 462 V = 8 V
- Percent imbalance = 100 × 8 V / 470 V = 1.70%
On the same run, the drive output terminals read 471 V, 473 V and 472 V: average 472 V, largest deviation 1 V, percent imbalance = 100 × 1 V / 472 V = 0.21%.
The decision: 1.70% at the motor against 0.21% at the drive indicts the branch between the two points, so pull and inspect the cable, every termination and every fuse in that branch. NEMA MG-1, the Motors and Generators standard, sets 1% voltage imbalance as the ceiling for continuous rated-load motor operation and calls for derating above that, so the motor end figure fails on its own. These are illustrative numbers, not a measurement of your installation: run the same arithmetic on your own readings and check the applied limit against the drive manual and the motor documentation.
How do you check the motor cable, terminations and fuses safely? #
De-energize the branch, lock it out and verify absence of voltage at the drive and motor terminals before opening any cover: NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, requires energized work to be justified and de-energizing to be the first choice. Confirm the lockout and verification steps with your authority having jurisdiction and the equipment documentation, because editions and local amendments differ.
- Drive output terminals: loose lugs, heat discoloration, corrosion, a conductor landed on the wrong terminal.
- Motor terminal box: the same defects, plus installed links and conductor positions matching the nameplate connection.
- Cable route: abrasion, crush points, sharp bends, moisture at glands, and any section that flexes in service.
- Branch fuses: check every phase; replace a blown fuse only after finding what opened it.
- Continuity and winding resistance: with the motor isolated from the drive, verify each conductor end to end, then measure the three line-to-line winding paths with the same instrument at one motor temperature; an open path, or one reading clearly apart from the other two, puts the defect in the winding or its internal links.
If the nameplate connection and the installed links disagree, the winding is set up for the wrong configuration, and the trade-offs are laid out in wye or delta winding for a 200 hp 480 V motor. Disconnect the motor from the drive before any insulation-resistance test so the tester's voltage never reaches the output stage.
When is the drive itself at fault? #
The drive itself comes into play only when the imbalance is already present at its own output terminals after the cable, terminations, fuses, wiring and windings have all passed inspection; then stop and refer the unit to the drive supplier for output-stage diagnosis.
The two measurement points sort every case:
- Balanced at the drive, unbalanced at the motor: the branch between the points holds the fault — cable, terminations or fuse. The drive is cleared.
- Unbalanced at both points: work outward from the drive — the output connection first, then the winding.
- Unbalanced at the drive with everything downstream verified: refer the unit for output-stage diagnosis, and stop resetting it while you wait.
After repair, torque the terminations to the values in the equipment instructions, restore covers and guards, and run a controlled start. Watch the three phase currents at the load point that used to trip, then repeat the stop and restart cycles that produced the fault. The repair holds when the monitor stays quiet at every operating point that tripped before.
Should you disable the motor lost alarm to keep running? #
No: disabling the motor lost alarm removes the protection that stops the motor before an open phase cooks the windings, and it leaves the original fault in place; fix the circuit first, and treat the disable parameter as a design decision, never as a repair.
The drive does offer the disable as a setting, and a machine designer may legitimately apply it where the application requires no phase-loss protection and the wiring has been verified. As a response to a trip it is the fault being ignored at higher speed, and repeated resets without a repair end in rewound windings rather than new lugs. On every trip the sequence is the same: read the fault history, compare both ends with a suitable meter, open the branch the numbers indict, and release the machine only after the monitor stays quiet through the cycles that used to trip it.
Questions asked
The display says input phase loss, not motor lost. Is that the same problem?
No. Input phase loss sits on the supply side of the drive: one incoming phase is missing or low, so the rectifier sees an unbalanced supply. Work from the supply inward: check the branch fuses or breaker feeding the drive, the input terminals and the voltage balance at the drive's line side before touching the motor circuit. The motor, cable and output terminations can all be perfect on this fault.
Why does the drive trip on imbalance when the voltage readings look nearly even?
Because the drive's monitor watches current, and a winding turns a small voltage imbalance into a much larger current imbalance. NEMA MG-1's guidance puts current imbalance at roughly six to ten times the voltage imbalance, driven by the negative-sequence voltage. That is why phase-to-phase voltages within a volt or two of each other can still carry enough phase current difference to trip the protection.
What happens if I keep resetting the fault and running?
The motor keeps turning on the phases that still work, so nothing dramatic happens at first, which is exactly why the fault gets ignored. The energized winding paths carry more than their share of the load current, slip rises, the motor heats beyond its design, and the insulation ages quickly. A phase left open long enough ends as a rewinding job, not a terminal repair.
Where does the imbalance trip setting live in the drive parameters?
It lives in the motor-protection parameter group of the drive series you have, alongside the phase-loss monitor and its enable setting. Parameter numbers and factory thresholds are specific to each model and firmware revision, so read the parameter table in your drive's own manual rather than borrowing a number from another series. One manufacturer's parameter number is never another's.
