Current IntelPower LibraryShop main store

Comparison

Feeding a machine with a stock VFD from single phase

Variable frequency drives Published 9 min read By Current Intel engineering team

Short answer

A stock three-phase-input VFD takes single phase only if its manual rates it at your voltage. Otherwise keep the drive and feed it from a rotary phase converter or a fixed-frequency drive ahead of it, or replace it with a single-phase-input drive wired to the control's run and speed signals. A 5 hp load on 230 V single phase draws roughly 20 to 29 A, so size the drive and the branch from input current.

On this page
  1. Can you feed single phase into the stock VFD and get three phase out?
  2. What are the three ways to run the machine on single phase?
  3. How much input current does a 5 hp drive draw on single phase?
  4. Will the machine still control the spindle speed automatically?
  5. Can you feed the stock VFD from the output of another VFD?
  6. What has to be rewired when the stock drive is replaced?
  7. What wire and breaker does the single phase branch circuit need?
  8. Which route is right for your machine?
  9. Questions asked

Do not move the supply wires onto the stock drive's three-phase input and expect three phase on the motor side: unless the manual rates that exact model for single-phase input at your voltage, the drive is built around three lines sharing the current. Three routes do the job. Keep the stock drive and feed it from a rotary phase converter, keep it and feed it from a fixed-frequency drive installed ahead of it, or replace it with a single-phase-input drive wired to the control's run and speed signals. On a 230 V single-phase supply a 5 hp load draws roughly 20 to 29 A depending on input power factor, so size the drive, the breaker and the conductors from single-phase input current, never from motor horsepower.

Can you feed single phase into the stock VFD and get three phase out? #

Only if the drive's own documentation gives a single-phase input rating for that model at your voltage; a drive's three-phase horsepower rating does not carry over to single-phase input without that second rating in print. A drive is three power stages in series: a rectifier bridge converts the incoming AC to DC, a capacitor bank holds that DC on the bus, and an inverter chops it into a PWM three-phase output.

On three-phase input the bridge draws in six overlapping pulses per cycle and the bus capacitors recharge at six times line frequency. Feed the same power through two wires and, at equal voltage and power factor, the line current rises by the square root of three, about 1.73 times, while the capacitors absorb a far larger ripple current recharging at twice line frequency. That is why a frame rated for three-phase input carries a smaller single-phase rating, and why the manual's single-phase input current, not its three-phase figure, is the number you design around. The derating and the terminal landing for single-phase input are covered in sizing a VFD for a three-phase motor on single-phase input.

What are the three ways to run the machine on single phase? #

Three routes reach the same spindle: a rotary phase converter ahead of the stock drive, a fixed-frequency drive ahead of it, or a single-phase-input drive in its place, and they differ mainly in what gets rewired and what can go wrong.

Route What feeds the spindle drive Automatic speed control Machine rework Main watch-out
Rotary phase converter Generated three phase at line voltage Unchanged: control and stock drive work as built Lowest: one new supply circuit Converter sizing and phase balance at the drive terminals
Fixed-frequency drive ahead of the stock drive PWM three phase held at the supply frequency Unchanged Low wiring change, but two drives in series The stock rectifier sees PWM edges; both makers must allow it
Single-phase-input drive replacing the stock drive Three phase direct from the new drive Survives only if run, direction and speed reference are re-wired Highest: cabinet rewiring plus full parameter setup Input-current sizing and signal mapping

The converter route has one advantage neither drive route offers: within its rating it also feeds other three-phase loads in the shop. The replacement route is the only one that leaves the machine self-contained on a single-phase branch, and the only one that touches the machine's control wiring.

How much input current does a 5 hp drive draw on single phase? #

The number that sizes the drive, the breaker and the conductors is single-phase input current at full load, and for a 5 hp load it falls between two bookends set by the drive's input power factor. Hypothetical worked example, every input stated:

  • Supply: 230 V single phase, 60 Hz
  • Shaft output: 5 hp, which is 5 × 745.7 W ≈ 3728 W
  • Combined motor and drive efficiency: assumed 0.85
  • Input power: P_in = 3728 W ÷ 0.85 ≈ 4386 W
  • Single-phase input current: I = P_in ÷ (V × PF)
  • Rectifier without a choke, PF assumed 0.65: 4386 ÷ (230 × 0.65) = 4386 ÷ 149.5 ≈ 29.3 A
  • With a DC choke or power-factor stage, PF assumed 0.95: 4386 ÷ (230 × 0.95) = 4386 ÷ 218.5 ≈ 20.1 A

The efficiency and power factor are example assumptions, not nameplate data; the drive manual's single-phase input current replaces them and becomes the load the branch circuit sees. How much a choke or an active front end raises that power factor is the subject of true power factor of a single-phase input VFD and how to raise it.

Will the machine still control the spindle speed automatically? #

Yes on both routes that keep the stock drive, because the control's enable, direction and speed-reference wires stay exactly where the builder put them; only the replacement route puts automatic speed control at risk, and only until those signals land on the new drive.

The control already commands the spindle electrically through the stock drive, so anything that changes only the line side of that drive is invisible to it. On the replacement route the new drive must take its command from terminals rather than its keypad, and each signal needs a mapped terminal: enable or run, forward and reverse, the analog speed reference with its type and range, and a ready or fault contact back to the control if it expects one.

Can you feed the stock VFD from the output of another VFD? #

On paper yes, in practice only with the upstream drive held at one fixed frequency, rated above the stock drive's three-phase input current, and cleared by both drive manufacturers, because the stock drive's rectifier would then be rectifying a PWM waveform instead of a sine wave.

A rectifier fed from another inverter sees the upstream drive's switching edges on every transition, which adds heating and insulation stress to the downstream input stage and loads the upstream output transistors and any output filter. Hold the upstream drive at the supply frequency and never vary it, verify its continuous output current exceeds the stock drive's three-phase input current with margin, and get confirmation from both drive makers that the series arrangement is permitted; a sine-wave output filter on the upstream drive removes most of the ambiguity. Note the limit: this works, if at all, for feeding one drive's rectifier. Why one VFD cannot serve as a phase converter for an entire machine is covered in why a VFD cannot power a whole machine as a phase converter.

What has to be rewired when the stock drive is replaced? #

The replacement route moves the work into the cabinet: you document the stock drive's signals, land the supply on the terminals the new manual names, and parameterize the new drive from the motor nameplate, all with the machine locked out.

  1. Shut the branch down, lock it out and test for absence of voltage before opening the cabinet; NFPA 70E, 2024 edition, covers the electrical safe-work practices behind that step, and your site's procedure with the authority having jurisdiction decides the details.
  2. Photograph and label every terminal on the stock drive, power and control, and trace each wire to the machine schematic before disconnecting anything.
  3. Write down the signals the control sends: enable or run, forward and reverse, the analog speed reference's type and range, and any ready or fault contact the control expects back.
  4. Land the single-phase supply on the input terminals the new drive's manual names and leave unused input terminals as the manual directs; the terminal landing for a single-phase feed is shown in wiring a VFD R S T input from a 240 V single-phase supply.
  5. Enter the motor nameplate voltage, current, frequency and base speed, set the command source to terminals, and set acceleration and deceleration ramps so the bus does not trip on overvoltage when the spindle stops.
  6. Scale the analog input so the control's full-scale command equals the maximum spindle speed you intend to allow.

The new drive's output voltage cannot exceed its input, the limitation explained in why a VFD on a 400 V supply cannot feed a 480 V motor, so connect the motor for the voltage you actually feed the drive.

What wire and breaker does the single phase branch circuit need? #

Size the branch conductors at not less than 125 percent of the drive's rated input current, and take the breaker or fuse from the type and maximum rating the drive manual lists, both under NFPA 70, the National Electrical Code, 2023 edition, Article 430.

Article 430.122(A) of that code requires conductors supplying power conversion equipment in an adjustable-speed drive system to have an ampacity of at least 125 percent of the equipment's rated input current: the drive's input current, not the motor's full-load amps. Run the earlier example: 29.3 A × 1.25 = 36.6 A minimum ampacity, which in the 75°C column of the code's conductor ampacity table (Table 310.16) rules out 10 AWG copper at 35 A and lands on 8 AWG copper at 50 A. With the choke, 20.1 A × 1.25 = 25.1 A, and 10 AWG copper covers it.

The breaker or fuse must match the type and maximum size the drive manual lists, because the drive's input protection and interrupting ratings are validated against exactly that device. Confirm conductor, termination and protection choices with the authority having jurisdiction and the drive documentation; the figures above are an estimate from the stated inputs. A bus-voltage dip toward the undervoltage trip point during acceleration means the supply impedance is too high, so recheck the branch length and the connections before blaming the drive.

Which route is right for your machine? #

Pick the rotary converter when other shop loads need three phase or the machine must stay untouched; pick the replacement drive when the machine should run self-contained on single phase; pick the upstream drive only when a suitable unit is on hand and both makers approve the pair.

  • The stock manual already lists a single-phase rating at your voltage: keep the drive, correct the supply wiring and the input parameters, and stop there.
  • Other shop equipment needs three phase, or the machine must not be touched: rotary converter, sized from the stock drive's rated input current plus the margin the converter maker's table requires.
  • The machine should run self-contained on the single-phase branch and you can document the control's signals: single-phase-input replacement drive, wired and parameterized as in the steps above.
  • A suitably rated drive is already on the shelf and both manufacturers approve the series arrangement: fixed-frequency drive ahead of the stock drive, with a sine filter if either maker asks for one.

Whatever you pick, the branch circuit follows the drive's stated input current, and the machine keeps its automatic spindle speed control as long as the control's signals land on whichever drive feeds the motor.

Questions asked

Does a rotary phase converter need to be bigger than the motor's horsepower?

Size it from the stock drive's rated input current rather than the motor's horsepower, then add the margin the converter maker's load table calls for. A converter running near its limit shows up as phase-voltage imbalance and bus undervoltage trips during acceleration. Measure all three line-to-line voltages at the drive terminals under load and stay inside the balance tolerance the converter maker publishes.

Is a static phase converter good enough to feed a VFD?

No. A static phase converter is a starting aid for one across-the-line motor; it leaves the generated leg unbalanced under load, and drive input bridges are not rated for that waveform. Feed the VFD from a rotary converter or an electronic three-phase supply instead, or take one of the single-phase-input routes described above.

Why does a single phase input drive need a DC choke or power factor correction?

Without one, the rectifier draws current in narrow peaks near the voltage crest instead of a broad sine, so the bus capacitors absorb far more ripple current and the input current lands at the high bookend in the worked example. A DC choke or an active power-factor stage widens those pulses and cuts the current toward the low bookend; the manual's single-phase input figure already reflects which design the drive has.

Will running on single phase lower the spindle's top speed?

No, as long as the motor is connected for the supply voltage. A drive's output voltage cannot exceed its input voltage, so a 230 V single-phase supply still drives a 230 V motor to full base frequency and top speed, and above base frequency speed rises while torque falls exactly as on three-phase input. A motor wound for a higher voltage is out of reach without a transformer or a different supply.

Keep reading

  • Selection guide

    Sizing a VFD for a 1 HP 220 V motor on single phase

    Size the drive by output current, not horsepower. This 1 HP, 220 V, three-phase motor draws 2.5 A at full load, so the drive needs at least 3.6 A of continuous output current; a 2 HP, 230 V single-phase-input frame rated about 7.5 A carries the single-phase rectifier's extra heat with room to spare. Stay on 230 V single-phase input rather than a 120 V voltage-doubler input.

    Variable frequency drives

  • Selection guide

    Sizing a VFD for a three-phase motor on single-phase input

    On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

    Variable frequency drives

  • Selection guide

    Line reactor sizing for servo drives on 240 V single phase

    Size a servo-drive line reactor from the drives' documented single-phase input currents, never from motor kilowatts. A 3 kW servo group on 240 V has a 12.5 A ideal floor but draws near 23 A in practice, so each machine branch takes a 25 A, 3 % reactor with the maker's documented two-coil single-phase connection.

    Variable frequency drives