Fixing servo drive phase loss fault on single phase input

Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

On a Milltronics MB20 with Yaskawa SGDB-10ADG axis drives, the phase loss fault on single-phase input clears only at each drive: feed the single-phase supply across L1(R) and L2(S), disconnect the incoming L3(T) conductor, and jumper L1(R) to L3(T) at the drive terminals. A jumper at the machine disconnect alone leaves the fault active whenever an axis is commanded, so test one axis before converting the rest.

On this page
  1. Why does the phase loss fault wait for an axis command?
  2. Why doesn't a jumper at the machine disconnect clear the fault?
  3. Which drive terminals get the single-phase supply on an SGDB-10ADG?
  4. What keeps the machine's 220 to 110 V control transformer fed?
  5. How do you convert one SGDB-10ADG drive, step by step?
  6. What do the drive terminal voltages look like before and after?
  7. How do you verify the fix before converting the remaining axes?
  8. Questions asked

A Milltronics MB20 from 2000 with Yaskawa SGDB-10ADG axis drives trips a phase loss fault on single-phase power the moment any axis is commanded, and the machine builder's disconnect-level jumper does not clear it. The fix lives at each drive: apply the single-phase supply across L1(R) and L2(S), disconnect the incoming L3(T) conductor and insulate it, then jumper L1(R) to L3(T) at that drive's terminals. In the field-verified test the supply read 230 V across L1(R) and L2(S), and the axes ran without the fault once the jumpers were in place. This article traces why the machine-level jumper fails, gives the per-drive conversion steps and the voltage arithmetic, and ends with the verification test one axis at a time.

Why does the phase loss fault wait for an axis command? #

The alarm comes from input phase sensing, which on these packs needs load current to see an imbalance: until an axis command draws real current through the rectifier, a dead or unjumpered L3(T) terminal hides, and the first motion command exposes it as the missing phase.

In the reported case the fault appeared as soon as any axis was commanded and never at idle, which is why an energized drive at rest cannot pass for a completed repair. Yaskawa's published fault documentation lists an input phase loss fault, coded PF, described as an open phase on the input or a large imbalance of input voltage; the troubleshooting manual for the GPD 506/P5 series adds a single-phase condition on the input and low input voltage at L1, L2 and L3 among the causes, with the corrective action to check the three-phase input. The SGDB-10ADG packs in this machine surface that same input condition as their phase loss fault.

Why doesn't a jumper at the machine disconnect clear the fault? #

The machine-level jumper energizes all three distribution legs, but it puts the same supply conductor on drive terminals L2(S) and L3(T), and the drive reads that collapsed pair as the large input imbalance its phase loss protection exists to catch.

The machine builder's instruction for this conversion — single-phase 220 V on machine lines L1 and L3, with L3 jumped to L2 — is correct at the machine level and was applied exactly as given, yet the fault persisted. Traced to the drive terminals, that pattern lands one machine conductor on both L2(S) and L3(T), so two of the three input terminals sit at one potential. The drive reports exactly the condition its documentation names. The correction has to appear at each drive's terminals, not only at the disconnect; the detection behaviour behind that alarm for a genuinely open phase is covered in our article on why a drive shows a missing phase fault on single phase supply.

Which drive terminals get the single-phase supply on an SGDB-10ADG? #

The input terminals are marked L1(R), L2(S) and L3(T), and the single-phase supply lands across L1(R) and L2(S) only; the former L3 conductor is disconnected and insulated, and a short jumper ties L1(R) to L3(T) at the drive.

For packs with input phase sensing, R and S carry the supply and T takes its reference from R, and the field sequence on this machine confirmed both halves of that pattern. With L3(T) merely disconnected the fault stayed, and adding the jumper from L1(R) to L3(T) was the step that cleared it. The jumper is therefore not optional on these packs, and the same correction repeats at every affected pack rather than anywhere upstream. A stock VFD usually absorbs single-phase conversion at the machine level, which is the difference described in our article on feeding a machine with a stock VFD from single phase.

What keeps the machine's 220 to 110 V control transformer fed? #

Leave the machine-level conversion as the builder specifies — supply on machine lines L1 and L3 with one of them jumped to L2 — because the machine's 220-to-110 V control transformer is fed across exactly that pair and loses its supply if the conversion happens only at the drive terminals.

Both requirements stand at once: the L1-to-L3 pair across the transformer primary at the disconnect, and the R-S-with-jumper pattern at each drive's terminals. Tracing the three conductors from the disconnect to each drive, rather than assuming the disconnect jumper reproduces itself downstream, is what separates the working conversion from the persistent fault. The same split between machine-level and equipment-level single phase comes up in our article on single phase control power for a three phase machine.

How do you convert one SGDB-10ADG drive, step by step? #

Work one drive at a time: de-energize and lock out the machine, verify the terminals are dead, move the supply connections at that one SGDB-10ADG, then test its axis before you copy the arrangement to the remaining drives.

NFPA 70E, 2024 edition, supplies the safe-work rule for this job: de-energize, apply lockout/tagout and verify absence of voltage before any conductor moves. NFPA 79, 2024 edition, is the electrical standard for industrial machinery that a modification like this must stay inside; confirm both with the authority having jurisdiction and the machine documentation.

  1. De-energize the machine, apply lockout/tagout at the disconnect, and verify absence of voltage across L1(R), L2(S) and L3(T) and from each terminal to ground.
  2. Identify the power terminals L1(R), L2(S) and L3(T) on the SGDB-10ADG from the terminal markings.
  3. Remove the incoming conductor from L3(T) and insulate its free end so it cannot contact the terminal block or ground.
  4. Restore power and command one axis from the machine's controller. In the field case the phase loss fault still appeared with L3(T) open, which proves the detector before anything else changes.
  5. De-energize, lock out and verify absence of voltage again, then add a short jumper from L1(R) to L3(T) at the drive.
  6. Re-energize and command the same axis; this is the step that ran clean in the verified test.
  7. Repeat the sequence at each remaining drive. The pattern is per drive, and a jumper at the disconnect cannot substitute for it.

What do the drive terminal voltages look like before and after? #

Set machine line L1 as the 0 V reference and line L3 as the 220 V supply, and the two arrangements separate cleanly: the disconnect jumper parks L2(S) and L3(T) together at 220 V, while the per-drive conversion parks L1(R) and L3(T) together at 0 V.

Under the disconnect-level arrangement, the jumper makes machine line L2 a copy of L3, so the drive terminals sit at L1(R) = 0 V, L2(S) = 220 V and L3(T) = 220 V, and subtracting potentials gives 220 − 0 = 220 V across L1(R)–L2(S), 220 − 0 = 220 V across L1(R)–L3(T) and 220 − 220 = 0 V across L2(S)–L3(T). That dead pair is the imbalance the detector reports. After the per-drive conversion, with the supply measured at 230 V, the terminals sit at L1(R) = 0 V, L2(S) = 230 V and L3(T) = 0 V through the jumper: 230 − 0 = 230 V across L1(R)–L2(S), 230 − 0 = 230 V across L2(S)–L3(T) and 0 − 0 = 0 V across L1(R)–L3(T).

Arrangement L1(R) L2(S) L3(T) L1(R)–L2(S) L1(R)–L3(T) L2(S)–L3(T) Field result
Disconnect jumper: 220 V on machine L1 and L3, L3 jumped to L2 0 V 220 V 220 V 220 V 220 V 0 V phase loss fault on axis command
L3(T) disconnected, no jumper yet 0 V 230 V floating 230 V — — fault remained
Per-drive conversion: jumper L1(R)–L3(T) added 0 V 230 V 0 V 230 V 0 V 230 V axes ran without the fault

Both patterns contain one tied pair, and the difference is which pair: these packs accept R tied to T with the supply on R and S, and they read the S-to-T tie fed from one conductor as an imbalance. Copy the first pattern.

How do you verify the fix before converting the remaining axes? #

An energized drive sitting idle proves nothing: the fault in this case appeared only when an axis was commanded, so the test that matters is a jog or move of one axis, made with the machine's controller or the JUSP handheld test unit.

Watch the fault indication through the whole move, not only at the command instant; the reported fault returned the moment motion was requested. Once one axis runs clean, confirm the control transformer and its secondary loads still operate, then repeat the conversion and the same one-axis test at each remaining pack. Because this fault only shows under motion, the checks pair naturally with the guide to troubleshooting a servo axis that faults mid move, which covers fault-hunting that only means something while the axis is moving.

The decision, case by case: a phase loss fault that appears only under axis command with the disconnect-level jumper in place calls for the per-drive conversion above, one pack at a time; a fault that survives a correct per-drive pattern means lock out again and trace the three conductors from the disconnect to that drive, because one of them is not the conductor you think it is.

Questions asked

Can the machine stay on a rotary phase converter instead of converting the drives?

Yes. This machine ran without the phase loss fault on a rotary converter, because the converter supplies a live third leg to the servo packs as well as to the rest of the machine. The terminal-level conversion removes the converter and its noise, but keeping the converter is a valid way to run production while you plan the rewiring.

Does single-phase input raise the current these servo drives draw?

Yes, roughly. The same power pushed through two conductors instead of three raises input current by about 1.73 times, the square root of three, at equal voltage and power factor. Size the supply conductors and the disconnect for that current and confirm the drive's input rating in its manual; the field case documented here does not include a single-phase derate for the SGDB-10ADG.

Does this terminal pattern apply to other servo drive models?

Treat it as verified for the SGDB-10ADG only. Other servo and drive families publish their own single-phase input rules, and the input phase loss fault Yaskawa documents for other series lists an open input phase or low input voltage at L1, L2 and L3 as causes. Read the manual for the specific pack before moving any conductor.

What should the control transformer secondary read after the conversion?

With the disconnect conversion left as the builder specifies, the 220-to-110 V transformer primary sits across machine lines L1 and L3 and sees the full single-phase supply, so the secondary should measure about 110 V. A low or dead secondary means the conversion at the disconnect has broken the L1-to-L3 pair that feeds the primary.

Keep reading

  • Comparison

    Running two separately controlled motors from one VFD

    Yes, a VFD can feed two motors, but only as one group that starts, stops and runs at the same frequency. If the two loads stay separately controlled, the answer is one drive per motor, each with a documented rating for the single-phase branch, and the shared design saves neither overload relays nor cost.

    Variable frequency drives

  • Troubleshooting

    VFD output phase loss fault: tracing the broken phase

    An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.

    Variable frequency drives

  • Explainer

    Why a 120 V VFD input needs a voltage doubler front end

    A 120 V single-phase supply can run a three-phase motor through a VFD only when the drive is listed for that input and rectifies through a voltage doubler, which lifts the bus from a 170 V peak to roughly the 339 V a 230 V-class inverter needs. The single-phase input also derates the drive, so the motor must be small and selected from the drive's single-phase rating table.

    Variable frequency drives