Comparison
Running two separately controlled motors from one VFD
Short answer
Yes, a VFD can feed two motors, but only as one group that starts, stops and runs at the same frequency. If the two loads stay separately controlled, the answer is one drive per motor, each with a documented rating for the single-phase branch, and the shared design saves neither overload relays nor cost.

On this page
A drive can feed two motors from one set of output terminals, but only as one load group: both motors start together, stop together and run at the same commanded frequency. Your case says separately controlled, and that word decides it. Buy one VFD per motor. The shared design does not even save you the protection hardware, because each motor behind a shared drive still needs its own overload relay rated for the PWM waveform on the drive's output leads. Add the enclosure space for those relays and the shared design costs about as much as two drives while giving you less control.
What one shared drive forces #
A VFD holds one output frequency for everything connected to its terminals. With two motors in parallel on one drive, the drive performs every start and every stop, and both shafts always turn at the same commanded speed. There is no supported way to run one motor at 40 Hz while the other sits at 65 Hz, and no supported way to start the second motor while the first is already running. Switching a motor onto or off a live drive output is documented by only a few drive makers, under strict conditions; the details of that arrangement are covered in running two motors on one VFD with output contactors. For motors that must stay separately controlled, that door is closed.
The shared drive also has to be set up for a parallel pair rather than for either motor: an open-loop volts-per-hertz mode, with the motor data entered as the sum of both motors, both currents and both powers added. Why the summed entry matters is explained in why a drive needs summed motor data for two motors in parallel.
The two designs compared #
| Requirement | One VFD for both motors | One VFD per motor |
|---|---|---|
| Independent start and stop | Not available; the drive starts and stops both | Supported by the architecture |
| Independent speed | Not available; one output frequency | Each drive runs its own speed reference |
| Motor overload protection | One overload relay per motor, rated for VFD output | Each drive protects its own motor through its configured motor data |
| Control mode | Open-loop volts-per-hertz with summed motor data | Any mode the drive supports, tuned to one motor |
| Fault handling | One fault stops both loads | A fault on one drive leaves the other motor running |
| Extra hardware beyond the drive | Two output-rated overload relays plus enclosure space | None beyond the second drive |
Overload protection is not saved by sharing #
The drive's electronic thermal protection watches the total output current, so on a shared drive it sees the sum of two motors and cannot tell when one of them is overloaded while the other runs normally. NFPA 70, the National Electrical Code, 2023 edition, Article 430 requires each motor to have overload protection, and that does not change because a drive is in front of the motors; confirm the application with your local authority having jurisdiction and the drive documentation. Each motor gets its own overload relay, and the relay must be rated for the PWM waveform on the drive output, not a standard thermal relay picked from a DOL-starter chart. A multi-motor branch circuit protector of the kind one automation vendor documents for exactly this duty gives individual motors both overload and short-circuit protection at the output of one drive, but the point stands: you buy and wire two protective devices per pair of motors. Why a single relay in front of two motors cannot protect either one is shown in why two motors behind one overload relay trip or burn.
Single-phase input sets the rating you buy #
Your building service is 120/240 V single phase, so the motors see three phase only because each drive rectifies the single phase and inverts it. That works only when the drive's own input specification permits it. Distinguish two kinds of drive:
- A drive designed for single-phase input at its rated output. Its published rating already accounts for the single-phase rectification, so no derating is added.
- A drive nominally rated for three-phase input whose documentation also permits single-phase input. Fewer rectifier paths feed the DC bus, ripple rises and available power falls, so the manufacturer publishes a single-phase derating or a reduced horsepower limit. Use only that documented figure; do not run such a drive on single phase at its three-phase rating.
Before either check, confirm which branch voltage actually lands at the drive location: the service offers both 120 V and 240 V, and a drive rated for one will not accept the other. IEC 61800-5-1 covers the safety requirements of complete drive systems including their rated supply conditions, so the input rating you select against is the one on the drive's nameplate and in its manual, verified for your branch. How that rating is applied when you size a drive this way is worked through in sizing a VFD for a three-phase motor on single-phase input.
Worked example: two 1 hp fans on a single-phase branch #
Illustrative inputs: two 230 V three-phase fan motors, 1 hp each, nameplate full-load current 3.2 A each, fed from the 240 V leg of the building's single-phase service. Motor efficiency 0.80 and drive efficiency 0.95 for the input estimate only.
Shared drive, if you insisted on one drive: the output must carry both motors, so the minimum continuous output current is
3.2 A + 3.2 A = 6.4 A
with volts-per-hertz control and summed motor data entered, plus two VFD-output-rated overload relays set to each motor's nameplate.
One drive per motor: each drive needs a continuous output rating of at least 3.2 A at 230 V three-phase output. The input current each drive draws from the branch is estimated as
P_in = 746 W / (0.80 × 0.95) ≈ 982 W
I_in = 982 W / 240 V ≈ 4.1 A
So each drive pulls roughly 4.1 A from the single-phase branch, well inside what small single-phase-rated drives in this class are documented for. These are estimates: check each drive's published single-phase input current against the branch circuit and breaker, and check the branch sizing against NFPA 70 Article 430 and your local amendments. The result is an estimate to be verified against the governing code and the equipment documentation, not a substitute for either.
Selection steps #
- Measure or confirm the branch voltage and phase at the drive location. Write it down; every rating you check next depends on it.
- Select two drives, each with a documented input rating for that exact single-phase voltage, and each with a continuous output current at least equal to its motor's nameplate full-load current. If a candidate is a three-phase-input drive with a permitted single-phase rating, size it from the published single-phase figure, never the three-phase one.
- Give each drive its own input breaker sized from the drive manual, and its own output leads sized for the motor current.
- De-energize the branch, lock it out and test for absence of voltage before opening any enclosure to make the terminations.
- Wire each motor to its own drive and configure each drive with its own motor's data.
- Run each motor through its full working sequence and confirm neither drive reports a DC-bus, input-supply, overload or output fault.
The decision for each case #
- The two loads stay separately controlled: one VFD per motor, each with a documented rating for the single-phase branch at its measured voltage. This is the design you should build.
- The two loads could become one group that always runs together: a single shared drive becomes legitimate, sized for the summed current, set to volts-per-hertz with summed motor data, with one VFD-output-rated overload relay per motor. Confirm the control change with the process owner before choosing it; do not accept it to save the cost of a second drive, because with the relays and enclosure it saves little.
- Either way, apply the manufacturer's published single-phase derating only to a drive whose nominal rating is for three-phase input; a drive rated for single-phase input is used at its rating.
Questions asked
Does the shared drive's built-in motor protection replace the individual overload relays?
No. The drive's electronic thermal model watches the total output current. If one motor overloads while the other runs normally, the summed current can stay inside the drive's limit and the drive never trips for the motor that is in trouble. Each motor still needs its own relay on its own leads.
Can output contactors let each motor start separately from a shared drive?
Only where the drive manufacturer documents switching motors on a live output, and most general-purpose drives do not support it. Connecting a stopped motor to an already-running output produces a high inrush the drive trips on, and the drive cannot ramp one motor independently anyway. Treat separately started motors as separately driven motors.
What control mode does a shared drive need?
An open-loop volts-per-hertz mode with the motor data entered as the sum of the two motors: both currents added and both powers added. A vector mode tuned to a single motor's data misreads the parallel pair, so use the summed-data procedure the drive manual gives for parallel motors.
Is the single-phase derating the same problem when two small drives replace one large drive?
Each drive is rated for its own single-phase input current, so you check each one against its own documentation rather than adding a group derating. Two drives each within their published single-phase rating need no extra margin between them, while one oversized drive is more likely to fall outside the single-phase ratings a manufacturer publishes.