High-resistance grounding does not lower arc flash severity

Electrical safety and codes Published 8 min read By Current Intel engineering team

Short answer

High-resistance grounding limits line-to-ground fault current, typically to about 5 or 10 A on a low-voltage system, and lowers the chance that a ground fault escalates into a multiphase arc. It puts no impedance in a line-to-line or three-phase fault path, so the calculated incident energy for those faults is worked exactly as on a solidly grounded system, and a lower probability of an event is not a lower severity.

On this page
  1. What the grounding resistor actually carries
  2. Where the resistor sits in a multiphase fault
  3. What the standards ask you to calculate
  4. Probability is not severity
  5. Working the numbers for a 480 V, 1000 kVA HRG bus
  6. When the first ground fault is standing
  7. What this means for your next study
  8. Questions asked

No — you run the line-to-line and three-phase numbers for a high-resistance grounded system exactly as you would for the same bus solidly grounded. The neutral grounding resistor limits line-to-ground fault current, typically to about 5 or 10 A on a low-voltage system, and that limit is what cuts the chance that a first ground fault escalates into a multiphase arc. But the resistor sits in the neutral, not in any phase-to-phase path, so once a multiphase arc is established, its current and its incident energy come from the source and circuit impedances alone.

Two different quantities are in play here: the probability that an arc flash event happens, and the severity of the one that does. High-resistance grounding improves the first and leaves the second untouched. The scheme is often presented as arc flash mitigation, and it is — but only on the probability side, because the incident energy calculation has no input where the grounding scheme could enter.

What the grounding resistor actually carries #

High-resistance grounding ties the system neutral — or a neutral point derived through a grounding transformer bank on a delta system — to earth through a resistance chosen to hold a line-to-ground fault to a small, controlled current. The purpose is continuity: with the fault current held that small, the first ground fault does not have to trip anything. The system keeps running and the fault raises an alarm, which is why process plants that cannot tolerate a trip favor the scheme.

The resistor value is not a free choice, though. It is sized to let through more current than the system's charging current requires — the capacitance of everything connected to the bus to ground — which is what caps how large that resistance can be. Why system charging current sets the maximum NGR resistance works through that sizing limit.

Medium-voltage systems use the same idea with far more let-through: low-resistance grounding there typically allows 400 to 600 A, because charging current grows with system voltage and cable length, and the earth-fault protection needs enough current to detect the fault dependably. The protection side of that medium-voltage arrangement is covered in earth fault protection for high-resistance grounded 11 kV systems.

Where the resistor sits in a multiphase fault #

Follow the fault loop. A line-to-line fault runs from the source, out one phase conductor, through the arc, back along a second phase conductor and into the source. A three-phase arc uses all three conductors the same way. The neutral — and the resistor at its end — is not in either loop, and no current from a line-to-line or three-phase fault has any return path through it. During a multiphase fault, the resistor carries nothing.

That leaves the current set by the impedances that are in the loop: the source, the transformer and the conductors between them — the same quantities you would add up for any solidly grounded system feeding the same bus. The two fault families are genuinely different circuits; comparison of line-to-ground and line-to-line fault current analysis on distribution cable works through that split fault by fault.

Fault you are analyzing What sets the current Does the neutral resistor enter?
Line-to-ground The resistor value, sized above the system charging current Yes — it limits exactly this fault
Line-to-line Source, transformer and conductor impedance No
Three-phase Source, transformer and conductor impedance No

The only current the resistor ever carries is ground-path current: the system's charging current in normal operation, and the designed fault current while a ground fault stands.

What the standards ask you to calculate #

NFPA 70E, 2024 edition, covers electrical safety-related work practices, and it requires an arc flash risk assessment for equipment that could be worked on while energized. The assessment is done either by incident energy analysis or by the standard's PPE category table method; the analysis route is the one that applies to a system like this, and its output sets the arc flash boundary and the PPE at each piece of equipment.

The incident energy numbers come from IEEE 1584-2018, the IEEE Guide for Performing Arc-Flash Hazard Calculations. The guide's model is built from three-phase arc tests, and its equations take the bolted three-phase fault current, the arcing time, the system voltage, the conductor gap, the enclosure size and the working distance. The method of system grounding is not an input, so the model produces the same answer for a high-resistance grounded bus as for a solidly grounded one. That bolted three-phase figure is what feeds the arcing-current model — the relationship between the two currents is covered in bus fault current vs arcing current in an arc flash study.

You may still meet older advice to classify the system as solidly grounded or ungrounded before calculating. That advice came from earlier editions of the guide, and the current model has no slot for it. Confirm the exact requirements with your authority having jurisdiction and the equipment documentation — editions and local amendments differ.

Probability is not severity #

A large share of multiphase arcs begin as a single line-to-ground fault that escalates. Holding the ground current at a level a power arc cannot sustain removes that escalation path, so the real effect of high-resistance grounding is on the odds: fewer first faults escalating, alarms instead of trips, more continuity. That is a reduction in how often an arc flash should happen — not in what the event delivers when it does.

The risk assessment framework treats likelihood and consequence as separate factors, precisely so a scheme that lowers one is not booked against the other. Whatever incident energy the three-phase case calculates at that bus, that is the number the boundary and the PPE come from. Where severity genuinely has to come down, the levers are clearing time and current limitation: maintenance-mode protection settings that cut the arcing time, or a current-limiting fuse whose total clearing curve sits under the breaker curve — when a Class L fuse actually cuts arc flash energy walks through when that pays off.

Working the numbers for a 480 V, 1000 kVA HRG bus #

One worked case shows how cleanly the two calculations separate.

Inputs

  • System: 480 V, three-phase, 60 Hz, high-resistance grounded — the typical low-voltage level for this scheme.
  • Neutral grounding resistor: selected to hold line-to-ground fault current at 5 A, the typical low-voltage let-through.
  • Transformer: 1000 kVA, 480 V secondary, 5.75% impedance — example nameplate values for this case.
  • Source: stiff enough on the primary that the transformer impedance dominates — a stated assumption of the example.

The rules in words

The resistor follows Ohm's law across the line-to-neutral voltage: divide the line-to-neutral voltage by the ground-fault current. The bolted three-phase current at the secondary follows from the transformer alone, by the standard percent-impedance method from the nameplate: take the transformer's base current — its rating in VA divided by 1.732 times the secondary voltage — and divide by its impedance expressed as a decimal.

The arithmetic

  • Line-to-neutral voltage: 480 V ÷ 1.732 = 277 V.
  • Resistor: 277 V ÷ 5 A = 55.4 Ω.
  • Base current: 1000 kVA × 1000 ÷ (1.732 × 480 V) = 1,000,000 VA ÷ 831.4 V ≈ 1202.8 A.
  • Bolted three-phase current: 1202.8 A ÷ 0.0575 = 20,918 A, about 20.9 kA.

The result

The resistor comes out at 55.4 Ω and carries the designed fault current on the first ground fault — and only the charging current while the system is healthy. The bolted three-phase current at the bus is about 20.9 kA, the same number this transformer delivers to an identical solidly grounded bus, because the resistor enters no line of that arithmetic.

The decision

Feed the bolted three-phase value into the study, exactly as you would for a solidly grounded system; feed the resistor's let-through into the ground-fault protection settings. The error to avoid is letting the small ground number stand in for the multiphase one. If the study puts incident energy above the arc rating your crews work in, severity reduction has to come from clearing time or current limitation — not from the grounding scheme.

This is an estimate from the example inputs: your nameplate impedance, the real source strength and the cable runs all move it, so run your own data before it goes into a study. The full low-side method, including source and conductor impedance, is laid out in calculating low-side fault current with source impedance.

When the first ground fault is standing #

The alarm is the scheme's whole arc-flash benefit, and it only works if the fault it reports gets found. While one ground fault stands, the system is one phase away from the multiphase fault this article has been calculating: a second fault on a different phase completes that loop, and every severity number applies at full value. A standing fault is a work order, not a watch item.

Start with the indication itself, because an indication circuit that has quietly failed looks identical to a healthy system: test the lamps, the relay and the sensing before you trust a green panel. Where the relay itself has died, a ground fault relay replacement for high-resistance grounding brings the alarm function back. Then trace and clear the fault — the practical steps for a system like this are in locating a ground fault on a resistance-grounded 480 V system.

One safety note: before you open any panel, motor junction box or the resistor enclosure to trace or clear that fault, de-energize and verify absence of voltage with a tested instrument. Tracing on a live system is energized work under NFPA 70E, 2024 edition, and it takes the same risk assessment, PPE and boundaries as any other energized task.

What this means for your next study #

Model the bus with the same source, transformer and conductor impedances you would use solidly grounded — the grounding scheme changes none of them. Take the probability credit where it belongs: fewer escalations, alarms instead of trips, more continuity. And do not let the alarm stand, because the severity the study reports is the severity you get on the day a second fault lands. The resistor earns its keep on the faults it prevents, not on the energy in the ones it does not.

Questions asked

Why do older references say to model an HRG system as ungrounded?

Earlier editions of the IEEE 1584 calculation guide carried grounding classification coefficients inside their equations, and they grouped high-resistance grounded systems with ungrounded ones, so an analyst had to pick a class before calculating. The 2018 edition removed the grounding term from the model, so the classification no longer changes the result and either label you meet in older literature is out of date.

What happens to the other two phases while a ground fault is standing?

The faulted phase sits at ground potential and the two healthy phases rise to roughly line-to-line voltage above ground for as long as the fault persists. That is why insulation, surge protection and anything connected line-to-ground on a resistance-grounded system must be selected for that elevated voltage, and it is a second reason the standing fault belongs on the work order, not the watch list.

Can HRG be taken as credit when choosing arc-rated PPE?

No. PPE follows the incident energy the study calculates at the equipment, and the multiphase calculation runs on the same inputs whether the neutral is solidly grounded or tied to ground through a resistor. High-resistance grounding reduces how often to expect an arc flash event; it does not reduce the energy in the event itself, so the arc rating required at that equipment is unchanged.

Is the resistor sized to a standard ampere value?

There is no standard ampere value. The constraint that matters is the system's charging current: the resistor must let through more current than the system capacitance to ground demands, because below that level the system behaves close to ungrounded and transient overvoltages return. Methods exist for measuring charging current without staging a fault, and the resistor is sized from that measurement rather than from a rule of thumb.

Keep reading

  • Explainer

    Why high resistance grounding can raise calculated incident energy

    High resistance grounding caps a line-to-ground fault at a few amperes, so that arc cannot sustain — a genuine risk reduction. IEEE 1584-2018 still scores a three-phase arc, and its grounded-system correction is withheld from HRG buses, so the calculated incident energy can come out slightly higher than for the same bus solidly grounded. Use the calculated value for the label and PPE; no edition of the standards grants formal credit for HRG.

    Electrical safety and codes

  • Explainer

    Why single line to ground fault current does not change arc flash

    Changing transformer or generator grounding from low-resistance to solid moves the single line to ground fault current sharply and leaves three-phase bolted fault current untouched. Because IEEE 1584 incident energy is calculated from the three-phase current and the protective device's clearing time, arc flash results do not change; only ground-fault relay settings and coordination need rework.

    Electrical safety and codes

  • Explainer

    Ground fault neutralizer arc flash mitigation limits on MV systems

    A ground fault neutralizer with residual current compensation limits only the phase-to-ground fault path. It can reduce the chance that a ground fault initiates or grows into a multiphase arc, but the calculated incident energy still comes from the credible three-phase arcing fault under IEEE 1584-2018 and NFPA 70E, 2024 edition. On a typical medium-voltage substation bus the multiphase fault current dwarfs the limited ground-fault current, so the label barely moves.