Model busduct risers as impedances between connection buses
Short answer
Model every plug-in tap on a busduct riser as its own bus and connect adjacent buses with impedance for the duct between them. A riser drawn as one ideal bus drops the series impedance, overstates downstream fault current, and is not reliably conservative for incident energy. Work from the tap schedule, the manufacturer impedance table and the software's busduct library entry, then check that fault current falls with distance.
On this page
Draw every plug-in tap on a busduct riser as its own bus, and connect neighboring buses with the impedance of the duct between them. A 4000 A, 480 V riser serving several floors is a chain of small series impedances, not one electrical point, and every section between taps lowers the fault current available at the taps beyond it. Short-circuit software uses the word bus for a connection point, never for a length of copper, so the duct belongs in the model as a branch impedance, exactly the way a cable run does. Drawn as one ideal bus, the riser reports full source current at every floor: overstated for breaker duty checks and not reliably conservative for arc flash. The steps below set up the model, work a three-tap example with the arithmetic shown, and end with what to release for each study type.
Why one ideal bus gets the riser wrong #
A bus in short-circuit software marks where branches meet; it carries no length and no impedance of its own. The duct between two connection points is a branch with series resistance and reactance, and the industry treats it that way: the point-to-point short-circuit worksheets that fuse and breaker publishers provide include a table of busway constants beside the table of conductor constants. SKM's knowledge base documents the software version of the same idea: take a cable-type branch on the one-line, change its symbol to a bus duct, and assign a busway library component to it. Drop the duct from the model and every tap inherits only the impedance up to the riser origin, a quantity you can reconstruct from the available fault current there; deriving source impedance from prospective short-circuit current works that arithmetic. Leave the sections out and the upper floors read high.
Map the connection points and section lengths #
Work from the riser one-line, the floor tap schedule and field records before opening the software. Record the riser route, every plug-in location, the order of the floors, and the duct length between each pair of neighboring connection points. Split a section wherever the electrical path changes: a plug-in tap, a feed back to the switchboard, a splice, a point the study must report. Do not create one bus per floor label when the tap schedule says otherwise; a floor with two plugs gets two buses, and a floor with none adds duct length but no bus. How taps, joint hardware and section lengths distribute along a real run follows the installation itself; the guide to industrial plug-in busway sizing, selection and installation shows the hardware those lengths come from.
Where drawings leave tap positions unclear, confirm the dimensions during an outage: de-energize the riser, lock it out, and test for absence of voltage at the plug openings before any cover comes off. Mark every estimated length in the preliminary model so the released study replaces it with confirmed dimensions. Splitting a run at points where no physical tap exists, purely to sharpen a study result, is a separate exercise covered by segmenting a long busway for arc flash studies.
Assign an impedance to each duct section #
Use the impedance table the duct's manufacturer publishes for the installed configuration: ampere rating, conductor material and construction, since a totally enclosed, non-ventilated sandwich design and a ventilated one do not share numbers. Most short-circuit programs carry busduct entries in their cable libraries, SKM among them; select the entry that matches the installed duct and compare its resistance and reactance against the manufacturer table before trusting either. Check three things on the entry: the units it expects (for example ohms per 100 ft), the frequency basis (60 Hz in a North American plant), and whether it wants a value per length or a figure for the whole section. Enter each section's own length once. Never borrow an impedance from a different rating because the numbers look close, and record in the study notes which source supplied each value. If the library entry and the manufacturer table disagree, resolve the configuration mismatch before running a case.
Build and run the model #
Connect the downstream equipment at its tap the way an MCC bucket is modeled for an arc flash study; keeping each bucket's connection bus explicit is what gives the feeder lengths meaning. Then build the riser:
- Place a bus at the riser origin and at every plug-in tap, splice and report point in the study scope.
- Connect neighboring buses with busduct branches, each carrying the impedance for the installed duct and its own documented length.
- Land each plug-in breaker on the bus where it physically taps the riser, with trip data from the breaker's documentation for that trip unit.
- Model downstream loads and motor contributions at their own buses, not at the riser origin.
- Run the short-circuit calculation and trace the one-line from the source through every section to each tap.
- Record the bolted current at each tap bus and confirm it falls as distance from the origin grows.
- Run the arc flash calculation on that verified model and keep the short-circuit results that feed it.
Worked example: three taps on one riser #
Every input below is illustrative; the method and arithmetic are what transfer to your study. Assume a three-phase, 60 Hz, 480 V riser rated 4000 A with 45.0 kA symmetrical available at the origin, a tap every 30 ft on floors one through three, no motor contribution, and example duct data of 0.0020 Ω resistance and 0.0080 Ω reactance per 100 ft standing in for the manufacturer's table. The ampere rating sets the duct's physical construction; the fault math uses the impedance.
Source impedance at the origin, from the three-phase relation I = V/(√3·Z) with √3 ≈ 1.732:
Z_source = 480 V / (1.732 × 45,000 A) = 0.00616 Ω
Each 30 ft section:
Z_section = (30 ft / 100 ft) × (0.0020 + j0.0080) Ω = 0.0006 + j0.0024 Ω
At each tap, sum the series impedances, take the magnitude, and divide:
Floor 1: |Z| = √(0.00676² + 0.0024²) Ω = 0.007173 Ω, so I = 480 V / (1.732 × 0.007173 Ω) = 38.6 kA
Floor 2: |Z| = √(0.00736² + 0.0048²) Ω = 0.008787 Ω, so I = 480 V / (1.732 × 0.008787 Ω) = 31.5 kA
Floor 3: |Z| = √(0.00796² + 0.0072²) Ω = 0.010733 Ω, so I = 480 V / (1.732 × 0.010733 Ω) = 25.8 kA
| Fault point | Duct impedance added | Total impedance | Bolted fault current |
|---|---|---|---|
| Riser origin | none | 0.00616 Ω | 45.0 kA |
| Floor 1 tap | 0.0006 + j0.0024 Ω | 0.007173 Ω | 38.6 kA |
| Floor 2 tap | 0.0006 + j0.0024 Ω | 0.008787 Ω | 31.5 kA |
| Floor 3 tap | 0.0006 + j0.0024 Ω | 0.010733 Ω | 25.8 kA |
Drawn as one ideal bus, all three taps report the 45.0 kA origin figure: 74% high at the top tap (45.0 / 25.8 = 1.74). The program's ANSI/IEEE short-circuit methods layer asymmetry, X/R and arcing-current factors on top of these bolted values, and the released numbers are estimates to be checked against the governing code and the equipment documentation.
Read the results before you trust them #
With the source held fixed, every added section lowers the bolted current at the buses beyond it. A value that rises along the run, or identical numbers at every tap despite modeled sections, signals a topology or input error, not a property of the riser. Look for a missing or bypassed section, a breaker landed on the wrong bus, a length entered twice, ohms per 100 ft entered where the program expects a whole-section figure, or a library entry for a duct other than the one installed. Then check the arc flash side: the program computes an arcing current and a lower second case from each bolted value, and why arc flash software reports 85% of the arcing current explains that pair. Both cases belong in the report for the buses you intend to label.
What to release for each study type #
Short-circuit duty screening: a one-bus riser is acceptable as a screening number because it hands every tap the highest bolted current the origin can deliver. Mark it as a duty-screening figure on the one-line and publish no incident energy from it.
Arc flash and field labels: model the sections, always. A bolted current that reads high can move a tap's operating point onto a faster part of its trip curve and understate the incident energy, so the one-bus model errs in a direction nobody wants. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers safe work practices around energized electrical equipment and calls for an incident energy analysis as part of the arc flash risk assessment; confirm the study and labeling requirements with your authority having jurisdiction and the equipment documentation, and take label values only from the sectioned model.
Final released study: sectioned model, confirmed lengths, impedance values reconciled between the manufacturer table and the library entry, sources documented, and the falling-current check passed at every tap.
Preliminary work: section the model even for the first pass. A handful of extra buses and branches removes the only part of the preliminary answer that can be wrong in either direction.
Questions asked
Does the bus in the software stand for a physical piece of busduct?
No. A bus in short-circuit software is a connection point, and the duct between two of them is a branch with resistance and reactance, the same as a cable run. SKM's knowledge base shows the technique of picking a cable-type branch, changing its symbol to a bus duct and assigning a busway library component, and most other programs offer an equivalent component. The symbol carries no impedance; the branch data does.
What if the manufacturer does not publish impedance for the installed duct?
Request the data in writing for the rating, conductor material and construction you actually installed, and keep the reply in the study record. Impedance changes with conductor spacing and enclosure construction, so a table for a different rating or a ventilated design is not a substitute. If the software library lists a close match, show that comparison in the study notes and switch to the manufacturer's figure once it arrives.
What length belongs to a section that passes floors with no plug-ins?
The full physical length between the two adjacent connection points that bound the section, including the riser distance through the unserved floors. A floor with no tap adds conductor, not a bus, so its length belongs in the section impedance. Only a real connection, such as a plug-in tap, a splice back to the source or a point the study must report, justifies splitting the branch into two.
Where does motor contribution enter a multi-floor riser model?
At the bus where each motor or motor cluster connects, not at the riser origin. Floor loads feed current back into a fault at their own tap, which partly offsets the attenuation the duct sections add downstream of them. Enter each contribution at its connection bus and let the program combine them, which is one more reason every tap needs its own bus.