Modeling inverter fault current in SKM: generator or VFD source

Protection: breakers, fuses and SCCR Published 6 min read By Current Intel engineering team

Short answer

A power-electronic inverter contributes a bounded fault current, so the model must reproduce the documented magnitude and its short window, not the kW rating. PTW version 6.5 has no AC inverter-output component, so the answer is a calibrated proxy: a synchronous generator near 0.55 reactance on its own base with a decrement to zero after the window, or a drive-output model with its current limit at the documented value.

On this page
  1. What does an inverter contribute to a fault?
  2. Why can't the model be built from the kW rating?
  3. Which PTW component represents the inverter's AC output?
  4. How do you calibrate a synchronous generator proxy?
  5. When is a drive-output model the better proxy?
  6. How do you verify the proxy in the study results?
  7. Which model serves each study decision?
  8. Questions asked

The inverter is a bounded source: it drives its documented fault current into a bolted fault for 10 cycles and then stops, and the model has to reproduce exactly that. The PTW release described here has no AC inverter-output component for a short-circuit study, so you build a proxy and calibrate it against two numbers, the magnitude and the window. The two candidates are a synchronous generator tuned to hold that current and decay to zero when the window closes, and a drive-output model with its current limit at the same value. Below is the calibration arithmetic, the verification run, and the decision for interrupting duty, coordination and arc flash.

What does an inverter contribute to a fault? #

The inverter behaves as a current-limited source: it drives its documented fault current, 495 A RMS in this case, into the fault for 10 cycles (0.166 s) and then stops, so the model must reproduce a bounded magnitude and a hard time limit. Power electronics set that current by design: the converter's switches and control loops clamp it near the limit instead of letting it decay the way a spinning machine's trapped flux does. For PV and fuel-cell grid-tied inverters the figure comes from the short-circuit abnormal test that UL 1741 certification requires, so it is a tested value; its current basis (symmetrical or asymmetrical RMS, which phase) is stated in the inverter's documentation, and the certification paperwork names the standard edition. The model must hold a near-constant magnitude through the window, then deliver nothing.

Why can't the model be built from the kW rating? #

Because the rating describes normal power conversion, not fault response: converting kW to current needs power-factor and connection assumptions the fault study never uses, while the short-circuit test figure already is the current you must model. A worked example shows how far apart the numbers sit. Illustrative inputs: three-phase, 480 V, unity power factor. Rated current: I = P ÷ (√3 × V × pf) = 225,000 W ÷ (1.732 × 480 V × 1.0) ≈ 270.6 A. The documented fault current is 495 A ÷ 270.6 A ≈ 1.8 times rated. A synchronous machine pushes several times rated current on its first cycle before the decrement pulls it down, so a generator proxy left on default machine data overshoots the inverter badly. The kW rating is context; the tested current is the model input.

Which PTW component represents the inverter's AC output? #

None in the release described: version 6.5 carries an "Inverter" component that solves DC Load Flow only, and a dedicated inverter-output component is slated for version 7.0, so a fault study today needs a calibrated proxy. The two stand-ins on the table are a synchronous generator, the common workaround for this gap, and a drive-output model, proposed as the closer electrical match because both it and the inverter are power-electronic, current-limited sources. Neither is an inverter model by nature: a proxy earns its place by reproducing the documented magnitude and the documented window in a verification run, not by its label.

How do you calibrate a synchronous generator proxy? #

Set the machine's first-cycle (subtransient) reactance near 0.55 on its own base so the model holds the documented current, then shape the decrement so the contribution is gone at the end of the window. The reactance falls straight out of the current you want. Continuing the same illustrative base, rate the proxy machine at 225 kVA, 480 V, so its rated current matches the 270.6 A above. The reactance that holds the documented current is X = V ÷ (√3 × I) = 480 V ÷ (1.732 × 495 A) = 0.560 Ω. The machine's base impedance is Z = V² ÷ S = (480 V)² ÷ 225,000 VA = 1.024 Ω, so X = 0.560 Ω ÷ 1.024 Ω = 0.547: enter 0.55. Check: 270.6 A ÷ 0.55 = 492 A, within 1 percent of the target.

Enter that reactance on the machine's own base; mixing bases is the classic way a generator model reports the wrong fault current, a failure covered in why mixed bases give the wrong generator fault current. For the time behavior, a walkthrough of generator decrement curve setup shows where the curve is defined; drive it to zero when the window closes instead of a machine-like multi-second decay.

When is a drive-output model the better proxy? #

When the drive component exposes an output current limit: a drive model clamps its output current the same way the inverter's controls do, so setting that limit to the documented fault current reproduces the bounded behavior without inventing machine impedances. Verify one behavior in the study run before trusting it: the component must act as a current-limited source in the short-circuit study, not as an impedance whose contribution scales with the fault level. If it clamps at the value you entered, it is the more natural stand-in. If it does not clamp, or the installed release offers no field that limits fault output, go back to the calibrated generator.

How do you verify the proxy in the study results? #

Run the fault study and read the proxy's own contribution at the point of connection, not the bus total, then check two numbers: magnitude against the documented current, duration against 10 cycles at 60 Hz, which is 10 ÷ 60 = 0.1667 s. That matches the documented 0.166 s. The bus total also carries the utility source and every motor on the section, so it always reads higher and proves nothing about the proxy; compare like with like, meaning the same fault type, the same bus and the same time point. A zero reading means the proxy is out of service or on the wrong bus before anything deeper is wrong. How a decaying contribution then rides through an incident-energy calculation is covered in handling generator fault-current decay in arc-flash studies.

Which model serves each study decision? #

For equipment duty the proxy runs at full documented magnitude; for arc flash it contributes only while the protective device clears inside the contribution window; and for anything slower the inverter is already off. The decisions:

  • Interrupting duty at the inverter bus (breaker, fuse, switchgear rating): count the proxy at full documented magnitude, added to the utility and motor contributions, because the window covers every fast device.
  • Coordination and time-delayed elements: the inverter is gone once the window closes, so model the decay; a sustained proxy contribution distorts the coordination study.
  • Arc flash incident energy: credit the proxy only when clearing happens at or under 0.166 s; for slower clearing it contributes nothing, and a proxy that keeps feeding the fault inflates the incident energy.

Those incident-energy results end up on equipment labels, and the work practices at that equipment follow NFPA 70E, 2024 edition, which covers electrical safety-related work practices, so confirm the study's assumptions with your authority having jurisdiction before they reach a label.

Questions asked

Is the documented fault current symmetrical or asymmetrical?

The figure alone doesn't say; its basis is stated in the inverter's documentation. Short-circuit studies separate symmetrical from asymmetrical RMS, and a symmetrical study value set against an asymmetrical test figure differs by the DC offset alone, so that mismatch is not a modeling error. Compare symmetrical with symmetrical, or convert both to one basis, before you judge the proxy.

How do you model several inverters on one bus?

Give each unit its own calibrated proxy at its own connection point instead of scaling one machine up. Identical units at the same voltage contribute in phase, so within the window the bus sees their documented currents added arithmetically: two identical units feed twice one unit's current, and every proxy still decays to zero at the same window's end.

Does the proxy stay in the model for load-flow or harmonics studies?

No. The proxy is a short-circuit stand-in only. For AC load flow, enter the inverter's real and reactive power injection as generation, and for the DC side use the Inverter component PTW already provides for DC analysis. The calibrated generator or drive model carries an artificial reactance or current limit that means nothing outside the fault study, so remove it before running other study types.

Keep reading

  • Explainer

    Which starting current to use for motor short-circuit contribution

    For an IEC 60909 short-circuit study of a motor fed through a wye-delta starter, estimate the machine's reactance from its full-voltage starting current — the 7×In locked-rotor ratio — never the reduced wye current. The starter changes how the machine starts, not what it feeds a fault. Enter the 50 m and 5 m cables as separate segments and give each fault case only the runs between contributor and fault.

    Protection: breakers, fuses and SCCR

  • Troubleshooting

    Why a generator decrement curve misses the protection curve

    The IEC 61363 hand and software results already agree; the comprehensive 11.3 kA is the initial symmetrical current of the same fault. The decrement curve misses the protection because the current falls to 2.5 kA at the 0.632 s high-set delay, below its 4.5 kA pickup. The model's sustained value is 1.6 kA, not the data sheet's 5.6 kA, which needs a field-forcing ratio of 10.4.

    Protection: breakers, fuses and SCCR

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR