Troubleshooting
Phase converter voltage sag causes machine startup faults
Short answer
Relocating drive alarms at power-up are the signature of converter voltage sag: measure all three line-to-line voltages at the machine disconnect during a failed start and a clean one, hold start-time unbalance within the 3% ANSI C84.1 utility limit, and if the recorded dip matches the alarms, work the single-phase feed, connections and converter sizing instead of replacing axis drives.

On this page
- Why does the fault move between axes on different power-ups?
- What should I measure during a failed power-up?
- How much voltage unbalance can a rotary converter feed a machine?
- Can an oversized phase converter still sag on startup?
- Which results point at the supply and which at one drive?
- What do I fix first once the sag is confirmed?
- Will a bigger phase converter fix the trips?
- Questions asked
A machine that alarms on one axis at one power-up, on two axes or all three at the next, with a spindle fault riding along, is showing the signature of the supply, not the machine: the rotary phase converter's output sags the moment a big motor starts, and every drive on that bus watches the same dip. Converter horsepower, conductor size and a clean cabinet do not settle the case; correlated voltage measurements do. Measure the three line-to-line voltages at the machine disconnect through at least one failed power-up and one clean one, judge the start-time unbalance against the utility-grade working limit below, and let the timestamp decide whether you work the feed and converter or the one axis that trips alone. Below: the measurement setup, the unbalance arithmetic, the feed drop calculation and the fix order.
Why does the fault move between axes on different power-ups? #
A fault that relocates between axes, pairs of axes and all three axes points at a condition every drive shares, and the only one that changes power-up to power-up is the converter's output sagging during the start transient; whichever drive samples its DC bus lowest first latches the alarm.
An axis drive watches its own DC bus, and on a 240 V-class three-phase input that bus idles near 340 V DC — the peak of the rectified line-to-line voltage — with the undervoltage trip set below it by the drive designer. During the fraction of a second a spindle or axis motor takes to run up, every rectifier on the machine sees the converter's dip together, and whichever bus crosses its trip first latches first; contactor coils fed from the same legs can drop out mid-start as part of the same event.
Which drive wins changes with idler temperature, with the load the converter already carries, and with where in the acceleration ramp the dip lands, so the alarm lands on one axis this start and on a different set the next. A failed motor, a damaged power cable or one bad drive does not behave that way: it fails the same way every time, on its own axis, whatever the supply is doing.
What should I measure during a failed power-up? #
Record all three line-to-line voltages at the machine disconnect during one failed start and one clean start, with a CAT III 600 V true-RMS meter or a three-channel recorder; the transient as the spindle energizes decides the case, not the steady readings taken before startup.
One safety note before the meters come out: de-energize, lock out and test for absence of voltage before opening the disconnect, the plug wiring or the converter control box — NFPA 70E, 2024 edition, covers those safe work practices, and your authority having jurisdiction and the equipment documentation carry the local requirements. Take the start-time readings where the installation allows it without opening an enclosure, such as at the plug and receptacle, with CAT III 600 V leads and the rated barriers in place.
A three-channel power recorder on the load side of the machine disconnect, logging continuously from before the first power-up through contactor pull-in and spindle enable, is the instrument that settles this case; a transient that lasts half a second is invisible to spot checks. Without a recorder, a true-RMS handheld meter with min/max capture held through the whole start gets the depth, though not the shape. Record the failed start first, then repeat an identical start for the clean reference with the recorder still connected. Beside each capture, write the alarm set and its order, the spindle-fault state, any control display code, and whether the converter's start contactor pulled in once.
How much voltage unbalance can a rotary converter feed a machine? #
Hold start-time unbalance at the machine within 3%, the ceiling ANSI C84.1 (2020 edition), the standard for service voltage ranges, recommends for utility supply, and treat anything past 5% as a trip waiting to happen; confirm the machine tool builder's own limit in its manual.
Unbalance comes from the three line-to-line readings: average them, take the largest departure from that average, and divide the departure by the average. IEEE 1159 (2019 edition), the recommended practice for monitoring electric power quality, treats unbalance toward 5% as an equipment-withstand matter. EN 50160 (2022 edition), the European standard for public supply voltage quality, holds utilities to 2%, the tightest of the three references, and a converter's start transient is exactly where it falls behind a utility.
Worked example - unbalance at the machine disconnect on a failing spindle start.
Illustrative readings, 240 V-class converter output:
AB = 238 V, BC = 214 V, CA = 232 V
Average = (238 + 214 + 232) / 3 = 684 / 3 = 228 V
Largest departure from average = 228 - 214 = 14 V
Unbalance = 14 / 228 × 100 = 6.1%
6.1% fails the 3% working limit and overshoots even the 5% withstand figure, so that capture convicts the supply regardless of what any drive manual says about ride-through. Read the result as an estimate to verify against the machine tool builder's electrical documentation and the limits your local code sets.
Can an oversized phase converter still sag on startup? #
Yes: a converter's horsepower rating describes the motor it can start, not the voltage it holds while starting it, and a rotary conversion raises the current a motor draws during start, so the sag depth is set by the single-phase feed and every connection, not by the converter's rating plate.
Worked example - single-phase feed drop at the start transient.
Illustrative inputs: 240 V single-phase service, 100 ft one-way run of #4 copper
from the main breaker panel to the converter control box, 150 A starting input current.
Resistance of #4 uncoated copper, NEC Chapter 9 Table 8 (NFPA 70, 2023 edition):
0.308 Ω per 1000 ft
Drop = 2 × 150 A × 0.308 Ω/1000 ft × 100 ft = 2 × 150 × 0.0308 = 9.24 V
Fraction of nominal supply = 9.24 V / 240 V = 3.9%
The two output legs tied to the single-phase lines carry that dip straight to the machine, and the generated leg follows; the converter's own regulation loss stacks on top, so the machine sees at least what the feed calculation shows. For the arithmetic I used the DC resistance NEC Chapter 9 Table 8 lists for #4 copper; at this feeder size the AC reactance adds slightly, so treat the number as an estimate checked against the converter manual's rated input current.
Converter sizing guidance is blunt about the physics: a motor start on converted three-phase draws noticeably more current than the same start on a utility service, which is the duty the horsepower rating is sold for. The fine print still matters: converters are advertised by the motor they can start while the continuous three-phase output rating can be far lower — one hard-start unit lists 25 A continuous — so sequence the machine's power-up, control first, then axes, then spindle, and never let the transients stack.
Which results point at the supply and which at one drive? #
Timestamp is the judge: if several axes and the spindle alarm within the same second that the recorder catches the lowest line-to-line voltages, the supply is the cause; if the voltage trace stays flat through every start and one axis alarms alone each time, work that axis branch instead.
Before convicting anything, pull each drive's fault history — trip timestamps, fault numbers, and the bus voltage at trip if the model logs it — and match it against the manufacturer's fault table for that exact model and revision. Read the label closely: many drives report a collapsed or lagging leg as a phase-loss fault rather than an undervoltage fault, the distinction the Why a drive shows a missing phase fault on single-phase supply page works through. The same mechanism bites when a drive decelerates into a weak supply instead of starting into one, which is the variant Undervoltage fault on decel: supply sag, not braking covers.
Then read the recordings against these patterns:
- Several axes and the spindle alarm together, inside the same second the recorder catches the deepest dip: the supply did it, and the fix is the feed, the connections and the converter sizing, not drives.
- The alarm relocates between attempts while every failing capture carries the same voltage signature: a marginal supply whose margin moves with idler temperature, line conditions through the day and start sequencing — same fix, then keep recording.
- Voltages stay flat and inside the working limit on failed and clean starts alike, and one axis trips alone every time: that axis branch owns the fault — motor, power cable, feedback or that drive, per its fault table.
- A contactor drops out mid-start while the recorder shows the dip: the coil follows the same sagged legs, a symptom, not a separate cause.
- Nothing repeats: record more starts, including a cold-morning one, before any part moves.
What do I fix first once the sag is confirmed? #
Work the supply path from the panel outward, cheapest and most likely first: remake connections, verify the feed's ampacity and drop, then the converter's capacitors and start contactor, and only then resize the converter; re-run the same recording after each single change.
- Remake every termination in the path — plug, cord ends, disconnect lugs, converter terminals — cutting back and remaking any conductor or screw that shows heat discoloration rather than only tightening it; a repair pigtail or a re-used cord end marks an earlier fight with this same fault.
- Check the feed conductors against the converter manual's rated input current: NFPA 70, the National Electrical Code, 2023 edition, Article 455 covers phase converters and requires supply conductors with ampacity of at least that rated input current — confirm the installation with your authority having jurisdiction.
- Re-run the drop calculation with your measured starting current; when the feed alone consumes around 3% of nominal at start, upsize the conductors or shorten the run before touching the converter.
- Compare the converter's run capacitors with the manual's rated capacitance and voltage, and watch the start contactor pull in and drop out exactly once per start; capacitors that have lost value shift the generated leg and deepen start-time unbalance.
- Change one thing at a time and repeat the recorded start after each change until the failed-start capture matches the clean one.
A converter that runs hot through these repeated starts is working past its continuous rating; Why a rotary phase converter overheats after startup covers that failure mode separately.
Will a bigger phase converter fix the trips? #
Not on its own: a larger idler draws a larger start transient through the same single-phase feed, so the machine-side dip can deepen rather than shrink; upsize only after the feed, connections and converter health verify clean, then size to the machine's total starting load, not its running horsepower.
Upsizing is right only when the arithmetic asks for it: total the machine's starting duty in the order you actually power it up — spindle, axes, hydraulics, coolant — and match the converter's starting rating to that total, with feed conductors sized to the new input current. A larger idler behind an unchanged, marginal feed reproduces the trip with more current behind it, which is why the feed and the terminations come first in the order above. If the converter itself keeps losing, weigh the alternatives with their limits in view: a single drive cannot carry a whole machine's mixed loads the way a converter does — Why a VFD cannot power a whole machine as a phase converter maps where that road ends.
Decided, case by case: a start-time dip landing together with multi-axis and spindle alarms is a supply fault — work the terminations, conductors, capacitors and sizing in the order above and verify with the same recording; a flat, healthy trace with one axis tripping alone every time is that axis branch — follow its drive's fault table; a moving alarm with no repeatable dip is a thin margin — keep recording across more starts, because the drop calculation will show where the margin went.
Questions asked
Does a phase-loss alarm on a converter-fed drive mean something different from an undervoltage alarm?
Often they share one root cause. The drive decides which label to give a leg that collapsed or lagged at the same instant, and the two faults sit in different rows of the drive's fault table. Read the table for your exact drive model and revision before assigning a cause, because one model reports input phase loss where another reports low DC bus for the same sag.
Can I keep restarting until the machine powers up clean?
No. Each start through a deep, unbalanced dip heats the axis motors and the idler windings without tripping anything, and the damage from repeated unbalanced starts is cumulative. A drive that trips on undervoltage is protecting itself; treat each restart as one recorded test instead, with the recorder connected and the results written down.
Does the same diagnosis apply to a static capacitor phase converter?
Expect it to look worse. A static converter shifts a leg with capacitors and leaves the three-phase output weakest exactly when a motor starts, so the same measurement and the same unbalance arithmetic apply, and a static unit usually shows deeper unbalance at lighter loads than the rotary the numbers above describe. Size and derate per the converter's own documentation either way.
Which leg sags first on a rotary converter under load?
The generated leg: the two output legs tied to the single-phase lines carry the load directly, while the third is produced by the idler through the converter's own impedance, so a start transient dips the pair of voltages that include the generated leg first. The machine can read balanced at no load and fail the start transient anyway.

