Troubleshooting
Why low motor voltage increases motor heating
Short answer
Yes — the extra heat follows the current. Torque capability falls with the square of terminal voltage, so a loaded motor on low voltage slows, slip rises, and the current needed to hold the same shaft power climbs; copper losses rise with the square of that current, whenever the motor carries load and not only during starting. Reduced-voltage starting overheats a motor only when acceleration stretches so long that high-slip heating becomes damaging.
On this page
- Why torque capability falls with the square of the voltage
- Where the extra heat goes at full load
- Reduced-voltage starting changes the shape, not the energy
- Worked example: a 30 hp motor at 460 V running on 414 V
- Trend five readings before touching anything
- Which branch you are on, and the fix
- Questions asked
The motor runs hot, the amps read high and the supply sags — those three belong together. Torque capability in an induction motor falls with the square of terminal voltage, so a loaded motor on low voltage slows, slip rises, and the current needed to hold the same shaft power climbs; stator and rotor copper losses rise with the square of that current. The heating follows the load, not the calendar: it appears whenever the motor carries load at reduced voltage, and not only during starting. Reduced-voltage starting is a different case, and it only overheats the motor when acceleration stretches so long that high-slip heating turns damaging. Measure terminal voltage, current, speed and acceleration time together, then fix the branch the readings name.
Why torque capability falls with the square of the voltage #
At a fixed supply frequency, the air-gap flux is set by the voltage-to-frequency ratio the winding sees. Torque comes from that flux acting on rotor current, and near standstill both scale with terminal voltage: starting current falls roughly in proportion to voltage, so starting torque falls with its square. At 80 percent of rated voltage the motor holds about 64 percent of its normal starting torque — 0.80 squared — and the same squared relationship governs the pull-up and breakdown torque available while it accelerates, so a sagging supply shrinks your accelerating margin much faster than it shrinks the current.
That square is why a voltage problem usually shows up first as slow starts and hot windings rather than as a modest amp reading.
Where the extra heat goes at full load #
The driven machine demands the same torque whatever the supply does. With less flux, the rotor must slip further against the field to make that torque, and slip roughly scales with load torque divided by the square of voltage. Rotor loss equals slip times the power crossing the air gap, so each extra point of slip is heat in the rotor bars and end rings. On the stator, holding the same shaft power at a lower terminal voltage takes more current, and copper loss rises with the square of current. Iron loss drops a little with the weaker flux, but under load the copper losses dominate and the net is more heat in the same frame. Whether winding temperature actually climbs then depends on how fast the frame sheds that heat — temperature rise falls as heat transfer improves, the same balance that governs a resistor cooling in still air.
Below some voltage the picture inverts. Flux collapse cuts torque below the load's demand, the motor decelerates toward stall, and stator current can fall below the overloaded-running value even as the motor heats faster — slip is near its maximum and a shaft-mounted fan is barely moving. That is why a current reading alone cannot clear a motor; read it with voltage and speed.
Reduced-voltage starting changes the shape, not the energy #
On a direct-on-line start the inrush runs about six times full-load current for a typical induction motor — the mechanism behind why an induction motor draws heavy current at starting — and through acceleration the rotor sits at high slip, where most of the power crossing the air gap is burned in the rotor. Reduced-voltage starting trades that tall, short current curve for a shallower, longer one. The energy the start must deliver is fixed by the load's inertia and final speed, so if acceleration completes inside the motor's permitted start time, the total heat put into the machine is close to the same either way; that is the design intent, and a completed reduced-voltage start is not itself a heating problem.
It becomes one when voltage is cut so far that accelerating torque barely clears load torque. Acceleration time then stretches out of proportion, the rotor parks at high slip with little cooling, and the long tail of elevated current does more heating than the peak it avoided. Each aborted attempt adds to that heat even when it ends before the overload acts, because the rotor does not cool between attempts. Judge the starter by the whole acceleration trace — current against time and speed against time — not by how low the inrush peak looks.
Worked example: a 30 hp motor at 460 V running on 414 V #
Inputs, all illustrative values for a typical case: a 30 hp — 22.4 kW at the shaft — 460 V, three-phase, 60 Hz induction motor with 40 A full-load current and 1775 rpm on its nameplate, and a voltmeter and clamp meter at the motor terminals reading 414 V under full process load.
Three relations do the work: torque capability scales with the square of the voltage ratio; current for constant shaft power scales with the inverse of that ratio while power factor and efficiency hold near nameplate; and copper loss scales with the square of current.
Voltage ratio: 414 V ÷ 460 V = 0.90. Torque capability: 0.90² = 0.81, so about 81 percent of nameplate torque capability remains. Current to hold the same shaft power: 40 A ÷ 0.90 = 44.4 A, which is 111 percent of nameplate current. Stator copper loss: (44.4 A ÷ 40 A)² = 1.23, about 23 percent more copper heat. Slip: rated slip is 1800 − 1775 = 25 rpm, and holding the same torque on 0.81 of the voltage stretches it to 25 ÷ 0.81 ≈ 31 rpm, which adds rotor loss of a similar order.
Result: the motor sits at the bottom edge of its voltage band, carrying 111 percent of nameplate current with roughly 23 percent more copper loss and a fifth of its torque margin spent.
Decision: NEMA MG 1, the NEMA standard for motors and generators, rates general-purpose polyphase motors to deliver rated output with terminal voltage within plus or minus 10 percent of nameplate, with temperature rise expected to climb toward the edges of that band; check the tolerance in your motor's own documentation and the edition it was built to, and confirm local requirements with the authority having jurisdiction. A terminal voltage at or under 90 percent of nameplate while the motor carries load is a supply defect — run the connections, conductor size, taps and source capacity down — not a motor setting to tune. Expect the overload to trip on 111 percent current eventually; the trip can come long after weeks of hot running.
Trend five readings before touching anything #
Before you connect any instrument or open a terminal box, de-energize the circuit, lock out and verify the absence of voltage; fit clamps and leads with the circuit dead, then restart and read live with instruments rated for the circuit's measurement category.
- Terminal voltage, at the motor terminals. Read it before the start, through acceleration and under load; a voltage taken at the panel with the motor disconnected cannot show the drop the feeder and its connections add under current.
- Line current, per phase. Compare the three phases with each other and with nameplate; a mismatch points at unbalance or a joint before it points at the supply.
- Speed. A tachometer or the driven equipment's own feedback; speed under the normal loaded value is slip made visible.
- Acceleration time. From start command to steady speed, against the motor's permitted start duty.
- Winding or frame temperature, trended. A climb across starts and shifts says losses are beating cooling, whatever a single reading shows.
Which branch you are on, and the fix #
- Voltage dips through the start and recovers at speed. The starting branch: feeder length, conductor size, source impedance, another motor starting on the same bus. Work it as numbers, not guesses — the second motor starting voltage drop calculation covers overlapping starts, and motor starting voltage drop with utility short-circuit capacity covers a weak source. Decision: correct the starting branch — shorter or larger feeder, staggered starts, a stronger source — and leave the running motor alone.
- Low at the terminals whenever the motor carries load. The running branch: work upstream from the terminals — lugs, contactor contacts, overload blocks, splices — then conductor size against length and current, then supply taps and source capacity; discoloration or a hot joint confirms it. Decision: repair the path, because no parameter fixes lost conductor.
- Terminal voltage normal, current high, speed low. The load or motor branch: confirm the driven equipment turns freely and the process demand has not grown, then run an unloaded or uncoupled check where the machine permits; little improvement points into the motor — bearings, winding, connection. Decision: load first, motor second.
- A reduced-voltage or soft start that stretches past its expected time. The start, not the supply: raise accelerating torque only inside the motor's and starter's documentation — a different autotransformer tap, a current limit that still finishes, less load during the start, such as a closed damper — and check the torque margin against inertia in the motor starting time calculation for torque margin and inertia; if a soft starter is in the circuit, its current-limit setting must still complete acceleration, which is the subject of setting a soft starter current limit without overheating the motor. Decision: if torque margin cannot be made positive with room to spare, change the starting method — and never raise or jumper the overload to force a start.
Questions asked
Does a small ongoing temperature rise really matter?
Yes. The usual rule of thumb is that every 10 °C of extra winding temperature roughly halves insulation thermal life, so the worked example's 23 percent extra copper loss is not cosmetic if it holds for hours each day. Trend winding temperature across weeks; a motor that trips its overload after months of running hot was being damaged the whole time.
The supply measures 480 V but the motor nameplate says 460 V. Is that low voltage?
No — it runs the other way. Motors installed on 480 V systems are commonly nameplated 460 V so the machine sits inside the system's voltage band, and 480 V on a 460 V nameplate is about 4 percent high, not low. Judge every reading against the nameplate and take it at the terminals under load, where the drops you are hunting actually appear.
What does the NEC say about voltage drop to a motor?
NFPA 70, the National Electrical Code, 2023 edition, publishes its voltage-drop figures as informational notes rather than enforceable rules — 3 percent for a branch circuit or feeder and 5 percent for the two together. The binding limit for your motor is its own rated voltage band, so measure at the terminals under load and confirm requirements with the authority having jurisdiction and the equipment documentation.
Does voltage unbalance heat a motor the same way as low voltage?
Faster. Unbalance drives negative-sequence currents whose slip runs at nearly twice the normal value, so a small unbalance makes far more rotor heat than the same shortfall in total voltage. NEMA MG 1 sizes motors on the basis of no more than 1 percent voltage unbalance at the terminals, and worked examples on its derating method put the life cost of 3 percent unbalance above half. Measure all three phases before blaming the feeder.
Will the overload relay catch undervoltage heating in time?
Eventually, and often later than you would like. A thermal overload follows current, so the example's 111 percent running current will trip a correctly sized relay — but trip curves let a modest overcurrent run a long time, and in a hot room the winding ages first. A stalled start at far lower voltage trips quickly. Treat any unexplained overload trip as a voltage question too.