What a CT-to-4-20 mA current transducer must match

Power quality and harmonics Published 9 min read By Current Intel engineering team

Short answer

Select the transducer by its CT input, not the primary amps: the input must be built for the installed secondary rating (5 A or 1 A), the loop scales as 4 mA plus 16 mA times primary over full-scale primary, and the CT's rated burden must cover the transducer's input VA plus the leads. For a 1500/5 A metering CT, set 4 mA at zero and 20 mA at 1500 A.

On this page
  1. Match the input to the CT secondary rating
  2. Set the two endpoints of the output span
  3. Check the burden the transducer adds
  4. The selection data to collect
  5. Sizing the loop for the worked metering CT
  6. Install, wire, and verify the loop
  7. Questions asked

The part you need is a current transducer with an explicit current-transformer input and a 4-20 mA output — not a converter specified only by the amperes it is supposed to read. A device sold by primary amps alone usually carries its own internal sensing core and knows nothing about the switchboard's metering winding you already have. Three matches decide the order: the transducer's CT input to the installed secondary rating, the loop's endpoints to the primary full scale you choose, and the CT's rated burden to the transducer's input VA plus the lead resistance. Get those three right and the loop reads true from commissioning day. The sections below give the selection table and a worked 1500/5 A example with the arithmetic written out.

Match the input to the CT secondary rating #

A CT secondary is not a voltage signal you can feed anywhere. It is a current source: the winding pushes an exact fraction of the primary current through whatever is connected, so on a 1500-to-5 metering set the secondary carries its full rated secondary current when the primary carries 1500 A, whatever the transducer does with it. The first selection line is the input class, and it must match the winding's rating exactly.

Feed that winding into an input built for a 1 A class and the receiver reads about five times the true current — the five-times error a 1 A relay input produces on a winding rated for the higher secondary — with the input driven past its rating on top of it. Run the mismatch the other way and you lose resolution rather than accuracy.

Manufacturers document the input side plainly. Littelfuse's TCSA series, a CT-input 4-20 mA transducer family, specifies its CT input as a 2 VA current transformer accepting the full secondary range, and the two-piece arrangement its datasheet assumes — the plant CT's secondary wired to the transducer's input terminals, the mA loop pair out to the receiver — is what most monitoring retrofits need.

Prefer a unit certified to the measurement-equipment safety standard: IEC 61010-2-010:2019 sets the particular safety requirements for measurement transducers and their accessories, so that certification is what a compliant CT-input transducer is built and tested to. Confirm what your installation requires with the local authority having jurisdiction and the equipment documentation. If a catalog search through a switchgear or drives brand comes up empty, the devices are not filed there; look in the measurement or signal-conditioning section under transducers and signal converters with a CT input option.

One more input-side check: whether the transducer reads true RMS. On a feeder serving a drive the current is deliberately distorted, an average-responding input misreads it, and the datasheet states which type the input is.

Where you get to choose the winding, meter from a metering-accuracy core. IEC 61869-2, the current-transformer part of the instrument-transformer series, defines the accuracy classes: a metering class such as class 0.5 bounds the ratio error to about 0.5 percent at rated current, while a protection class such as 5P20 promises output within 5 percent up to 20 times rated current for relays and makes no promise at light load. A transducer on a protection core still reads, but its light-load accuracy is whatever the core happens to give, so check the class printed on the nameplate before hanging anything else on that winding.

Set the two endpoints of the output span #

The loop is linear, and the transducer's manual states it as a definition: the device holds 4 mA at zero primary current and the span's top value at the configured full-scale primary, and between those points the loop current in milliamperes equals 4 plus 16 times the primary amperes divided by the full-scale amperes. Full scale is your choice, not the winding's: map the whole rated primary onto the span, or set the top point at the highest steady load the receiver actually watches and gain resolution over the range that matters. Configure the same endpoints in the receiver's analog input, and only there — the transducer emits the raw span and the receiver owns the engineering units. Putting that signal into a PLC cleanly is a subject of its own; conditioning a current sensor signal for a PLC analog input covers the receiving side.

Keep the live zero. An unloaded feeder still produces 4 mA, so a receiver scaled to that span can tell a healthy no-load feeder from an open loop wire, which reads 0 mA and can be alarmed as a fault.

Check the burden the transducer adds #

Every device wired into a CT secondary adds burden, and burden past the winding's rating bends the ratio: the secondary current falls below its true value, readings run low near full load, and the accuracy class on the nameplate no longer holds.

The transducer datasheet states its input burden in VA, sometimes in ohms, at rated secondary current. Add the leads at the square of the rated secondary amperes times the round-trip ohms — on the 5-ampere winding class that is 2.5 VA for every 0.1 ohm — and keep the sum at or below the VA printed on the CT nameplate. On a 1 A winding the same 0.1 ohm costs only 0.1 VA, which is why long secondary runs are built on 1 A cores. This is the same arithmetic metering installations already use, and this CT secondary burden sizing guide works it in detail. If the nameplate burden cannot cover the transducer plus the leads, the fix is a different winding, not a setting — split core current transformer selection for power meters covers choosing the core itself.

The selection data to collect #

Fill every line before ordering; each one comes off a nameplate or a datasheet, never off the primary amps.

Selection item What to record What it decides
CT ratio primary over secondary, for example 1500/5 A the span available to scale
Secondary rating the 5-ampere or 1-ampere class, from the nameplate the transducer input class
CT rated burden VA at rated secondary, from the nameplate whether transducer plus leads fit
Winding class metering or protection class the monitoring accuracy you can claim
Transducer CT input documented input for that exact secondary class, with its input VA the match itself and the burden adder
Loop output 4-20 mA, two-wire loop-powered or four-wire wiring and receiver compatibility
Loop supply the documented supply window, such as 10 to 30 V DC voltage headroom for everything in the loop
Receiver analog input the span it expects and its input resistance endpoint configuration and the loop voltage budget
Full-scale primary the highest primary current the span should represent the span's top endpoint

Sizing the loop for the worked metering CT #

The inputs, and where each comes from:

  • Winding: a metering current transformer marked 1500/5 A on a 1500 A feeder — the size of real-time feeder monitoring job that sends people hunting for a converter in the first place.
  • Transducer input: documented for that exact CT secondary class with a 2 VA input burden — the input class the named transducer family specifies.
  • Loop supply: inside the family's documented 10 to 30 V DC window.
  • Chosen full scale: 1500 A, the winding's rated primary, so the whole span maps onto the feeder rating.
  • Still unknown: the CT's rated burden in VA, which sits on the nameplate and decides the last step.

The scaling rule, in words: the transducer holds 4 mA at zero primary current and raises the loop linearly to the top endpoint at full scale, so loop milliamperes = 4 + 16 × (primary amperes ÷ full-scale amperes). The burden rule is separate: input VA plus lead VA must stay within the winding's rated VA.

The arithmetic:

  • Endpoints: 1500 ÷ 1500 = 1, so 4 + (16 × 1) = 20 mA at full primary, and 4 + (16 × 0) = 4 mA at no load.
  • Quarter-load check: at 375 A, 375 ÷ 1500 = 0.25, then 16 × 0.25 = 4, so the loop sits at 4 + 4 = 8 mA.
  • Working backwards: a receiver showing 12 mA corresponds to (12 - 4) ÷ 16 = 0.5 of full scale, and 0.5 × 1500 A = 750 A.
  • Burden: the input impedance is 2 VA ÷ (5 A × 5 A) = 2 ÷ 25 = 0.08 ohm, which drops 5 × 0.08 = 0.4 V across the input terminals at rated secondary output, and each 0.1 ohm of round-trip lead resistance adds 25 × 0.1 = 2.5 VA.

Result: the loop maps 0 to 1500 A onto the full live-zero span — 8 mA at a quarter load, 12 mA at half — the input absorbs 0.4 V at rated output, and the winding must carry 2 VA plus 2.5 VA for every 0.1 ohm of leads.

Decision: order a transducer whose input is documented for the winding's own secondary class, configure the endpoints worked above at both the transducer and the receiver, and read the CT nameplate before the purchase order goes out. If the rated burden is smaller than 2 VA plus the lead VA, the winding overburdens and the readings sag low: pick a lower-burden input or a higher-rated winding. A 1 A input device is not a fix for anything in this example. These are datasheet and nameplate numbers, not field measurements, so check the sum against the actual nameplate and the transducer manual.

Install, wire, and verify the loop #

  1. De-energize the feeder and verify absence of voltage before opening the CT compartment or the transducer terminals; a locked-out, tested-dead circuit is the only condition under which this wiring gets touched.
  2. If a job must ever be done with the feeder energized, the CT secondary terminals are shorted with the winding's shorting block before any wire is lifted — an open-circuited CT secondary under load builds hazardous voltage at its terminals.
  3. Wire the CT secondary to the transducer's input terminals exactly as the datasheet's diagram shows, and run the loop pair to the receiver in the polarity its input expects.
  4. Power the loop inside the transducer's documented window — 10 to 30 V DC on the named family — remembering that a two-wire loop-powered unit draws its operating power from the loop, so the receiver's supply must still cover the transducer's drop at full span.
  5. Verify at a steady load: clamp a suitable ammeter around the primary, read the receiver's engineering value, and expect the two to agree inside the transducer's stated accuracy. Confirm the live-zero reading at no load; a feeder running while the loop reads 0 mA points to the wiring or the loop supply.

Questions asked

Can one 4-20 mA transducer feed a PLC input and a local panel meter together?

Yes, in series. The loop current is identical through every device wired into the loop, so a PLC input and a panel meter can share one transducer. Add the input resistances of everything in the loop, multiply the total by 16 mA, and keep that voltage plus the transducer's own drop inside the loop supply's range; a loop-powered model documented for 10 to 30 V DC shows the kind of window to check. Both devices' manuals state their input drops, so confirm before wiring.

How does the receiver tell an unloaded motor from a broken loop wire?

Through the live zero. A healthy feeder carrying no current still produces 4 mA, so the receiver shows a low but real reading; a broken wire, a lost loop supply or a dead transducer pulls the signal to 0 mA. Many analog inputs are configured to treat anything at or below 3.6 mA as a fault indication, the convention behind NAMUR NE 43, so set that threshold and the input alarms on a dead loop instead of reporting zero amps.

Can I clamp a transducer around the conductor instead of using the existing CT?

Yes. Transducers with a built-in sensing core clamp around the conductor and deliver 4-20 mA directly, which suits a retrofit where the winding is a protection class, its burden is already spoken for, or no secondary is free. Select the clamp by the conductor's maximum load current and diameter, because the core sees the full load current, then scale and verify the endpoints exactly as with a CT-fed unit.

What accuracy should I expect from the finished loop?

The errors stack. A class 0.5 metering winding contributes up to 0.5 percent at rated current, the transducer adds its own stated percentage, and the analog input's resolution adds a little more; leads that push the winding past its rated burden distort all of it. Read each figure from its own datasheet and nameplate, and use the steady-load clamp comparison at commissioning to confirm the assembled loop.

Keep reading

  • Selection guide

    Split core current transformer selection for power meters

    The meter input decides: a 5 A or 1 A secondary split core CT feeds a low-impedance current input and must stay shorted, while a voltage-output split core needs a high-impedance input. Then match the ratio to the load, add meter burden to lead resistance against the rated VA, and take class, window and insulation from the datasheet.

    Power quality and harmonics

  • Selection guide

    Measuring three-phase motor current for a PLC alarm input

    Use a self-powered current-loop transducer with a span at least equal to the motor's maximum current — 100 A here — clamped around one insulated phase conductor and wired to a PLC analog input configured for current. Never land a bare CT secondary on an analog input, never clamp around all three conductors, and treat the alarm as monitoring: the overload relay still does the protecting.

    Motors and motor starters

  • How-to

    Why a shunt alone can't meter DC amps and volts into a PLC

    One shunt cannot serve both measurements. Its millivolt drop is a differential, non-isolated signal proportional to current only, and either terminal can sit at full bus voltage above the PLC analog common. Read the 5–60 A current with a Hall-effect DC current transmitter and the 110–240 V DC bus with an isolated DC voltage transmitter, each scaled to the module's input range.