What the thermal overload relay current setting dial shifts
Short answer
The current setting dial on a thermal overload relay moves the trip curve's pickup, nothing else. At 85% the curve picks up at 0.85 times the heater or range rating, at 115% at 1.15 times, with the curve shape and trip class unchanged. Read any trip time at the multiple of the dialed pickup — applied current divided by the dial fraction times the heater rating — and verify against the relay's published curve.

On this page
The current setting dial marked 85, 100 and 115 on a thermal overload relay moves exactly one thing: the pickup current of its trip curve. The curve keeps its shape, the trip class stays as designed, and no trip time on the sheet scales by a fixed factor. At 85% the curve's pickup sits at 0.85 times the heater or range rating; at 115% it sits at 1.15 times. Every trip time is read at the ratio of the applied current to the dialed pickup, never by scaling the 100% time up or down by 0.85 or 1.15. This page defines the terms, works the arithmetic, shows the shift on a time-current curve sheet, and gives the injection test that proves the scaling on your relay.
The dial sets pickup current, nothing else #
A thermal overload relay's calibration reference is the rating of its heater elements or its marked current range; call it the base current, in amperes. The dial is a fraction of that base: 0.85, 1.00 or 1.15 on the common band (some relays mark a continuous adjustment across the same span). The pickup equals the dial fraction times the base current. Below the pickup a cold relay never times out; above it, the bi-metal integrates heat toward a trip. Everything downstream of the pickup — the curve shape, the trip class, the cooling and reset behavior — comes from the element's design. Moving the dial translates the entire curve along the current axis and touches nothing else.
What moves and what stays fixed #
- Moves with the dial: the pickup current, and with it the multiple that any applied current represents on the curve's current axis.
- Stays fixed: the curve shape, the trip class, the thermal memory (heating and cooling), the reset behavior.
On a relay calibrated to a 10 A base (example base current), the three positions land as follows:
| Dial position | Pickup current | Multiple versus the 100% read | Trip time at the same applied current |
|---|---|---|---|
| 85% | 8.5 A | 1.18 times the 100% multiple | shorter |
| 100% | 10 A | 1.00 times | reference |
| 115% | 11.5 A | 0.87 times the 100% multiple | longer |
The factors come from 1 ÷ 0.85 = 1.18 and 1 ÷ 1.15 = 0.87. Dropping the dial to 85% multiplies the applied current's effective multiple by 1.18 and the trip comes sooner; raising it to 115% multiplies by 0.87 and the trip takes longer.
The formula and a worked example #
One formula carries every read on a curve sheet:
multiple = applied current ÷ (dial fraction × base current)
Amps over amps leaves a dimensionless multiple, which is the unit the sheet's current axis is drawn in. The fixed anchor is the trip class: IEC 60947-4-1 (2018 edition, with later amendments), the low-voltage switchgear and controlgear standard covering contactors, motor starters and overload relays, defines the classes by cold trip time at 7.2 times the setting current — class 10 within 10 s, class 20 within 20 s, class 30 within 30 s. The class is printed on the relay or stated in its datasheet, and Reading overload relay trip classes and curves works through how the class bounds the curve.
Example inputs: base current 10 A, trip class 10, applied test current 72 A, dial moved with nothing else changed.
- Dial 100%: pickup 10 A, multiple 72 ÷ 10 = 7.2. At 7.2 times setting current the class 10 anchor applies: trip within 10 s, cold.
- Dial 85%: pickup 8.5 A, multiple 72 ÷ 8.5 = 8.47. A higher multiple, so the trip comes sooner than the anchor; the exact time comes off the relay's own class 10 curve.
- Dial 115%: pickup 11.5 A, multiple 72 ÷ 11.5 = 6.26. A lower multiple, so the trip takes longer than the anchor.
- Equivalence check: at the 85% dial, 0.85 × 72 A = 61.2 A, and 61.2 ÷ 8.5 = 7.2 — the same multiple, therefore the same trip time as the 100% test at 72 A. At the 115% dial, 1.15 × 72 A = 82.8 A gives 82.8 ÷ 11.5 = 7.2 again.
Each read is an estimate anchored on the class table; the time at any other multiple comes from the relay's published curve for that class, checked against the equipment documentation.
Reading a trip time off the curve sheet #
- Read the trip class and the base current from the relay marking and its datasheet.
- Compute the multiple with the dialed pickup in the denominator: applied current ÷ (dial fraction × base current).
- Find that multiple on the sheet's current axis, drawn in multiples of setting current.
- Read the time at that point, remembering the sheet assumes a cold relay; a hot one trips sooner.
The division direction is where reads go wrong. Multiplying the applied current by the dial fraction before dividing understates the multiple at 85% and overstates it at 115%, so the predicted trip moves the wrong way. The dial fraction divides; it never multiplies the applied current.
Drawing the three settings on one sheet #
Plot the 100% curve once. The 85% setting is the same curve translated so its pickup sits at 0.85 times base; the raised setting translates it to 1.15 times base. Because both axes are logarithmic, that horizontal translation changes the read time non-linearly: near the pickup a small current change swings the time a long way, and at high multiples the time barely moves. Sliding the curve right also walks it toward the motor's thermal damage region — coordination practice keeps the overload curve between the running current and the motor damage curve, so the long-time margin shrinks as the dial goes up even though the class never changes.
Proving the scaling with a current injection test #
De-energize the starter, lock out and tag, and verify absence of voltage before opening the enclosure; inject through the relay per the manufacturer's documented test procedure.
Set the dial to 100% and inject 72 A; record the trip time. Move the dial to 85% and inject 61.2 A — the trip time returns within test tolerance. Move to 115% and inject 82.8 A — it matches again. A mismatch points at the test, not the scaling: start each injection from the same thermal state, because a relay that has just tripped is hot and trips early, as described in Why a thermal overload trips again right after reset, and control the ambient around the relay; the controlled method is laid out in Thermal overload relay current injection test in a 25°C MCC.
Choosing where to put the dial #
Select the heater or range so it brackets the motor's nameplate full-load current — Setting overload relays from motor nameplate full-load current covers the selection — then trim the dial onto the intended setting inside the band. NFPA 70, the National Electrical Code, 2023 edition, Article 430.32, caps separate overload devices at 125% of nameplate full-load current for motors marked with a service factor of 1.15 or more and a temperature rise not over 40 °C, and at 115% for all others; the cap is a maximum, not a target.
Example: a motor at 9.5 A nameplate on the 10 A base lands near a 95% dial. When the correct dial would fall outside the band or the cap, the heater or range is wrong — a dial cannot rescue a mis-sized heater. Where a relay carries a separate 125% mark, What the 125% trip current dial setting on an overload relay means explains it. Confirm the final setting with the local authority having jurisdiction and the relay and motor documentation.
The decision #
- Reading a time: divide the applied current by the dial fraction times the base current, read the relay's own class curve at that multiple, and use the class table only as the cold anchor.
- Predicting the dial move: 85% makes the same current trip sooner (effective multiple ×1.18); 115% makes it trip later (×0.87); neither changes curve shape or class.
- Verifying: one injection at the 100% dial and the same current scaled by 0.85 and by 1.15 must return the same cold trip time.
- Setting: heater for nameplate full-load current first, dial inside the band and under the code cap, never to cover a wrong heater.
Questions asked
Do electronic overload relays have the same 85 to 115 percent dial?
Most do not. An electronic overload relay sets the motor full-load current and the trip class as separate settings, so pickup and timing are independent instead of tied to a heater rating. Some models add jam or stall protection as a separate pickup, for example choices of 150%, 200%, 300% and 400% of the setting with trip delays of half, 1, 2 or 4 seconds on some product families. Check the model's own documentation.
Is the 85 percent position the same thing as the NEC 115 percent allowance?
No. The dial positions are fractions of the relay's own heater or range rating, while the NEC numbers are percentages of the motor's nameplate full-load current. A dial at 115% lands at 115% of nameplate current only when the heater rating equals that full-load current. Select the heater for the motor first, then use the dial to land inside the allowed band, and treat the code caps as limits on the final setting.
Does ambient temperature shift the curve the same way?
It can, and the datasheet tells you which way. Ambient-compensated relays hold the pickup near the dialed value across enclosure temperature; uncompensated designs trip earlier in a hot cabinet and later in a cold one. That ambient shift stacks on top of the dial's deliberate shift, so a bench time measured in a cold shop will not match a hot MCC. Verify in the conditions the curve sheet assumes.
Can I get a trip time at 85% without the relay's curve sheet?
Only to an anchor point. The trip class fixes one time: a class 10 relay must trip within 10 seconds from cold at 7.2 times the dialed setting current, per IEC 60947-4-1. At an 85% dial the same applied current is a higher multiple, so the trip comes sooner than that anchor; the exact time needs the manufacturer's curve for the relay and its class.