Current IntelPower LibraryShop main store

Explainer

Why a bigger transformer trips a generator on DOL start

Motors and motor starters Published 7 min read

Short answer

No. At the same 5% impedance the 500 kVA unit's ohmic impedance is three times the 1500 kVA unit's, but the generator, cables and motor already limit the current, so the generator sees only about 5-6% less through the small unit. That few percent is still enough: the start sits near the breaker's pickup, so one transformer lands under it and the other over; fix the pickup setting or soften the start, not the transformer.

On this page
  1. The ohms behind the percent
  2. The current only moves a few percent
  3. Why a few percent still trips
  4. Read the trip timing, then the setting
  5. Fix the setting or the start, not the transformer
  6. Prove it with a recorded start
  7. The decision
  8. Questions asked

Short answer: no, not significantly. With both transformers at 5% impedance, the 500 kVA unit's ohmic impedance is three times the 1500 kVA unit's, but that extra ohms sits in series with the generator's own reactance, the cable run and the motor's locked-rotor impedance, which already do most of the limiting. In the worked example below, the generator sees only about 5-6% less starting current through the small unit. That is still enough to explain your trip: a DOL start this size lands within a few percent of the generator breaker's pickup, so the small unit slips under it and the big unit crosses it. The transformer is not faulty and not the fix. The fix is the breaker's magnetic setting or a softer start.

The ohms behind the percent #

Percent impedance is quoted on the transformer's own rated base; IEC 60076-1 defines the short-circuit impedance that way. Two units with the same percentage are therefore not the same source in ohms. Convert both at one common voltage:

Z = (%Z / 100) x V² / S

with V the line-to-line voltage in volts, S the rating in volt-amperes, and Z in ohms. Referred to an example motor-side voltage of 415 V:

  • 500 kVA at 5%: Z = 0.05 x 415² / 500,000 = 0.0172 Ω
  • 1500 kVA at 5%: Z = 0.05 x 415² / 1,500,000 = 0.0057 Ω

Same percent, triple the rating, one third the ohms: 1500 / 500 = 3. A bigger transformer at the same percent impedance is a stiffer source in ohms, and that is the whole reason it passes more starting current. The ohms scale with V², so another voltage changes both numbers but never the 3:1 ratio, and nothing below depends on it. The same conversion, with the transformer as the only impedance in the path, is the one behind calculating transformer secondary fault current in per-unit.

The current only moves a few percent #

At the instant of a DOL start, one series path sets the current: generator reactance, cables, transformer, motor locked-rotor impedance. The transformer is one term of four and rarely the largest. Hypothetical worked example, every input stated, all referred to the motor's 415 V side:

  • Generator: 750 kVA, example reactance 0.25 per unit on its own base, so Z = 0.25 x 415² / 750,000 = 0.0574 Ω. Your set's data sheet gives the true subtransient and transient reactances, X″d and X′d; the first peak follows one, the sustained start the other, and changing that value moves both cases together, not the gap between them.
  • Cables: 0.002 Ω, an example for a short run.
  • Motor: 180 kW at 415 V, example efficiency 0.95 and power factor 0.85, so FLC = 180,000 / (√3 x 415 x 0.95 x 0.85) = 310 A. Locked-rotor current taken as 6 x FLC = 1860 A at rated voltage, giving a locked-rotor impedance of 415 / (√3 x 1860) = 0.129 Ω. The real multiple comes from the motor's NEMA MG-1 locked-rotor code letter or its data sheet; 6 is typical for a standard squirrel-cage machine.

Adding the magnitudes in series, the usual first estimate:

Series term smaller transformer bigger transformer
Generator 0.0574 Ω 0.0574 Ω
Cables 0.002 Ω 0.002 Ω
Transformer 0.0172 Ω 0.0057 Ω
Motor, locked 0.129 Ω 0.129 Ω
Total 0.2056 Ω 0.1941 Ω

Current is V / (√3 x total): 415 / (√3 x 0.2056) = 1165 A through the smaller unit, 415 / (√3 x 0.1941) = 1234 A through the bigger one. The whole transformer swap is worth 69 A, about 5.9%; call it 6%. For scale, at rated voltage this start would draw about 1340 kVA, close to twice the set's rating, and during the example start the motor terminals sit near 260 V through the small unit versus 276 V through the big one. Those are deep dips either way: this is a hard start through both transformers, and neither makes it comfortable.

Why a few percent still trips #

Two effects turn a small difference into a trip.

The magnetic element of a thermal-magnetic breaker fires on the first asymmetric peak, which is the RMS current times a DC-offset factor. The number that meets the pickup is therefore a recorded peak, not the calculated RMS, and that comparison has traps of its own; why motor start peaks don't compare to instantaneous breaker settings covers them.

The observation itself is the second effect, and it is proof. A pickup well above both starts would let both through; well below, both would trip. One rides through and one trips, so the pickup, on the same side and basis as the currents, sits inside the roughly 6% band between the two starts. The start is marginal through both transformers; the small unit does not cure anything, it lands on the safe side of a line drawn through the middle of the band. Any other load running on the set during the start widens the current the breaker sees and slides the start within the band.

What the trip is not: inrush, because the transformer was energized first and held; and a transformer fault, because energization was clean and the oil shows no fault gases. More oil tests on the big unit answer a question that is already answered.

Read the trip timing, then the setting #

The timing names the element. A trip at contactor close is the magnetic pickup. A trip a second or more in is the long-time element: at the depressed voltage the fan accelerates slowly, and the current stays high long enough to cross the thermal curve. A set this size normally carries a thermal-magnetic case-frame breaker with adjustable long-time and magnetic dials rather than a programmable relay, so read the dials and the nameplate instead of assuming a curve. Opening that panel starts with the set shut down, locked out and verified dead, the electrically safe work condition that NFPA 70E, the standard for electrical safety in the workplace, 2024 edition, is built around.

Where the settings may sit: NFPA 70, the National Electrical Code, 2023 edition, caps the instantaneous setting of a motor's branch-circuit breaker in Article 430.52, but the generator's main breaker sits outside that article. Its settings come from the set's documentation and the coordination study, confirmed with your authority having jurisdiction.

Fix the setting or the start, not the transformer #

  • Trips instantly: raise the magnetic pickup one setting, on two conditions. The new pickup stays above the worst recorded start peak, and the cables and generator winding keep their short-circuit protection, because you are trading a little fault sensitivity for start tolerance. The long-time element still covers overload.
  • Trips after a second or more: start a centrifugal fan with its damper closed so the wheel is unloaded during acceleration, then compare the recorded acceleration time against the breaker curve. If the curve still crosses, the start has to get softer.
  • Pickup already at its top setting, or coordination forbids more: reduce the voltage at start. A soft starter with a 3 x FLC current limit hands the generator about half of what the DOL start pulled; converting a soft-start current limit to starting current shows the arithmetic. An autotransformer starter at an 80 percent tap trades starting torque for line current at the square of its tap. A VFD cuts furthest if the fan can use speed control.
  • The transformer itself: keep whichever unit the running load needs, presumably the big one, and put it back once the start is fixed. If you are still sizing, sizing a transformer for an across-the-line motor start covers the running side, but once a unit carries and survives the start, extra kVA buys the generator almost nothing.

Prove it with a recorded start #

Capture the start with a power analyser or the set's own metering: peak current, time above rated current, and voltage and frequency dip at the generator terminals. Then run three cold starts and one hot with the big transformer connected. Compare the recorded peak to the magnetic pickup and insist on visible margin, not a pass by the few percent that caused this whole problem. Check the dip against the limit in the set's documentation; ISO 8528-5 defines the transient performance terms generator sets are specified against. Confirm the run current after acceleration sits below the long-time setting. If the trip persists with settings verified and the dip inside its limit, take the waveform and both nameplates to the generator and breaker manufacturers' support.

The decision #

  • Whether the generator sees significantly less current through the small unit: no, about 6% in the example, real but small.
  • Trips at contactor close: raise the magnetic pickup one setting after the short-circuit check, then prove it with a recorded start.
  • Trips a second or more in: damper closed for the start, re-check acceleration time; if the thermal curve still crosses, fit a soft starter.
  • Pickup maxed or coordination blocked: soft starter at 3 x FLC, or a VFD if speed control pays for itself.
  • The transformer is neither the fault nor the fix: reinstall the unit the running load needs.

Questions asked

Does it matter that the transformer steps the voltage up?

No. The turns ratio scales the current on both sides by the same factor, so work the entire circuit referred to one voltage, either the generator's or the motor's, and compare everything there. The percentage difference between the two transformers, and the pickup sitting between the two starts, come out identical either way.

Can the smaller transformer saturate during the start and make things worse?

Not from starting current. Saturation belongs to energizing inrush, which lasts a few cycles and was ruled out here because the transformer was already live when the fan started. During the start the unit behaves as its ordinary series impedance, so the extra drop is simply current times impedance and recovers as the motor accelerates.

If the small unit clears the magnetic pickup, can the start still trip thermally?

Yes. Its extra impedance lowers the voltage at the motor, so the fan accelerates more slowly and the current stays above the long-time curve longer. A start that clears the magnetic pickup can still trip thermally, which is why you record acceleration time and not only peak current.

What current limit should a soft starter be set to for this fan?

Start at about 3 times the motor's full-load current, roughly half of what the direct-on-line start drew, and raise it one step only if acceleration is too slow. Each step trades generator current for start time, so check the resulting time against the motor's permitted stall time and the fan's inertia.

Keep reading

  • Explainer

    Converting a 350 kVA soft start limit to starting current

    A 350 kVA soft start limit is about 421 A of line current at 480 V: divide 350,000 VA by √3 × 480 V. The figure is apparent power, so no power factor enters the conversion, and it carries no duration — that comes from the torque-speed margin. The 12.5 kV fuse is a coordination problem; motor protection belongs at 480 V.

    Motors and motor starters

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Selection guide

    Sizing a transformer for a 200 HP across-the-line motor start

    Select a 1000 kVA transformer with nameplate impedance of 6.5% or less. The 3 kVA-per-HP rule gives 600 kVA for the 200 HP pump alone; adding 390.9 kVA of always-on load gives 990.9 kVA, so that is the screening size. The dip screen confirms it: 8.8% sag at 5.75% impedance, inside the 10% target, while 750 kVA would need 4.9% impedance to pass.

    Power distribution and transformers