Why a center-tapped 240 V delta has a 208 V high leg
Short answer
In a 240 V delta with one winding center-tapped, the grounded neutral sits at that winding's midpoint: its two ends read 120 V to neutral, and the opposite corner reads 240 × √3 / 2 ≈ 207.85 V, the altitude of the line-to-line triangle. A delta without a center tap has no neutral and no line-to-neutral relationship at all.

On this page
- One winding midpoint becomes the neutral
- The high leg is the altitude of the triangle
- Worked example for the nominal four-wire delta
- A delta without a center tap has no neutral
- Telling the four-wire systems apart
- Where the high leg may and may not feed a load
- Checking the pattern on the bench and in the panel
- Questions asked
The high leg of a 240 V delta with a grounded center tap reads about 208 V (240 × √3 / 2 ≈ 207.85 V) because that leg is the altitude of the equilateral triangle the three line-to-line voltages form. The tap puts the neutral at the midpoint of one winding, so that winding's two ends sit at half the line-to-line voltage from the neutral, while the corner opposite the tap sits at the triangle's full altitude. A delta without a center tap brings out no neutral at all, so there is no line-to-neutral relationship to calculate.
One winding midpoint becomes the neutral #
A delta secondary closes three equal windings in a loop; the three line terminals are the corners, and any pair of corners spans one full winding. Nothing in that loop is a neutral. The four-wire version adds a single detail: a tap at the exact electrical midpoint of one winding, brought out as the fourth conductor. That midpoint becomes the grounded neutral, the two ends of the tapped winding become the low legs, and the corner opposite the tap becomes the high leg — also called the wild leg or stinger. The underlying wiring ideas are collected in a reference on center-tapped and tapped transformer wiring principles.
On services, NFPA 70, the National Electrical Code (2023 edition), requires a four-wire delta to be grounded at the winding midpoint whenever that midpoint is used as a circuit conductor, and requires the conductor with the highest voltage to ground to be durably marked — in practice an orange outer finish or other effective means — at any accessible point. Confirm the grounding and marking practice with the authority having jurisdiction and the serving utility.
The high leg is the altitude of the triangle #
Draw the phasor triangle: each side is one line-to-line voltage, all three equal, so the triangle is equilateral. Put corners A and C at the ends of the tapped winding and the neutral N at the middle of that side; the high leg is corner B. The voltage you read from B to N can be walked in two steps: from B to A (one full winding) and then from A to N (half a winding). In an equilateral triangle the line from a vertex to the midpoint of the opposite side is perpendicular to that side, so those two phasors meet at 90 degrees and Pythagoras applies:
V_highleg = √(V_LL² − (V_LL / 2)²) = V_LL × √3 / 2
For the nominal system here the line-to-line voltage times root 3 over 2 gives ≈ 207.85 V, rounded to 208 V on every schedule. The shortcut V_LL × sin 120° gives the same figure because sin 120° equals √3 / 2; the 120 degrees is the phase angle between two line-to-line phasors. What does not apply is line-to-line divided by root 3: that multiplier locates the centroid of the triangle, which is where a wye neutral sits, not where this one sits. The delta neutral lies on a side, so the multiplier is root 3 over 2, and the high leg reads above the low legs instead of equal to them.
Worked example for the nominal four-wire delta #
Inputs, all nominal: a balanced, unloaded bank rated 240 V line-to-line.
- Low legs. The tap halves the tapped winding, so each end reads half of that rating = 120 V to neutral.
- High leg by Pythagoras. The rating squared is 57,600 V²; 120² = 14,400 V²; 57,600 − 14,400 = 43,200 V²; √43,200 V² = 207.85 V.
- Check with the multiplier. 120 V × 1.7321 = 207.85 V. Schedule it as 208 V.
The full nameplate schedule is therefore the line-to-line rating on all three pairs and 120 V / 120 V / 208 V line to neutral, and the high-leg reading is close to root-3 times each low-leg reading — a handy ratio check in the field. Under load, regulation pulls every value down a few volts and the three line-to-line readings separate slightly; treat the numbers above as the ideal-balance nominal, not a pass/fail band.
A delta without a center tap has no neutral #
Bring out only the three corners and the phrase line-to-neutral loses its meaning: no conductor is a neutral, so there is no voltage to calculate, only whatever the grounding arrangement does to a meter. Two arrangements cover what you will meet:
- Ungrounded delta. The system floats; a meter shows finite voltages to ground set by capacitive coupling and leakage, and a single ground fault re-references every reading without tripping any overcurrent device.
- Corner-grounded delta. One corner is bonded to ground, so the meter reads zero at that corner and the full line-to-line voltage at the other two. No low-voltage supply exists anywhere in the system.
Decision: if the drawing or the terminal chamber shows no tap, stop applying the tapped-delta schedule — that relationship belongs to the winding midpoint, not to the delta connection itself. Low-voltage loads on an untapped delta get their supply from a transformer with its own secondary.
Telling the four-wire systems apart #
The readings, not the word delta on a nameplate, identify the system. Measure any two lines, then each line to the same neutral terminal:
| System | Any two lines | Each line to the neutral |
|---|---|---|
| Delta, one winding tapped | 240 V | 120 V, 120 V, 208 V |
| Wye 208Y/120 | 208 V | 120 V on all three |
| Delta, corner grounded | same line-to-line rating | 0 V, then the full rating on the other two |
Mind the coincidence in the middle row: a wye's line-to-line voltage and this delta's high-leg voltage share one magnitude while coming from different geometry. A single reading near 208 V therefore proves nothing — pair it with the other two line-to-neutral readings before naming the system.
Where the high leg may and may not feed a load #
Line-to-line loads never see the tap. A single-phase load across any two lines — including a pair containing the high leg — receives the full line-to-line voltage, and a three-phase motor on all three lines runs exactly as it would on an untapped delta.
Line-to-neutral loads are different. Between the neutral and a low leg a load sees its rated voltage; between the neutral and the high leg it sees root-3 times its rating, roughly 1.73 times, which burns out lamps and power supplies — classically right after a panel rewire. For control power, feed a control transformer primary line-to-line; if the primary has to hang off the high leg, read feeding a 240 V control transformer from a high leg before you land the wires. Decision: every line-to-neutral load goes on one of the two low legs; the high leg serves line-to-line duty only.
Checking the pattern on the bench and in the panel #
Tracing secondary wiring or torquing a terminal means opening a cabinet: lock out, test for absence of voltage and verify the tester on a known source first. The voltage readings themselves are energized work, performed by qualified personnel under the site's NFPA 70E (2024 edition) procedure, with a meter rated for the circuit voltage and available fault current.
Then check:
- From the transformer drawing and terminal markings, confirm which winding carries the tap and which terminal is the neutral. No tap, no schedule.
- Read the three line-to-line pairs. Each should sit near nominal; a missing or far-off pair means a blown fuse, an open winding or a bad termination, and it invalidates every line-to-neutral reading.
- Read each line to that same neutral terminal and record the value against its physical lug. Expect two equal low readings and one roughly root-3 higher; the high reading is the high leg, and it must land on the corner opposite the tapped winding on the drawing.
- Identify it per the code marking above; never trust a phase label or conductor color alone.
- Recheck under load. If the two low readings pull apart as load comes on, the neutral path has impedance — a loose or undersized neutral — and that failure is walked through in why one 120 V leg rises under load on the other leg.
Pass condition: equal line-to-line readings, two equal low legs, one high leg near root-3 times them. That is a healthy four-wire delta delivering its design schedule. Anything else is a wiring, grounding or neutral fault — not a different formula.
Questions asked
Why isn't the high leg 240 V divided by the square root of 3?
Dividing by root 3 locates the centroid of a wye: on a 240 V system it gives 138.6 V, and that answer applies only when the neutral is the common junction of three equal windings. Here the neutral is the midpoint of one winding, so the multiplier becomes root 3 over 2, not one over root 3, and the reading lands at the triangle's altitude instead of its centroid.
Does the high leg affect a three-phase motor?
No. A three-phase motor connects to all three lines and never touches the neutral, so every pair it sees is a full line-to-line pair, including the pair that contains the high leg. The elevated voltage exists only between that one line and the neutral, which is why only line-to-neutral loads ever notice it.
Which phase carries the high leg?
Whichever phase lies opposite the tapped winding. North American panelboards commonly land it on B phase, but that is a convention, not a property of the connection. Identify it by reading each line to the neutral, then follow the orange or high-leg marking that NFPA 70, the National Electrical Code (2023 edition), requires at any accessible point.
What are the voltages on a center-tapped delta with a different line-to-line rating?
The two ratios are fixed by the geometry. On an older 230 V delta, each end of the tapped winding reads 230 V / 2 = 115 V to neutral, and the high leg reads 230 V × 0.866 = 199 V. Whatever the winding voltage, the low legs get one half of it and the high leg gets root 3 over 2 of it.