Troubleshooting
Why a rotary phase converter shows unequal leg voltages
Short answer
A rotary phase converter's manufactured leg sits above the utility legs at no load, so unequal leg voltages at the converter output are expected, not a defect. Calculate unbalance the NEMA MG-1 way from the three line-to-line pairs — 240, 260 and 272 V works out to 6.7% unbalance — then measure at the machine input under load and compare against the machine's documented input window before swapping any wires.

On this page
A rotary phase converter shows unequal leg voltages because two of its legs are the incoming single-phase supply and the third is generated by an idler motor whose voltage is propped up by run capacitors. At no load the manufactured leg reads high, and that is the design, not a defect. The fault that shapes this article: a 5 hp converter feeding a CNC mill whose display threw a voltage overload message while its output read 240 V, 260 V and 272 V. The number that matters is the voltage unbalance percentage, not the raw spread, and the measurement that settles the repair is taken at the machine input, with the machine running. Compute the unbalance the way NEMA MG-1 defines it, hold the loaded readings against the machine's documented input window, and leave the wiring alone until those numbers say something.
Why the manufactured leg reads high on an unloaded converter #
A converter delivers two legs straight off the single-phase supply and creates the third with the idler: the spinning idler acts as a generator, and the run capacitors between the manufactured leg and each supply leg feed the magnetizing current the idler needs. With nothing drawing on the output, that capacitor current has nowhere to go, so it pushes the manufactured pair's voltage above the supply voltage. The converter is sized the other way around: the same pair is meant to fall toward the nameplate value once the machine draws current. An unloaded converter with a visibly high third reading is behaving like a converter.
Two ground rules before the math. The pair between the two utility legs tracks the supply almost exactly, so it is your reference; the other two pairs include the manufactured leg. And take every reading line-to-line — the manufactured leg has no solid ground reference, so its voltage to ground is set through the capacitors and compares against nothing.
The unbalance calculation NEMA MG-1 defines #
NEMA MG-1 defines percent voltage unbalance for polyphase motors in clause 14.34 (the clause number has moved between editions; the formula is stable): 100 times the largest deviation from the average of the three line-to-line voltages, divided by that average. Many power meters report unbalance with this same formula, so a hand calculation matches what a meter display shows. Use three line-to-line readings from one point, one meter and one operating state, or the result describes nothing.
Worked example: the converter output, machine off #
Inputs: three line-to-line readings at the converter output, machine off, one digital multimeter: 240 V, 260 V and 272 V.
- Average = (240 + 260 + 272) ÷ 3 = 772 ÷ 3 = 257.3 V
- Deviations: 257.3 − 240 = 17.3 V, 260 − 257.3 = 2.7 V, 272 − 257.3 = 14.7 V
- Largest deviation = 17.3 V — it comes from the low reading, not the high one, which is why you calculate instead of eyeballing
- Unbalance = 100 × 17.3 ÷ 257.3 = 6.7%
| Pair at the converter output | Reading | Deviation from the 257.3 V average |
|---|---|---|
| Lowest pair | 240 V | 17.3 V |
| Middle pair | 260 V | 2.7 V |
| Highest pair | 272 V | 14.7 V |
The highest pair is almost certainly one that includes the manufactured leg, since the utility-to-utility pair sits at supply voltage — identify the pairs before acting on the pattern. By motor standards 6.7% is severe unbalance, but it is still not the verdict: these numbers are unloaded readings at the converter, and the machine responds to what reaches its input terminals under load.
What the machine does with the number #
Machine input monitors watch each pair against a window printed in the manual. As an example rather than a rule: a machine nameplated 230 V with a plus-or-minus 10 percent input window accepts 207 to 253 V on every pair. In this fault the highest pair sits 19 V above that ceiling while the other two stay inside, so the monitor can declare an input fault on one pair alone — exactly the pattern a converter's unloaded high leg produces, and exactly why the fault can appear with nothing overheating. The manual for the machine on your floor states the window it actually enforces.
The spindle motor cares too: unequal line-to-line voltages drive unequal winding currents, so the motor heats unevenly. And when a machine transformer sits between converter and spindle, the unbalance on its secondary will not match the converter output — the arithmetic behind that is in phase converter voltage unbalance across a transformer.
The measurement sequence #
De-energize, lock out and verify absence of voltage before opening either enclosure or moving a conductor; metering live terminals is energized work, and NFPA 70E, 2024 edition, covers the approach boundaries, the verification method and the protective equipment for that work — confirm what applies at your site with the authority having jurisdiction and the machine documentation.
- Label the three conductors at both ends and write down exactly which two points sit behind each reading. Line-to-line only, one meter, one setting throughout.
- Read the three pairs at the converter output with the machine off, then again with the machine running the cut that trips it. The manufactured pair should fall toward the nameplate value under load.
- Read the same three pairs at the machine input terminals under the same load. A gap between converter-output and machine-input values is voltage dropped in the feeder and its connections; matching values send the diagnosis back to the converter or to the machine's window.
- If the fault is intermittent, spot readings will miss it. Log the three pairs continuously instead: a power meter writing a timestamped record into a fanless mini PC gives you a trace to line up against the machine's fault history.
- Compute the unbalance at each point and in each state with the formula above, and put every number next to the machine's documented window.
- If the manufactured pair stays high under full load, or any pair collapses on machine start, stop measuring and inspect the converter's capacitor bank and its connections — where overloads and run capacitors sit in a rotary phase converter shows what belongs where.
The decision, case by case #
- Converter spread unloaded, machine input inside its window under load, no faults. Correct behavior. Record the numbers as the baseline and change nothing.
- Machine input above its window under load. Real overvoltage. Correct it at the converter using the adjustment the manufacturer documents, or set the machine transformer taps to the supply you actually have. Converter installations are covered by NFPA 70, the National Electrical Code, 2023 edition, Article 455; the adjustment procedure itself comes from the converter's documentation.
- Machine input below its window on start or under cut. Supply-side sag, not converter wiring — phase converter voltage sag causes machine startup faults covers that path.
- Machine-input unbalance above the machine's documented limit under load. The capacitor bank becomes a suspect; verify its values and connections against the converter documentation before replacing anything.
The wire swaps tried first could never have worked: relabeling conductors changes no line-to-line voltage, and swapping any two at the machine reverses the spindle, as why any two phase swaps reverse a three-phase motor explains. The verdict comes from the meter at the machine input under load, read against the machine's printed window — measure first, and rewire only when those numbers point at a connection.
Questions asked
Which of the three readings is the manufactured leg?
On a converter fed at 240 V, the pair between the two utility legs holds at the supply voltage through every load state, while the two pairs that include the manufactured leg move with load. Watch the three pairs while the machine starts and stops: the pair that stays flat is utility to utility. Identify the pairs before comparing anything against the machine's input window, because one reading belongs to the supply and two belong to the converter's output stage.
Does voltage unbalance hurt the motor or only trip the input monitor?
It does both. Unequal line-to-line voltages make a motor draw unequal currents, several times the voltage unbalance percentage, so one set of windings runs hotter than the nameplate cooling assumes. NEMA MG-1 answers with a derating requirement that tightens as unbalance grows, and the extra heat accumulates over every running hour, not only at the moment a monitor trips. Treat unbalance at the machine input as a motor-life issue even when no fault is showing.
Can I adjust the converter so all three legs read equal at no load?
Not in any useful way. The spread comes from capacitor current holding the manufactured leg up while nothing draws from it, so trimming capacitors until the unloaded readings flatten would starve the manufactured leg as soon as the machine pulls current. Converters are adjusted for the loaded condition, and the converter's documentation is the only source for how. Judge any adjustment by loaded machine-input readings, never by the idle spread.
Why do my leg-to-ground readings disagree with the line-to-line numbers?
The manufactured leg has no solid connection to ground; its voltage to ground is set through the run capacitors and shifts with capacitance, load and even the meter's input impedance, while the two utility legs sit near a fixed relationship to ground. Leg-to-ground numbers on the manufactured pair are not wrong, they are just not comparable, and no unbalance calculation uses them. Take every number for the comparison line-to-line.


