Current IntelPower LibraryShop main store

Troubleshooting

Why a sodium flood light goes out at motor start

Power quality and harmonics Published 8 min read By Current Intel engineering team

Short answer

The flood light almost certainly extinguished in the voltage dip the motor start drove through the shared upstream supply, and the delayed return is the hot lamp waiting to restrike. Confirm it with a power-quality recorder on the lighting circuit during a controlled start, then hold the dip above the ballast's band by cutting start kVA, stiffening the shared source or riding through at the fixture.

On this page
  1. The arc goes out, the lamp waits
  2. Causes to rule out first
  3. Record the event before changing anything
  4. Checking a recorded dip on the 220 V flood light circuit
  5. Countermeasures that keep the lamp lit
  6. The retest that proves the fix
  7. Questions asked

When a large motor starts and a sodium flood light on another switchboard goes dark for about two minutes, test the motor-start voltage dip first. A high-pressure sodium lamp that loses its arc cannot restrike until it cools, roughly 1 to 2 minutes, which is exactly the reported outage. Separate switchboards do not mean separate supplies: any transformer, generator or feeder shared upstream of both boards carries the dip into the lighting circuit. Record the lighting-circuit voltage during a controlled start before blaming the ballast, the generator or either board.

The arc goes out, the lamp waits #

An across-the-line start pulls several times rated current, and that current through the shared source impedance drops the voltage on every circuit behind it. The motor is fed from the main board and the flood light from the emergency lighting board, but the dip crosses between them at the first common point — the same coupling behind why a 4.16 kV motor start dips a 120 V branch to 109 V.

High-pressure sodium lamps are sensitive to voltage dips. When the ballast input falls out of its operating band the arc is lost, and the ignitor's 2500 V to 3000 V pulse cannot relight a hot lamp, because the arc tube pressure is too high until it cools. That cooling takes about 1 to 2 minutes, so the lamp stays dark about two minutes and then returns with no human intervention.

Timing sorts the causes: a lamp that recovers the instant voltage returns only flickered; one that stays dark through the restrike wait lost its arc; one dark for many minutes is behaving like metal halide.

Causes to rule out first #

These look-alikes produce the same symptom, and most take an hour to clear:

  • A tripped breaker or blown fuse at the lighting board. A trip needs a reset, so a lamp that returned by itself was not on a tripped circuit. Check the flags and relay targets anyway.
  • A contactor or photocell relay in the lighting circuit. A coil that drops out below its hold-in voltage gives the same signature. Record at the fixture supply as well as the board feeder, or simply watch the contactor during the start.
  • Tired ballast parts. A weak capacitor or worn ignitor makes the lamp dip-sensitive even with the supply in band; flood light ballast capacitor function and failure causes covers what to measure once the fixture is open.
  • An aging lamp. A high-pressure sodium lamp near end of life cycles off and on by itself. If outages also happen with no motor running, the lamp is due.
  • A loose connection in the lighting circuit. It can flicker a lamp under load but cannot deliver a clean, repeatable return after every start. Inspect the terminations while the fixture is open.

Record the event before changing anything #

Open the lighting board under the site's lockout procedure — de-energize, lock, test for absence of voltage, fit the leads, close the panel, then re-energize — wearing the PPE that NFPA 70E, 2024 edition, the workplace electrical-safety standard, calls for on your arc-flash assessment for that task.

  • Instrument: a power-quality recorder to IEC 61000-4-30 (2015), Class A or S, the power-quality measurement-methods standard. A handheld multimeter misses the event entirely. Set sag capture to the IEEE 1159 (2019) window, the monitoring practice's definition of a sag: rms voltage falling to between 0.1 and 0.9 of nominal for half a cycle to a minute.
  • Lighting side: the 220 V circuit at the emergency lighting board, and the fixture supply too if a contactor sits between them.
  • Motor side: read the start current and motor-bus dip from existing metering or protection event records rather than opening medium-voltage gear, and note the timestamps.
  • A camera on the fixture, time-synced to the recorder, settles what the lamp actually did.
  • Several starts, plus a baseline capture with no motor running.
  • The one-line: mark where the two boards first share supply. If a generator carries the plant, its impedance and excitation response set much of the dip; generator swing and voltage control in motor start studies covers that response.
  • The board's own rules: where this is a vessel's emergency system, 46 CFR Part 112, Emergency Lighting and Power Systems, applies, and one of its supply rules keeps the storage battery's initial voltage no more than 5 percent above the standard system voltage when feeding emergency lighting loads; confirm applicability with the authority having jurisdiction.

Checking a recorded dip on the 220 V flood light circuit #

The reported case, with example recorder readings in place of measurements — replace them with your own capture.

Inputs:

  • Lighting circuit nominal: 220 V, from the reported case.
  • Motor: 6.6 kV, started across the line, from the reported case.
  • Recorder capture, example: minimum 176 V for 150 ms at the lighting board; lamp dark at the same timestamp and back about two minutes later.
  • Ballast sensitivity: the fixture documentation warns that a 20 V drop on a 240 V circuit can cause problems, here scaled in proportion to this circuit.

The rule in words: the lamp holds while the ballast input stays inside its band; below the band the arc is lost and cannot restrike hot. The screening floor is the nominal voltage minus that band.

The arithmetic:

  • Band: 20 V ÷ 240 V = 0.083, or 8.3 percent of nominal.
  • Floor: 220 V − (0.083 × 220 V) = 220 V − 18.3 V = 201.7 V, call it 202 V.
  • Recorded depth: 220 V − 176 V = 44 V; 44 V ÷ 220 V = 0.20, a 20 percent dip.
  • Margin: 176 V sits 26 V below the floor, well outside the band.
  • Duration: 150 ms is inside the 0 ms to 265 ms response window observed in street-lighting dip tests, so the lamp reacts within the dip.
  • Recovery: voltage returns within the start, but the hot lamp restrikes only after cooling, about 1 to 2 minutes, matching the recorded return.

Result: the dip is deep enough and long enough to extinguish this lamp, and the timing is the restrike signature. The supply dip is the cause; the fixture is healthy enough to relight.

The decision: every start that pulls this circuit below 202 V will drop this lamp, so choose a countermeasure that holds the recorded minimum above that floor — and treat the floor as a screening number, replaced by the band the ballast datasheet states when it states one. If a capture ever stays above the floor while the lamp goes dark, stop looking at supply and move to the fixture circuit: contactor coil, connections, ballast, ignitor.

Countermeasures that keep the lamp lit #

In order of what holds the light through the start:

  1. Cut the start kVA. The dip scales with the start kVA while that stays small against the short-circuit capacity at the shared point. In the example the dip must fall from 44 V to under 18.3 V, so the start kVA must come down to 18.3 ÷ 44 = 0.42, about 42 percent of today's value. Halving it with a soft starter leaves a 10 percent dip — 220 V − 22 V = 198 V — still below the floor, so at this depth a soft starter alone does not hold the lamp. It also changes little where a stiff utility bus sets the dip, as why a soft starter barely improves utility bus voltage dip shows; it earns its place where plant transformers or a generator set the shared impedance.
  2. Raise the short-circuit capacity at the shared point: a larger or parallel transformer, or a larger generator. The dip scales inversely with it, so the example's 20 percent must come down to 8.3 percent — the capacity needs about 44 ÷ 18.3 = 2.4 times today's. Work the numbers with the method in motor starting voltage drop with utility short-circuit capacity.
  3. Ride through at the fixture: a ferroresonant constant-voltage transformer or a UPS ahead of the ballast. Specify an input window that covers the recorded minimum — 176 V is 80 percent of nominal in the example — output VA at least the ballast input VA on the nameplate, and documentation for the ballast type, since reactor, regulator and auto-regulator circuits respond differently. An electronic ballast drives the lamp at 100 Hz to 400 Hz and draws rectifier current, so the unit must be rated for non-linear loads. For a single flood light this is the smallest change that works.
  4. Change the fixture: a sodium flood light with an auxiliary filament backup lights during the restrike wait, or an LED flood with a driver whose published ride-through time at least covers the recorded dip, 150 ms plus margin in the example.
  5. What not to do: a new lamp or ballast faces the same dip; separate switchboards are not separate supplies; and where other loads share the dipped path, fix the dip rather than only the fixture — the flood light is just the first load to complain.

The retest that proves the fix #

Repeat the same start with the recorder running. Pass is two things on one capture: the lamp stays lit through the whole start, and — for a supply-side fix — the recorded minimum stays above 202 V. Log three consecutive clean starts, then leave the recorder on the circuit for a week; a heavier load or a colder motor can produce a deeper start, and the floor tells you the margin left.

Questions asked

Does the voltage dip damage the sodium lamp or ballast?

One low-voltage event does not by itself harm the lamp or the ballast. The wear is cumulative: every extinction forces a hot restart, and repeated failed restarts strain the ballast and age the ignitor. A fixture that goes dark at each start should be corrected rather than reset, and a ballast that can no longer start the lamp at all is due for replacement, not another lamp.

How long would a metal halide flood light stay dark after the same dip?

Longer. Metal halide hot restrike commonly takes 5 minutes or longer, against about 1 to 2 minutes for high-pressure sodium, because its arc tube must cool further before the ignitor can relight it. If a fixture returns after many minutes rather than a couple, check the lamp type before quoting a restrike time or choosing a workaround.

Will swapping in an LED flood light solve it?

Only with the right driver. LED drivers vary widely in ride-through: street-lighting dip tests recorded response delays anywhere between 0 ms and 265 ms, so some lamps drop out almost instantly. Specify a driver whose datasheet states a ride-through or hold-up time at least as long as your recorded dip, then prove it with the same recorder test after the swap. A driver with no published ride-through figure should be assumed to drop out.

Does upsizing the lighting feeder or breaker help?

No. The dip is generated upstream of both boards and merely passes through; the lighting circuit's own voltage drop is small because its load is small, so a bigger feeder or breaker changes nothing the lamp sees. Put the effort into the start kVA, the shared transformer or generator, or ride-through at the fixture. Only a feeder undersized for the lighting load is worth changing, and that shows as permanently low voltage, not an outage that heals itself.

Keep reading

  • Troubleshooting

    Why a 4.16 kV motor start dips a 120 V branch to 109 V

    The one-second dip to 109 V on the branch is the medium-voltage motor's starting current flowing through impedance shared with that branch: about 8 V, or 6.8%, well inside the 15% starting-drop practice but low enough to trip one sensitive device. Capture the dip at the load, fix it at the motor start or at the device, and leave the utility tap alone - raising the bus to 4368 V only lifts the floor to about 114 V without removing the dip.

    Power quality and harmonics

  • Troubleshooting

    Why power factor capacitors don't fix motor starting sag

    No — panel power factor capacitors will not fix motor-start dimming. They cancel steady-state reactive current; the dim is a locked-rotor surge several times full-load through the source and feeder impedance for about a second. Cut the impedance or cut the starting current: fix the feeder, strengthen the supply, or soft-start with a VFD or starter where three phase allows.

    Power quality and harmonics

  • Troubleshooting

    Why a soft starter barely improves utility bus voltage dip

    On a fixed-impedance screening calculation, cutting starting current from 600% to 400% scales a 10% utility-bus dip to about 6.7%, so a modeled 2-point gain signals a study-method or data problem, not a soft-starter fault. A 10% dip on a shared medium-voltage feed also exceeds the roughly 5% planning ceiling utilities apply at the point of common coupling. Keep the starter for the motor and the mechanical train; fix the study, then the supply, before ruling the starter out.

    Motors and motor starters