Explainer
Why a soft starter fits a hydraulic lift but not a traction lift
Short answer
No for a traction lift, yes for a hydraulic lift's pump motor. A traction machine works in all four quadrants and needs speed control, feedback and a path for regenerated energy, none of which a voltage ramp gives. A hydraulic lift's pump runs at line speed with the valves setting car speed, so a soft starter fits once starts per hour and motor start duty are checked.

On this page
- Why a traction lift rules a soft starter out
- The four quadrants a traction machine works in
- Where the soft starter fits: the hydraulic pump motor
- The three checks that decide the hydraulic case
- Worked example: the speed a soft starter can give a 4-pole pump motor on 50 Hz
- Setting it up and proving it on the pump
- What the starter does not replace
- Questions asked
No for a traction lift, yes for the pump motor of a hydraulic lift, and the dividing line is what sets the car's speed. A traction machine's car moves at the speed of its motor, and a soft starter cannot set motor speed: it ramps terminal voltage, then the motor runs wherever line frequency and load put it. A hydraulic lift's car speed comes from its valve block, so its pump motor only has to start smoothly and run at line speed — exactly a soft starter's job, once starts per hour, motor start duty and thermal limits are checked. Here is the quadrant picture, the hydraulic case, and the arithmetic that shows why the speed ceiling decides the answer.
Why a traction lift rules a soft starter out #
A soft starter is a thyristor voltage controller. During the ramp it raises motor terminal voltage from an initial value to full line voltage over a set time; after the ramp the motor is effectively across the line, and its shaft settles just under the speed that supply frequency and pole count fix. That is the whole of its authority: no frequency control, no encoder input, no DC link, no brake chopper, no regenerative front end.
A traction lift needs all of those. Its motor accelerates the car, holds contract speed, decelerates to a leveling crawl and stops on a landing — a profile built on speed feedback — and over part of every round trip the load overhauls the machine, which must then hold speed while energy flows back out of the motor. A device that only shapes voltage can do none of this. It is the same ceiling behind why a soft starter cannot reduce a pump's running speed: frequency unchanged means running speed unchanged.
The four quadrants a traction machine works in #
The motor of a traction lift works in all four quadrants — forward motoring, forward braking, reverse motoring and reverse braking — and the quadrant follows from which side of the rope system is heavier:
| Travel | Heavier side | Motor duty | Demanded of the controller |
|---|---|---|---|
| Up | Car | Motoring | Controlled torque, speed holding |
| Down | Car | Braking, regenerating | Held speed, path for returned energy |
| Up | Counterweight | Braking, regenerating | Held speed, path for returned energy |
| Down | Counterweight | Motoring | Controlled torque, speed holding |
The machine regenerates whenever the heavier side is descending. A drive with a speed loop and feedback covers all four rows; a soft starter covers none of them beyond smoothing the first start.
Where the soft starter fits: the hydraulic pump motor #
In a hydraulic lift the pump motor only moves oil. On up travel the pump runs at line speed and the up valve sets how fast the car rises; on down travel gravity pushes oil out of the cylinder through the down valve with the motor off. Nothing asks the motor for a second speed, holding torque or regeneration: the duty is start smoothly, run at one speed, stop, repeat.
That is an established soft-start application, not a stretch — one manufacturer lists a soft starter series built specifically for hydraulic elevators, cULus listed (ABB's ELV-X series is the documented example). The payoff is the classic one: a start current well under the locked-rotor inrush an across-the-line start exposes the motor and feeder to, less mechanical shock in the pump coupling, and a gentler pressure build at every up call.
The three checks that decide the hydraulic case #
- Starts per hour. A lift starts its pump at every up call, far more often than the fan or pump duty these starters are usually sized on, and every ramp heats the thyristors. Count the pump starts your busiest hour produces and hold that figure against the starter's start duty and the motor's start rating — what NEMA MG-1 start clauses mean for motor start inhibits shows how to read the motor side. Over the limit, take a larger frame or a different arrangement; a longer ramp only moves the heat around.
- Bypass. Fit a bypass contactor, internal or external, so the thyristors carry current only during the ramp and the starter stays cool through the long runs between starts.
- Motor start method. Confirm the motor accepts soft starting with the ramp time you intend — especially pump motors submerged inside the oil power unit.
Worked example: the speed a soft starter can give a 4-pole pump motor on 50 Hz #
Inputs. Supply frequency: 50 Hz, the supply in the case in question. Motor pole count: 4, the example machine; your nameplate gives yours, directly or through the full-load speed.
Rule. An induction motor's synchronous speed equals 120 times the line frequency divided by the pole count, where the 120 is 60 seconds per minute times the two poles of a pole pair. A soft starter changes terminal voltage only, so after the ramp the motor can only settle just below that speed, at the slip the load sets.
Arithmetic.
- Synchronous speed = (120 × 50 Hz) ÷ 4 poles = 1500 r/min
- Cross-checks: 2 poles on the same supply gives (120 × 50) ÷ 2 = 3000 r/min; the same 4-pole machine on 60 Hz gives (120 × 60) ÷ 4 = 1800 r/min
Result. The example motor runs just under 1500 r/min and no starter setting moves that number: pole count and frequency set it, and the nameplate confirms it as the printed full-load speed.
Decision. If the specification needs that single line speed and nothing else — a pump pushing oil while valves run the car — the soft starter fits. The moment the job calls for a second motor speed, a leveling or inspection crawl, the soft starter is out and the answer is a drive. One speed, soft starter; two speeds, drive.
Setting it up and proving it on the pump #
Lock out the pump feeder and test for absence of voltage before opening the starter enclosure or the motor terminal box; settings are entered from the keypad with the cover closed.
- Take the nameplate — rated current, voltage, pole count or full-load speed, duty — and enter the rated current into the starter's motor data.
- Choose the control mode for a pump start; which soft starter control mode fits each load type walks through that choice.
- Set a short ramp and an initial voltage just high enough to break the pump away, then lengthen the ramp only until pressure builds without a bang.
- Set current limit and motor overload from the nameplate — the 3RW55 soft starter control wiring and overload setup shows that work for one starter series.
- Wire the starter's fault and ready contacts into the lift controller so a trip blocks further car calls until the fault is cleared.
- Prove it: run empty, then at rated load. Current, read with a clamp meter or the starter's own readout, should rise smoothly to a peak below the across-the-line value and fall to running current at ramp end; the bypass should close at ramp end and stay closed; the worst traffic pattern should bring no thermal trip; and the car should leave the floor without a jolt — any jerk left after the ramp points at valve timing, not the starter.
What the starter does not replace #
The soft stop is not a brake: lowering voltage produces no holding torque and cannot arrest an overhauling load. On the hydraulic unit the stop belongs to the valve sequence, and on every lift the machine brake, car safety gear and overspeed protection stay exactly as the governing lift code requires — ASME A17.1/CSA B44 (2019 edition with its later addenda), which covers the construction, operation, testing and maintenance of elevators in North America, or EN 81-20 (2014 edition with its 2020 amendment), the European safety rules for the construction and installation of lifts. Confirm the edition and amendments your authority having jurisdiction enforces, and put any change to the lift controller through the lift inspector before the unit returns to service.
Questions asked
Does a soft starter save energy on a hydraulic lift?
No. Once the ramp ends, the bypass contactor carries the current and the motor runs exactly as it would across the line, so energy per trip is unchanged. The gains are a lower start current, a smaller voltage dip on the feeder and less mechanical shock in the pump coupling, not kilowatt-hours.
How do I count starts per hour for a hydraulic lift?
Each up call is exactly one pump start and each down call is none, so the busiest hour of up travels gives the base figure. Add the rest: inspection runs, service operation and any pump jogs the control sequence makes to re-level the car at a floor. Check that total against both the starter's start duty and the motor's start rating.
Can the soft stop replace the valve sequence?
No. The car's motion is hydraulic, so the valve block decides how it stops, and on most units the motor is simply switched off while the valves close. Add a soft stop only where the pump is stopped against pressure and the sequence tolerates a slower stop, and verify the result on the machine against the valve timing.
Why could older traction lifts run without a drive?
Simple geared machines used two-speed pole-changing motors: a high-speed winding for travel, a low-speed winding for the approach to the floor, and the mechanical brake to finish the stop. Both speeds come from the motor's windings and their contactors, never from the starter, and ride quality and landing accuracy are what that arrangement trades away against a drive.