Why a Z axis trips motor overload on rapid traverse
Short answer
A Z axis that throws Motor Overload only on rapid traverse is losing torque in proportion to commanded speed, or running servo gains that never matched a swapped motor. Read the axis lag display: 0 ±1 count at standstill, symmetric both directions, linear with jog rate; a lag jump past the speed step sends you to brushes, brake, cable or retune.

On this page
- Why does Motor Overload fire only on rapid Z moves?
- How do you read the axis lag display?
- How much lag is too much at fast jog?
- Was the motor swapped without a servo tune?
- Which hardware faults make a servo lose torque at speed?
- Why does E-stop stay on when Reset will not clear it?
- What order should the tests run in, and what is safe to open?
- Questions asked
A Z axis that throws Motor Overload only during rapid traverse, while X and Y hold position at every feedrate, is losing torque in proportion to commanded speed or running servo gains that were never matched to the motor now installed. The fastest test costs nothing: turn on the axis lag display and read it at standstill, in both jog directions and at three jog rates. Standstill lag should read 0 ±1 count, magnitudes should match plus and minus, and lag should scale linearly with jog rate. When fast-jog lag grows faster than the speed step, work down the differential below: brushes and commutator, brake release, the flexing motor cable, a retune for a swapped motor, or a hardware overload or fuse behind an E-stop that will not clear.
Why does Motor Overload fire only on rapid Z moves? #
Because the defect is velocity-proportional: the axis only exceeds its current or following-error limit when commanded speed outruns available torque, and a fault that spares X and Y at every feedrate cannot be a control-wide power, logic or overload-setting problem.
Two symptom patterns travel together on these brushed-DC servo machines, and they are one defect at two severities. The hard trip: rapid Z in either direction throws Motor Overload and drops the machine into E-stop, Reset clears it, and the next rapid trips it again. The soft failure: Z moves above roughly 50 ipm (inches per minute) drift — a peck-drill cycle with fast Z retract overshoots the top Z position slightly every cycle until the drill no longer reaches the material, and cavity-mill toolpaths with short internal Z rapids show the same creep. Z motion below about 20 ipm shows none.
That pattern is the discriminator: a control-wide power or logic fault would not spare X and Y, and a constant mechanical bind would drag at every speed rather than growing with commanded velocity. Whatever is wrong lives in the Z chain and scales with speed — torque loss at speed, or a loop never matched to the motor.
How do you read the axis lag display? #
Standstill lag must read 0 ±1 count, the magnitude must match jogging plus and minus, and lag must scale linearly with jog rate — three checks that separate a loop or torque problem from a mechanical bind or a control-wide fault in minutes, with no instruments.
This class of control turns the display on in the setup screens; the position page then shows lag alongside position. Read it three ways:
- At standstill: anything outside 0 ±1 count means the drive offset or balance is off, or the loop is not closing.
- Jogging plus and minus at the same rate: magnitudes must match, differing only in sign. Asymmetry points at drive balance, a dragging way or gib preload, or a vertical axis without proper counterbalance.
- At three jog rates, slow to fast: record the lag at each step. In a proportional position loop, steady-state following error scales linearly with commanded velocity, so the lag ratio between two steps should match the speed ratio between them.
How much lag is too much at fast jog? #
Judge lag by ratio against speed ratio: this failing Z axis read 0.002 in at slow jog, 0.02 in at medium and 0.37 in at fast — a clean 10:1 slow-to-medium step, then an 18:1 jump that is only linear if the fast rate is 18 times the medium rate.
| Jog step | Reported lag (in) | Lag ratio to next slower step |
|---|---|---|
| Slow | 0.002 | — |
| Medium | 0.02 | 10:1 |
| Fast | 0.37 | 18:1 |
These are reported measurements from one machine showing this fault, not a specification; record your own before judging. The slow-to-medium step is consistent with a 10:1 jog-rate step on a healthy linear loop. The medium-to-fast step is the tell: read the commanded rate for each jog step from the control and divide. A speed ratio smaller than the lag ratio means the axis is losing torque as speed rises, and that excess lag is the fault itself — the drive sees the growing position error and shuts the axis down on Motor Overload. Ratios that stay clean while lag sits uniformly high point instead to gains set for a different motor, which is the retune case below.
Worked example, position-loop gain from lag. In a proportional position loop, steady-state following error (in) equals feedrate (ipm) divided by the position-loop gain Kv (ipm per in), so Kv = feedrate / following error. Inputs: a fast jog rate of 200 ipm — an example value, read the real one from the control — and 0.37 in of fast-jog lag. Kv = 200 / 0.37, which is about 540 ipm per in, or roughly 0.54 ipm of feed per 0.001 in of lag. Treat the result as an estimate of loop stiffness under the gain definition in the control's servo documentation; some controls quote the gain in other units, so check that definition before comparing. The figure means something only next to X and Y measured the same way at the same rates: X and Y behaved correctly on this machine, so they are the reference, and a materially lower figure on Z puts the defect in the Z loop or Z motor, not the CNC.
Was the motor swapped without a servo tune? #
If the Z motor is newer than its drive — the rebuilt 12 A brushed-DC replacement on this machine had spotless brushes — suspect a drive never retuned for the motor now installed: mismatched gains give speed-proportional lag with no heating, no noise and no mechanical drag.
A tune means resetting the drive's gains and balance against the installed motor, in-house through the control's servo setup screens on controls that expose them — not a send-away rebuild. The tune gain exists to minimize following error during the constant-velocity part of a move; when the motor changes — a different torque constant, tachometer or encoder sensitivity, rotor inertia — the old gains leave steady-state lag high at speed. The signature here was exactly that: lag high but linear across the rates, symmetric plus and minus, no abnormal motor heating, no mechanical noise, and replacement brushes that looked brand new. If the cable and brake checks pass and lag stays symmetric and linear across all three rates but sits uniformly high, retune before buying parts — the fault is in the gains, not the hardware.
Which hardware faults make a servo lose torque at speed? #
Three hardware defects produce the same velocity-proportional lag: worn or carbon-fouled brushes that lose contact as armature speed rises, a brake solenoid that never fully releases and makes the motor fight its own brake, and a work-hardened conductor in the vertically flexing motor cable.
| Cause | Symptom signature | First check |
|---|---|---|
| Worn or carbon-fouled brushes, carbon dust bridging commutator segments | Torque falls off as speed rises; lag grows with velocity; trip on rapid only | Pull the motor: brush length, freedom in the holder, spring pressure, seating arc; blow out the carbon dust |
| Failed brake solenoid holding the brake on | Motor fights an applied brake, current pegs, overload trips; seen on spindle brakes as well as axis brakes | Command motion and verify the solenoid shifts and air pressure or release voltage is present |
| Broken or chafed conductor in the Z motor or encoder flex cable | Intermittent; position- or direction-dependent; can trip mid-move | Ring out each conductor end-to-end while flexing the cable through full travel |
| Servo loop never retuned | Lag high but linear and symmetric; no heat, no noise | Lag sweep at three rates; compare the gain with X and Y |
| Shorted axis control module | Fault follows the module when cards are swapped | Swap the Z module with X or Y and see whether the fault moves |
Two of these hide well. Brushes that look clean can still be short, hung in a fouled holder or seated over a fraction of the commutator, so judge by length, spring pressure and seating arc rather than shine, and read the commutator for even wear, no burned bars and no copper dragged across the mica while the motor is out. The flexing cable fails inside the jacket: repeated vertical travel work-hardens the conductors, so ring the cable while flexing it through full travel and treat any resistance blip as a failure, not just a dead open.
A trip keyed to temperature rather than speed — fine cold, tripping after warm-up — has a different diagnosis; that pattern is covered in why a servo axis trips motor overload only on cold start.
Why does E-stop stay on when Reset will not clear it? #
When E-stop will not clear at Reset, the control is reporting a hardware contact, not an internal following-error fault: look for a tripped manually reset three-phase overload on the spindle or axis feeders, a blown control-transformer or axis-supply fuse, or a shorted axis module.
Reset clears control-generated faults; a tripped hardware device holds the interlock until it is physically reset. Find the manually reset three-phase overloads on the spindle and axis feeders, reset the one that tripped, and note which — the tripped device names the loaded circuit. Check control-transformer and axis-supply fuses against the machine schematic: a partially open fuse on one leg produces load-dependent faults that mimic servo trouble.
The ladder settles which alarm you are looking at. With the I/O list and schematics in hand, monitor the overload input while the fault is present — a held contact means the hardware device, an internally generated following-error fault means the loop. That three-phase overload is a thermal device with a trip class and curve, described in reading overload relay trip classes and curves; one that resets and trips again right away points at real load current, as why a thermal overload trips again right after reset explains. A shorted axis control module reproduces the entire picture on an otherwise healthy axis — swap the Z module with X or Y and watch whether the fault follows the card.
What order should the tests run in, and what is safe to open? #
Order the work as: read the lag display with the covers on, then lock out the main disconnect and verify zero volts on the amplifier DC bus before touching motor leads, overloads or modules — and support the Z head or bottom it out before the motor comes out.
Servo amplifier DC buses and three-phase feeders stay energized behind the E-stop contactor on many of these cabinets, so treat cabinet work as planned energized-electrical work under NFPA 70E, 2024 edition, which covers lockout, verifying absence of voltage and protective equipment; confirm the details with your authority having jurisdiction and the machine documentation.
- Reproduce the pattern: rapid Z in both directions, X and Y clean at all speeds.
- Turn on the lag display in the setup screens; record standstill lag, plus and minus symmetry, and lag at three jog rates.
- Compute the lag ratios and the position-loop gain from the worked example above; compare Z against X and Y measured the same way.
- Lag ratios clean but lag uniformly high at every rate: retune the servo gains to the installed motor through the setup screens, then recheck the sweep.
- The fast-jog ratio outrunning the speed ratio: pull the motor with the head supported or bottomed out, and inspect brushes, commutator and carbon dust.
- Ring out every conductor in the Z motor and encoder cable end-to-end through full travel; re-terminate or replace on any resistance blip.
- Command motion and verify brake release for as long as the axis moves: solenoid shifted, air pressure or release voltage present.
- Swap the Z axis control module with X or Y; a fault that follows the module is a failed module.
- E-stop that Reset will not clear: reset the tripped three-phase overload, check control and axis-supply fuses per the schematic, and confirm the hardware contact in the ladder.
The decision for each case: clean ratios with uniformly high lag end in a retune, not parts. A lag step that outruns the speed step ends in the motor — brushes and commutator first, then brake release, then the flexing cable. An E-stop that Reset cannot clear ends at the hardware: the tripped three-phase overload, a blown fuse or a shorted axis module, and the ladder names which.
Questions asked
Do I need special instruments for the lag test?
No. The lag display is built into the control's setup screens and reads out on the position page; the only tools needed beyond it are a multimeter for the cable ring-out and the brake voltage check, plus an insulated screwdriver for the brush caps. Current probes and oscilloscopes help later, but the lag sweep localizes the fault without them.
Can I just turn the rapid rate down and keep running?
Lowering the rapid rate cuts lag in proportion and will stop the trips, but it masks a real torque or gain defect and leaves the axis one parameter change away from tripping again. Use a reduced rate only as a temporary production measure while the lag sweep and the brush, brake and cable checks run.
Does a servo tune mean sending the motor out for overhaul?
Tuning is drive-side setup at the control's servo screens, not motor surgery. Send the motor out only if the inspection fails it: short brushes, burned commutator bars, a dragging brake or a bound holder — everything else is set at the control.
Why does Z position creep appear only on peck-drill cycles?
Peck cycles pack many short Z rapids into one program: every retract in the speed range where lag is large ends with a small position discrepancy, and repeating it dozens of times accumulates the drift until the drill no longer reaches the material. Single moves hide the same error because one cycle's discrepancy is too small to notice.
The brushes looked clean — can they still be the cause?
Yes. Appearance says nothing about length, spring pressure or freedom in the holder: a brush can look spotless and still be too short, hung in a carbon-fouled holder, or seated over only part of the commutator. Measure the remaining length against the wear limit marked on the holder or stated by the brush maker, and check the commutator for burned bars before clearing the motor.