Why an inside delta soft starter current rating is higher

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

Inside delta, a soft starter sits in series with the motor windings and carries line current divided by the square root of three, about 58 percent, so the same frame is applied at a higher line current. One published range runs 30 to 1050 A in line and up to 1810 A inside delta. Confirm the as-built connection before matching any starter rating to motor full-load current.

On this page
  1. Why does a soft starter inside delta carry less current than the line?
  2. How much less current does an inside delta starter carry?
  3. What does that buy you on a real starter range?
  4. What starter does a 100 A delta motor need?
  5. Which standard defines soft starter ratings?
  6. When is wiring a soft starter inside delta worth it?
  7. What must you confirm before matching the rating to the motor?
  8. How do you set overload protection inside delta?
  9. Questions asked

Wire a soft starter inside the delta and the same frame can serve a motor that draws about 72 percent more line current than its in-line rating allows. The reason is topology, not a second rating scale: inside delta, the starter's thyristors sit in series with the windings instead of in the supply lines, so each one carries winding current, which is line current divided by the square root of three, roughly 58 percent. One starter family publishes the split openly: 30 to 1050 A in line, up to 1810 A inside delta, a published ratio of 1.72 against the mathematical 1.732. The decision follows from that number: before you compare any soft starter rating to a motor's full-load current, read the as-built wiring diagram and establish whether the unit is in line or inside delta. Comparing an in-line rating to an inside-delta installation, or the reverse, sizes the starter wrong in both directions.

Why does a soft starter inside delta carry less current than the line? #

Inside delta, the starter sits in series with a winding, not in the supply line, so it carries winding current; the motor still draws its normal line current from the feeder, but the thyristors never see it.

In an in-line connection, each supply line passes through one leg of the starter on its way to the motor terminal, so all three legs carry full line current for the whole start and run. Inside delta, the three supply lines land on the corners of the delta and each starter leg is inserted in series with one winding branch. The feeder still delivers the same line current it always did; the only element that sees less is the starter itself. That is why the frame can be smaller without changing anything upstream, and why the connection cannot be judged from the starter's rating alone.

How much less current does an inside delta starter carry? #

A three-phase delta connection splits the line current between two windings, so each winding, and each starter leg wired in series with one, carries line current divided by the square root of three, about 58 percent.

For balanced windings the phasor relation is I_line = √3 × I_winding, so I_winding = I_line ÷ 1.732 = 0.577 × I_line. The line conductor feeds two windings whose currents are equal in magnitude and 60 degrees apart in phase; the feeder carries the vector sum of the two, not their arithmetic sum, and that geometric factor is the square root of three. The ratio is fixed by the delta connection itself. Voltage, horsepower and manufacturer do not move it, and it holds during the start and while running, because the topology, not the control method, sets what the thyristor path carries.

What does that buy you on a real starter range? #

The published ratings make the factor explicit: one soft starter family lists 30 to 1050 A in line and up to 1810 A inside delta, and 1050 multiplied by 1.732 gives 1819 A, which rounds to the published inside-delta figure.

The product data for the ABB PST(B) range states a rated operational current of 30 to 1050 A, up to 1810 A inside delta, an operational voltage of 208–690 V AC, and support for both in-line and inside-delta connection. The arithmetic checks out across the top of the range, but treat the factor as a sanity check, not a selection rule: each frame carries its own published inside-delta rating, derived from its thermal design and testing, so read the figure for the frame in front of you instead of extrapolating. How a starter's current range maps onto its power structure is the same question in another form, covered in matching a soft starter current range to its power structure.

What starter does a 100 A delta motor need? #

For a delta-connected motor with a 100 A nameplate line current, an inside delta starter carries 100 divided by 1.732, about 58 A, so a 58 A frame inside delta does what an in-line installation needs a 100 A frame for.

Worked example, with illustrative inputs — check your own nameplate and the manufacturer's selection tables:

  • Motor: 480 V, three phase, delta-rated at supply voltage, nameplate full-load current 100 A, which is line current.
  • In line: each starter leg carries the full 100 A, so the frame must be rated at least 100 A in line.
  • Inside delta: winding current = 100 A ÷ 1.732 = 57.7 A, so a frame rated 58 A inside delta suffices for the same motor.
  • Upstream: the feeder conductors, branch protection and disconnect see 100 A of line current in either connection, so none of them change.

The nameplate figure you start from is line current even though the delta windings themselves carry less; that distinction is set out in why motor nameplate current is line current, not winding current.

Which standard defines soft starter ratings? #

IEC 60947-4-2 is the product standard for semiconductor motor controllers, soft starters included, and it defines the rated operational current manufacturers publish; confirm the edition and any local amendments with the authority having jurisdiction and the equipment documentation.

The standard's ratings are conditional, and manufacturers state the conditions next to the numbers. One reduced-voltage starter catalog, for example, declares its power ratings according to IEC 60947-4-2 for a 10 second ramp, one start per hour, a 300 percent current limit and a 40 °C ambient. Change any of those inputs — a 30 second ramp on a high-inertia fan, six starts an hour, a panel running at 50 °C — and the usable rating for that frame is lower than the table value. So the comparison that matters is not just starter rating versus motor current, but starter rating, under your duty cycle and ambient, versus motor current, in the connection actually wired.

When is wiring a soft starter inside delta worth it? #

Inside delta pays off when the motor runs delta permanently and the line current lands just above an available in-line frame: the connection cuts the starter's current duty to a bit over half and can keep you one frame size down.

The connection needs a motor rated for full voltage in delta at the supply voltage, with all six winding leads brought out and accessible; if you are unsure what the lead bundle in front of you means, what six leads and two plate voltages tell you about wiring walks through that identification. The motor must then run delta permanently, which rules the connection out wherever a wye-delta changeover or wye running at light load shares the same starter. The saving reaches the bypass contactor too: if the starter has a built-in bypass wired inside delta, it also carries winding current rather than line current. Nothing upstream shrinks, so inside delta is a frame-sizing and panel-space decision, not a feeder decision.

What must you confirm before matching the rating to the motor? #

Before comparing any rating to motor full-load current, read the as-built wiring and confirm the connection, because the same nameplate current means different starter duty in line and inside delta.

De-energize, lock out and test for absence of voltage before opening the starter's terminal covers; NFPA 70E, the National Fire Protection Association's electrical work practice standard, 2024 edition, governs that kind of work, and requirements differ by country and local amendment, so confirm them with the authority having jurisdiction. With the covers off or the drawings in hand, check three things: which terminals the supply lines land on, which terminals the motor leads land on, and where the bypass contactor sits, because the rating basis follows the bypass too. Then check the starter nameplate for which current basis its rating was published against, and confirm the control supply separately — a correct motor voltage says nothing about the control circuit voltage.

How do you set overload protection inside delta? #

Set the starter's overload function on the current basis its connection creates: inside delta the starter measures winding current, about 58 percent of the nameplate line current, so the setting follows the manufacturer's inside-delta instructions, not the nameplate value entered directly.

An electronic overload in the starter tracks the current through its own power path, so inside delta it sees winding current and an in-line starter sees line current for the same motor. Follow the manufacturer's setting procedure for the installed connection. A separate thermal overload relay mounted in the supply lines is a different case: it sits outside the delta and always sees line current, so it is set from the nameplate full-load current, the method described in setting overload relays from motor nameplate full-load current. After setup, verify under real duty: watch the acceleration and running current on the starter's display or analog output and confirm the trip behaves as selected.

The decision, both cases: an in-line starter is matched against the nameplate line current; an inside-delta starter is matched against that line current divided by 1.732, with the overload set on the same basis and the upstream gear sized on the line current either way. Verify the finished installation against the starter's own selection data before the first start.

Questions asked

Does inside delta wiring reduce the current the supply delivers?

No. The motor still draws its full line current from the feeder, so the feeder conductors, disconnect, branch protection and any line contactor are sized on line current regardless of where the starter sits. Only the starter's own thyristors, and its bypass contactor if that is also wired inside delta, are relieved, because they carry winding current instead.

Can every motor be wired inside delta?

Only a motor rated for full voltage in delta at your supply voltage, with all six leads accessible, can use the connection. It also has to run delta permanently, so the option disappears where a wye-delta changeover, wye running at light load, or a shared starting method forces the windings into another configuration.

Does the same inside delta trick work with a VFD?

No. A variable frequency drive must sit in the supply lines, because it synthesizes its own output voltage and current and its rating is defined against full line current. Inside delta is a soft-starter and electromechanical-starter connection, not a drive connection.

Why is the inside delta rating not exactly the in-line rating times the square root of three?

The physics sets the ratio but the frame sets the number. Manufacturers publish a discrete inside-delta rating for each frame, based on its thermal design and its testing, so the published inside-delta figure can sit slightly below the mathematical product. Read the inside-delta rating from the frame's own data; never assume the factor.

Keep reading

  • Selection guide

    Matching a soft starter current range to its power structure

    Match the power structure before anything else: a solid-state soft starter covers 90–520 A and an internal-bypass unit covers 108–480 A, both rated 200–690 V AC at 50/60 Hz. Size the starter so the motor's full-load current sits inside the span for the structure you actually have, then set the start modes.

    Motors and motor starters

  • Explainer

    Motor nameplate current is line current, not winding current

    The amps printed on a three-phase motor nameplate are line current: what a clamp meter reads in each supply conductor at full load in the plate's designated connection. In star, winding current equals line current; in delta, each winding carries the line current divided by 1.73 — about 14.5 A for a 25 A plate.

    Motors and motor starters

  • Explainer

    What star and delta jumper bars mean on a motor terminal box

    One jumper bar joining the three winding ends is a star connection — the supply lands on the other three terminals. Three bars, each bridging one terminal to its neighbour, are delta. At 380 V in star, each winding sees about 219 V and the leads carry the plate's 2.7 A; delta needs a 220 V-class supply and about 4.7 A at the leads.