Why connected load kW does not size a service transformer

Power distribution and transformers Published 7 min read By Current Intel engineering team

Short answer

A 100 kW connected total does not pick the transformer. NFPA 70 Article 220 (2023 edition) sets the calculated demand, in kVA, checked against the heaviest-loaded phase; an assumed 0.9 diversity factor or an 80% loading shortcut is not the method. Transformer Z% belongs to the available fault-current calculation that sets service-equipment interrupting ratings, not to demand.

On this page
  1. Connected load is not calculated demand
  2. kW must become kVA before it meets a rating
  3. A phase-to-phase load is a single-phase load
  4. Worked example: the 100 kW site on a 208Y/120 V secondary
  5. Z% belongs to the fault-current check
  6. The order to run the checks
  7. Questions asked

Connect 100 kW of heaters, lighting, motors, HVAC, battery chargers and receptacles, and the transformer question looks like division: multiply by 0.9, divide by 0.8, pick the nearest catalogue number. It is not. Under NFPA 70, the National Electrical Code (2023 edition), a customer-owned service transformer takes its rating from the Article 220 calculated demand — demand factors applied by load type to a documented load schedule — expressed in kVA and checked on the heaviest-loaded phase. An assumed diversity coefficient and a loading-percentage shortcut each answer a different question, and neither is the code method. Transformer impedance, Z%, feeds the available fault-current calculation that sets service-equipment interrupting ratings; it never adjusts demand. Below is each check in turn, then the same case worked through to a kVA rating, a main breaker and a fault-current figure.

Connected load is not calculated demand #

Article 220 of the 2023 NEC, "Branch-Circuit, Feeder, and Service Load Calculations," is the method that converts a connected-load schedule into a demand, and the diversity you are looking for already lives inside it, load type by load type. The nondwelling receptacle calculation in 220.44(A) takes the first 10 kVA at 100% and the remainder at 50%; motor loads enter through 220.50, which sends you to Article 430, where the largest motor counts at 125%. Note the direction: the code cuts some loads and raises others, so no single coefficient applied to the grand total can reproduce it.

A 0.9 multiplier is a guess with a decimal point. The 80% loading figure is not in the code either: NFPA 70 sets no 80% loading limit for a transformer, and nameplate kVA is a continuous rating at the manufacturer's stated ambient and altitude. Spare capacity is a legitimate owner decision, made after the calculation and recorded as margin, not a sizing method.

The 50 to 60% of connected load figure is a third practice again: utilities derive it from measured coincidence across their whole customer base on utility-owned units, and Article 220 does not govern those. One site cannot borrow that diversity. Confirm the adopted edition and local amendments with the authority having jurisdiction, and the demand factors with the equipment documentation; the article numbers here are from the 2023 edition.

kW must become kVA before it meets a rating #

A transformer rating is kVA; a load schedule is mostly kW, and comparing them directly is the second way this sizing goes wrong. Convert every load: kVA equals kW divided by power factor. Where a load carries a nameplate kVA — chargers, UPS units, much HVAC equipment — use it as it stands; otherwise calculate from voltage and current, or from the schedule's kW and power factor. Dividing by the power factor only ever grows the number, and the worse the site's power factor, the more transformer the same kilowatts demand, so the conversion belongs at the top of the worksheet, not after a rating is chosen.

A phase-to-phase load is a single-phase load #

The site almost certainly has no two-phase loads. Two-phase is a historical supply with two voltages displaced 90 degrees, and modern equipment does not use it. A heater, motor or charger wired between two lines of the three-phase system is a single-phase load that happens to sit at line-to-line voltage. Inventory the loads by connection — line-to-neutral, line-to-line, three-phase — because the phase-loading step depends on that classification.

A line-to-line load draws its current out of one line and returns it on another, displaced 30 degrees from the line-to-neutral currents, so the line currents add as phasors, not by arithmetic: plain addition overstates the phase loading, and ignoring the split misses it in the other direction. Work the loading on all three lines and take the heaviest one, because the transformer must carry that phase and a grand total in kW can hide a badly unbalanced panel. The line-by-line bookkeeping is worked in sizing a three-phase transformer for unbalanced 230 V loads.

If phase currents are confirmed with a clamp meter rather than from the schedule, that is energized work: NFPA 70E (2024 edition) governs the PPE and the energized-work permit for it, and neither step is optional.

Worked example: the 100 kW site on a 208Y/120 V secondary #

Inputs and where each comes from.

  • Connected load, all loads summed: 100 kW — the site's load-schedule total.
  • Overall power factor: 0.9 — an example value standing in for the schedule's actual kVA; replace it with the measured or nameplate figure.
  • Secondary voltage: 208Y/120 V — an example site voltage, needed only for the ampere steps.
  • Impedance Z%: read from the nameplate of the specific unit chosen; no catalogue typical.

The rule in words. The transformer is the first standard kVA rating at or above the Article 220 calculated demand; the main breaker follows the transformer through Table 450.3(B); the available fault current follows from Z%.

Arithmetic.

  1. Convert the connected load: 100 kW ÷ 0.9 = 111.1 kVA. For this mix of receptacles, lighting and noncoincident HVAC and heating, that is the ceiling the worksheet works down from, with the largest-motor 125% the one item pushing back up.
  2. Run the Article 220 worksheet on the real schedule. A demand at or below 112.5 kVA lands on the 112.5 kVA unit — and because the connected ceiling is 111.1 kVA, this case does. Above that rating, the next standard size is 150 kVA.
  3. Secondary full-load current of the chosen unit: 112,500 VA ÷ (1.732 × 208 V) = 112,500 ÷ 360.3 = 312 A.
  4. Main breaker, Table 450.3(B) of the 2023 edition, for a transformer rated 1000 V or less: not more than 125% of 312 A = 390 A, and where that figure falls between standard ratings, the next higher standard rating — a 400 A breaker.
  5. Available fault current at the secondary terminals: approximately 312 A × 100 ÷ Z%. The service equipment's interrupting rating must meet or exceed it under 110.9, and the figure goes into the available-fault-current field marking under 110.24.

Result. A 112.5 kVA dry-type unit with a 400 A main on the example 208Y/120 V secondary, with service equipment rated above the nameplate-Z fault current.

Decision. Buy the 112.5 kVA unit. Not 90 kW: no standard three-phase dry-type rating sits there, and the coefficient behind it has no code standing. Not 125 kVA: that number comes only from the 80% shortcut; if the owner wants the margin, record it as a margin decision. Re-run steps 2 to 5 whenever the schedule changes — the kVA, the breaker and the interrupting check move together.

Z% belongs to the fault-current check #

Impedance answers a different question than demand. Z% does not set diversity or continuous loading; it sets how much current the transformer delivers into a fault at its terminals — roughly the secondary full-load current times 100 divided by Z% — and that current, with motor contribution and conductor impedance added where the design includes them, is what the service equipment's interrupting rating must meet under 110.9 and what the field marking under 110.24 records. Keep the two checks on separate lines of the design file: demand from Article 220, interrupting rating from Z%. The arithmetic with worked figures is in calculating transformer fault current from percent impedance at the terminals; the marking duty is covered in NEC available fault current labeling requirements.

The order to run the checks #

  1. Build the load schedule: every load with its connection (line-to-neutral, line-to-line or three-phase), its kW or nameplate kVA, and its power factor.
  2. Run the Article 220 worksheet for the adopted edition; its output is the calculated demand in kVA.
  3. Assign loads to lines, combine the line currents as phasors, and identify the heaviest-loaded phase.
  4. Choose the first standard kVA rating at or above the demand, then set the secondary main breaker from Table 450.3(B), with the next standard rating permitted where the limit falls between sizes.
  5. Read Z% from the selected unit's nameplate, compute the available fault current, confirm every service device's interrupting rating against it, and apply the field marking.
  6. Hand the package — schedule, worksheet, phase loading, kVA choice, breaker, fault current — to the qualified person who stamps the design.

The diversity coefficient and the loading percentage appear nowhere in that order, and impedance appears exactly once, in the check where it belongs.

Questions asked

Can I use the 50 to 60 percent figure the utilities apply?

Ownership decides the method, not geography. Where the utility owns and sizes the transformer, its planning practice stands and Article 220 does not apply. The moment the site owns the dry-type unit behind the service point, the NEC demand calculation governs, because a single site cannot demonstrate the customer-to-customer coincidence the utility figure is built on.

What if the calculated demand falls between two standard ratings?

Take the higher rating, always. A continuous load is never rounded down to reach a catalogue number, and the gap you gain is real spare capacity, effectively the margin the 80% shortcut was reaching for, except it falls out of the standard ratings instead of an invented rule. Record the chosen rating and the demand it serves in the design file.

Why do line-to-line and line-to-neutral currents add as phasors?

Because they do not share a time axis. A line-to-neutral load's current lines up with its phase-to-neutral voltage, while a line-to-line load's current lines up with the voltage between two lines, which sits 30 degrees away. On a shared conductor the two partially oppose, so plain arithmetic addition overstates the loading. Draw the phasor diagram or let the calculation software combine them.

Where does the Z% value come from?

From the nameplate or datasheet of the specific transformer purchased, after the kVA is chosen. Impedance varies with the rating and the design, so a catalogue typical is not a design value. Carry the nameplate figure into the fault-current calculation, and file it together with the resulting fault current and the interrupting ratings selected against it.

Keep reading

  • Explainer

    Sizing a neutral grounding transformer on a 22 kV feeder

    A wye-delta bank that creates a neutral on a 3-wire 22 kV feeder is sized by the duty that neutral carries. A continuous 10 A single-phase load puts 127 kVA on one primary winding, so the three-phase nameplate lands near 381 kVA — take the next common rating, 500 kVA. A grounding-only neutral is sized from phase-to-ground voltage × fault current × a duration factor K.

    Power distribution and transformers

  • Selection guide

    Is a 6 kVA transformer enough for a 5 hp motor drive

    A 6 kVA three-phase transformer supplies 7.5 A per line at 460 V and 15.1 A at 230 V. A 5 hp rating is 3.73 kW of shaft output, not input kVA. Measure the machine's simultaneous input current at its heaviest cut: if it stays under the transformer's nameplate current, the 6 kVA unit is enough; if it crosses, order the next standard size.

    Power distribution and transformers

  • Selection guide

    Sizing a three-pole breaker for a single-phase transformer

    Use the real primary current, 10 kVA x 1000 / 480 V = 20.83 A, not the 36.1 A a phantom balanced 30 kVA three-phase load gives. NFPA 70, 2023 edition, Table 450.3(B) permits 125% plus the next standard rating, so a 30 A two-pole breaker is the pick. A three-pole breaker of the same rating works only where its listing allows two-pole use, or with two poles in series on a differential-trip device.

    Protection: breakers, fuses and SCCR