Current IntelPower LibraryShop main store

Explainer

Why DC motor reversing relay contacts weld at 110 V

Motors and motor starters Published 10 min read

Short answer

The contacts weld because a 110 V DC arc never crosses zero, so a general-purpose relay's AC ampere rating does not carry to DC motor duty. Select DC-rated reversing contactors with magnetic blowout and arc chutes on their make and break ratings at 110 V DC, interlocked and delayed between directions.

On this page
  1. Why do reversing relay contacts weld on a DC winch?
  2. Why doesn't an AC or general-purpose relay rating transfer to DC?
  3. How much current do the contacts make and break in a winch cycle?
  4. What does the 7 A breaker tell you about the switching duty?
  5. Does an RC snubber stop DC contact welding?
  6. Are 50 A solid-state relays the right answer for a DC winch reverser?
  7. What contactor survives the DC reversing duty?
  8. How should the reversing controls be interlocked and timed?
  9. Questions asked

The contacts weld because the switched circuit is DC: the arc never sees a current zero, so an AC or general-purpose relay rating does not transfer to DC motor duty at this bus voltage, and the make, braking and plugging currents run far past the breaker's running-load rating. A bigger general-purpose relay or an RC snubber will not fix it. The fix is a pair of DC-rated reversing contactors with magnetic blowout coils and arc chutes, selected on their make and break ratings at the bus voltage for inductive motor duty, mechanically and electrically interlocked, with a reversal delay so the contacts never break plugging current. Solid-state relays remain the fallback where a DC contactor with a 12 V coil cannot be sourced.

Why do reversing relay contacts weld on a DC winch? #

The contacts weld because the arc never sees a current zero: at 110 V DC the arc burns until the gap or an arc chute stretches it out, and a general-purpose relay offers neither, so the molten bridge solidifies as a weld.

An AC circuit passes through zero current twice per cycle — 120 times a second at 60 Hz — so an opening arc dies at the next crossing without help. A DC arc has no crossing: it burns until the lengthening gap raises the arc voltage above the supply, or until a magnetic blowout coil and arc chute stretch and cool it. A general-purpose relay has a short gap and no blowout, so at this voltage neither rescue arrives in time; the arc melts the contact faces and the molten metal solidifies as a weld on the next closure. Contact bounce makes it worse because every re-strike closes onto a fresh arc — the same family of trouble as fixing AC contactor chatter on a loaded 80 HP motor start. The molten-bridge mechanism also explains why a contactor contact melts on high-speed transfer, but on DC there is no zero crossing to interrupt the burn, so the damage lands within a handful of operations rather than after years.

Why doesn't an AC or general-purpose relay rating transfer to DC? #

It doesn't because DC ratings are tabulated separately: an AC motor contactor family rated 22 A make and break at 600 V AC may be listed for only about 0.1 A make and break at the bus voltage, and a general-purpose relay's 20 A is an AC resistive figure.

The AC ampere and horsepower lines assume the current's own zero crossings do the arc breaking. On DC the manufacturer has to guarantee that its own arc management forces the current down, so the DC figures live in a separate table, arranged by voltage and by duty — resistive, motor, inductive. Read that table at the bus voltage and in the inductive motor column, and ignore the AC horsepower lines entirely; in the example above, the DC make and break figure sits more than two orders of magnitude below the AC one at a comparable frame size. The same caution applies to a small relay's printed DC rating, which is often given only for resistive loads at 30 V DC or less: a low-voltage resistive figure says nothing about breaking an inductive motor current at the bus voltage. For the contactor series you are considering, go to the manufacturer's specification section for DC motor loads rather than the front-page AC rating.

How much current do the contacts make and break in a winch cycle? #

Not the nameplate amperes: in the worked example in this section the contacts close onto about 44 A at standstill, break about 37 A of braking current at neutral and can face about 81 A of plugging current on an instant reversal.

Only the first of the three events below resembles the running current you would guess from the breaker. At standstill the armature generates no back-EMF, so winding and lead resistance alone limit the current; the field's inductance slows the flux build, which is why a shunt motor's first instant is governed almost entirely by armature resistance, and the closing contact can bounce while carrying all of it.

If the opposite direction is pressed before the motor stops, the armature is still generating EMF against the new supply polarity, and plugging current is (V + E) ÷ R — the EMF adds to the supply — approaching twice the start current.

In neutral this winch shorts the motor terminals and the coasting machine brakes itself through that short. Releasing the control opens the shorting contact, so it is the shorting contact, not the supply contact, that breaks the braking current. Hoist operators then pulse the pendant to place the load, so start and brake events repeat faster than the faces can cool.

Event in the winch cycle Current the contact sees Example value Why it punishes the contact
Close onto a stopped motor V ÷ R 44 A no back-EMF to limit it; bounce re-strikes onto the full current
Release to neutral at speed E ÷ R through the short 37 A the shorting contact opens under braking current
Reverse before the motor stops (V + E) ÷ R 81 A armature EMF adds to the supply in plugging

Worked example, with illustrative inputs: supply 110 V DC. The ohmmeter reads R = 2.5 Ω around the armature circuit — for a series motor this loop includes the field winding — and the motor runs at load near the breaker's 7 A rating. Back-EMF at that load: E = V − (I × R) = 110 V − 17.5 V = 92.5 V. Start current: I = V ÷ R = 110 V ÷ 2.5 Ω = 44 A. Plugging on an instant reversal: I = (V + E) ÷ R = 202.5 V ÷ 2.5 Ω = 81 A. Braking at release: I = E ÷ R = 92.5 V ÷ 2.5 Ω = 37 A. Treat the results as estimates: resistance shifts with brush contact and temperature, and EMF shifts with speed, so recheck against the nameplate and your own measurements.

Before the meter comes out, de-energize the winch, lock it out and verify absence of voltage at the terminals — establishing the electrically safe work condition that NFPA 70E, 2024 edition, requires before work on equipment that could otherwise be energized — and confirm the steps in your site's electrical safety program.

What does the 7 A breaker tell you about the switching duty? #

Very little about contact duty: at the supply voltage the 7 A breaker corresponds to about 770 W of running input, so the motor is in the few-hundred-watt to one-kilowatt class, and the breaker tolerates start and plugging surges that will still weld a small relay's contacts.

P = V × I gives that input: 110 V × 7 A = 770 W, a small machine by motor standards and still well past what a relay face clears on DC. The breaker is thermal and magnetic protection sized to the running load, and it is built to ride through the surges tabulated above — precisely the currents that weld relay contacts. Changing a protective setting does not change what the contacts must make and break, the same lesson as why raising a magnetic overload setting won't fix a hard start. It is also why larger DC machines start through staged resistance or a power-electronic drive instead of a bare contact pair closing onto full voltage; at this size, a DC motor-duty contactor pair is the proportionate equipment.

Does an RC snubber stop DC contact welding? #

No: an RC network across the contacts limits the voltage rise as they part and tames the inductive kick, but it does nothing to the make current into a stationary armature or the plugging current on reversal, which are the currents that weld the contacts.

A suppression network has a real job — clamping the opening transient so it stays off the contact gap and the wiring insulation — but it cannot shrink the amperes the contacts must make and break, and the welding on this winch happens at make into a stopped armature and at the break of braking and plugging current. If a network is ever needed for a separate reason, take its values from the relay or contactor manufacturer's application data for DC motor loads at your voltage; there is no calculation that turns an RC pair into a DC motor-duty make and break rating. Spend the effort on the contactor selection instead.

Are 50 A solid-state relays the right answer for a DC winch reverser? #

They work electrically but are not the fail-safe choice on a hoist: an SSR output typically fails shorted, so a fault can leave a direction energized, and the pair still needs an interlock; they remain the fallback where a DC contactor with a 12 V coil cannot be sourced.

A genuinely DC-rated output — MOSFET or IGBT, not the thyristor output used for AC loads, which cannot commutate off a steady DC current — has no arc at all, which is why a 50 A pair holds up where the 20 A general-purpose relays welded. Two cautions remain. A semiconductor output usually fails shorted, and on a hoist that leaves one direction energized with no outward sign, so a mechanically applied brake and a separate power-removing contactor belong in the circuit either way; and two conducting outputs in parallel across the supply are a bolted short, so the interlock of the next section stays mandatory. Keep a working solid-state pair behind brake and contactor; for a new design, prefer the DC contactor pair and hold solid-state as the fallback.

What contactor survives the DC reversing duty? #

A pair of DC-rated reversing contactors with magnetic blowout coils and arc chutes, selected on their make and break ratings at the bus voltage for inductive motor duty — not on AC horsepower or ampere figures — is the equipment built for this job.

A DC contactor earns the rating with hardware a relay lacks: a blowout coil in series with the load throws the arc magnetically off the contact faces and into an arc chute, where splitter plates stretch it, cool it and drive its voltage up until the current is forced down through zero. That is how DC is made to behave like AC at the gap. Some blowout designs are polarity-sensitive, so land the load cables on the marked polarity.

Selection then reads the DC columns: the rated operational voltage must cover the bus voltage, and the make and break figures must be taken for inductive motor duty at that voltage. IEC 60947-4-1, the standard covering low-voltage contactors and motor starters, defines the DC utilization categories — DC-3 for shunt-motor plugging and inching, DC-5 for series-motor plugging and inching — so a DC-5 make and break rating at the bus voltage is the figure to hold against the plugging current tabulated earlier. Confirm the categories and figures in the manufacturer's datasheet for the exact series, because the tables change with frame size and edition.

Then hand the supplier the numbers and let them select the frame: supply voltage, motor type, nameplate running current, the measured armature-circuit resistance, the start, braking and plugging currents from the example, and the operations per hour the pendant duty implies. A maker with a DC motor ratings page will return a frame, a utilization category and an endurance figure you can hold the selection to.

How should the reversing controls be interlocked and timed? #

Mechanically or electrically interlock the two contactors so neither can close while the other is closed, and add a reversal delay set to the time the loaded motor takes to stop, so the contacts never break plugging current.

Wire normally closed auxiliary contacts from each contactor into the other's coil circuit and insist on a mechanical interlink as well, so a stuck contact cannot let both directions close — the same two-contactor pattern that reversing a three-phase motor needs two contactors. Add the reversal delay between a stop and the opposite direction, set to the coasting-and-braking time you actually observe under load; that delay is what keeps the contacts off plugging current. An anti-bump interval between commands caps operations per minute so face heating stays inside the endurance the manufacturer published. One optional change trades braking away: diodes in the switch return legs remove the shorted-terminal braking current, but an overhauling load then has no electrical hold, a mechanical brake becomes mandatory and the pendant loses its precise stops — keep the shorted-terminal braking when positioning accuracy matters.

Questions asked

Does full-wave rectified 110 V DC behave any better at the contacts than battery DC?

Effectively no. The rectifier's output touches zero twice per mains cycle, but the motor's armature and field inductance carry the current through those notches, so the contacts still part a continuous DC current with no natural zero to extinguish the arc. Smoothing capacitors make it worse, because stored charge can keep feeding the arc after the contacts separate. Treat rectified and battery supplies the same way when you read DC ratings.

Can the 12 V pendant signal drive the contactor coils directly?

Order the contactor coils to match the control voltage you actually have. DC contactor ranges include coil versions for common control voltages, so a 12 V pendant signal can pick up the contactor directly if you specify that coil. If the frame you need is only offered with a higher-voltage coil, drive it through a small interposing relay whose contacts carry the coil current, and check the coil's pickup and dropout voltages against the supply before you commit.

What makes a solid-state relay risky on a hoist?

A semiconductor output most often fails shorted, so a faulted unit can leave one direction energized with no outward sign. On lifting equipment that means the load can keep moving after a control fault. Pair any solid-state reverser with a mechanically applied brake and a separate contactor that removes armature power, and exercise the failure behavior during commissioning instead of assuming the relay opens when it should.

How do you reverse a series-wound DC motor without losing direction control?

Reverse the armature relative to the field: swap the two armature leads, or swap the two field leads, but never both, because reversing both leaves the direction of rotation unchanged. Keep the series field circuit unbroken while running; an open series field at speed can let the motor overspeed or pull a damaging current without warning. The interlocked contactor pair performs the swap between its two closed positions.

How long should DC-rated contacts last in this service?

Electrical endurance is published as a number of operations at a stated utilization category and current, and the figure at plugging duty is much shorter than the figure at running current. Ask the manufacturer for the endurance curve at your computed start, braking and plugging currents and your operations per hour; that curve, not the frame's ampere figure, is what tells you the interval between contact renewals.

Keep reading

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters

  • How-to

    Wiring overload relay contacts to the coil and the PLC

    The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters