Power distribution and transformers Published 4 min read By Current Intel engineering team

Short answer

The (continuous x 1.0 + intermittent x 0.3 + standby x 0.1) x 1.2 formula is a project convention with no IEC or IEEE basis. Size the transformer on the highest credible coincident kVA the control sequence allows, count a standby pump fully where it can run with or overlap the duty pump, and check the motor-start voltage dip separately.

On this page
  1. Where the 1.0 / 0.3 / 0.1 weighting comes from
  2. Counting a redundant standby pump
  3. Intermittent loads and diversity
  4. Worked example
  5. The motor-start check the 1.2 factor cannot cover
  6. The decision
  7. Questions asked

The formula (continuous load x 1.0 + intermittent load x 0.3 + standby load x 0.1) x 1.2, seen in many project specifications, is a weighted demand estimate. The 0.3 and 0.1 multipliers and the 1.2 margin are project conventions, not IEC or IEEE rules. IEC 60076 defines transformer ratings, tests and insulation levels; IEEE C57.91 is a loading guide that covers how loading accelerates insulation aging in mineral-oil-immersed units. Neither publishes demand factors. The defensible method is to size on the highest credible coincident kVA the control sequence allows, then check the worst motor start separately.

Where the 1.0 / 0.3 / 0.1 weighting comes from #

The weighting assumes intermittent loads draw about 30% and standby loads about 10% of their ratings on average. That can be true for a facility where those loads rarely run, and badly wrong where they run together. Before applying any weighted sum, make every input the same quantity: transformer capacity is in kVA, so convert kW load values with their power factors (kVA = kW / PF) and note whether each figure is running demand, nameplate rating or starting demand. Mixing nameplate kW with kVA, or running current with starting current, invalidates the total.

Counting a redundant standby pump #

"Standby" describes an operating arrangement, not a fixed percentage of demand. The decision follows the control sequence:

  • Duty and standby pump mutually exclusive, with the failed unit disconnected before transfer: count one pump at its full running kVA, plus the other coincident loads. A 0.1 weight on the spare is then acceptable only as bookkeeping; it is not a demand.
  • Changeover overlaps both units for a few seconds: the overlap case belongs in the starting check, not the steady-state total.
  • Sequence permits parallel operation (lead/lag, high-demand mode): count both pumps fully. A 0.1 factor here under-sizes the transformer.

For unlike units, total the actual kVA of the combinations the control logic allows. The governing case is the highest credible coincident demand, not the equipment label.

Intermittent loads and diversity #

A diversity factor is defensible only when it reflects the process sequence or measured demand. Build the load list around operating modes: which loads run together, which are mutually exclusive, which may start while others run. If two intermittent loads can run concurrently with the full continuous load, that case, not two separate 0.3 multipliers, sets the running kVA.

Worked example #

Hypothetical load list, 400 V three-phase secondary, all values running demand:

  • Continuous: 180 kW at PF 0.90, so 180 / 0.90 = 200 kVA
  • Intermittent conveyor: 45 kW at PF 0.85, so 45 / 0.85 = 53 kVA
  • Two 75 kW pumps at PF 0.88, so 75 / 0.88 = 85 kVA each, one duty and one standby, parallel operation permitted

The weighted formula gives (200 + 0.3 x 53 + 0.1 x 85) x 1.2 = (200 + 15.9 + 8.5) x 1.2 = 224 x 1.2 = 269 kVA. The coincident method with parallel pumping and the conveyor running gives 200 + 53 + 85 + 85 = 423 kVA. The convention under-sizes the transformer by roughly 37%. If the sequence forbids parallel pumping, the total drops to 200 + 53 + 85 = 338 kVA; the next standard rating above that is the selection, with margin chosen for future load, not by a blanket multiplier. Estimate only; confirm against the governing code and the equipment documentation.

The motor-start check the 1.2 factor cannot cover #

A transformer that carries the running load can still dip the bus unacceptably when a large motor starts, because starting current is several times running current and the value is motor-specific. Take the locked-rotor current from the motor data, the transformer impedance from its nameplate, and the upstream source strength, then compute the dip with the fixed-current method described in fixed-current vs motor-impedance motor starting dip. The method that separates the two cases for sequential starts is in sizing a 22/6.6 kV transformer for sequential motor starts. If the dip exceeds the tolerance of the other connected equipment, change the starting method (drive, soft starter, staged starts) or strengthen the supply rather than adding margin to the running kVA. Note that a larger transformer is not always the fix when the source is a generator, as covered in why a bigger transformer trips a generator on DOL start.

The decision #

  • Running size: the highest credible coincident kVA combination, standby units counted fully wherever the sequence can run or overlap them.
  • Intermittent loads: diversity only from documented sequence or measured data, never a universal 0.3.
  • The 1.2 factor: drop it; state margin explicitly against a named future load instead.
  • Starting: a separate voltage-dip calculation with motor-specific locked-rotor data, compared with equipment voltage limits.

Before any check that opens a panel or terminal box on a live transformer secondary, de-energize, lock out and verify absence of voltage. Confirm the governing installation requirements, such as NFPA 70, the National Electrical Code, 2023 edition, or IEC 60076 as applicable, with the local authority having jurisdiction and the equipment documentation.

Questions asked

Does IEC 60076 or IEEE C57.91 give demand factors for transformer sizing?

No. IEC 60076 defines ratings, tests and insulation levels; IEEE C57.91 is a loading guide for mineral-oil-immersed transformers, covering how loading affects insulation aging and loss of life. Neither publishes a 0.3 or 0.1 weighting. Those numbers come from project specifications and must be justified by the facility's operating sequence or measured demand.

What demand factor should I use for intermittent loads if I have no measured data?

Build the load list around operating modes instead of guessing a factor: group the loads that can run together, mark mutually exclusive ones, and total the highest combination in kVA. Where a reduced factor is still wanted, derive it from duty cycle: a 40 kW load running 15 minutes in each hour supports roughly 0.25 on average, but the start case and overlap with other loads still governs the transformer size.

Can the 1.2 factor replace the motor-start voltage dip check?

No. A 20% margin on running kVA says nothing about a starting event, where a pump may draw several times its running current. The dip depends on motor locked-rotor current, transformer impedance and source strength, so it needs its own calculation against the voltage tolerance of the other connected equipment.

Keep reading

  • Selection guide

    Sizing a transformer for a 200 HP across-the-line motor start

    Select a 1000 kVA transformer with nameplate impedance of 6.5% or less. The 3 kVA-per-HP rule gives 600 kVA for the 200 HP pump alone; adding 390.9 kVA of always-on load gives 990.9 kVA, so that is the screening size. The dip screen confirms it: 8.8% sag at 5.75% impedance, inside the 10% target, while 750 kVA would need 4.9% impedance to pass.

    Power distribution and transformers

  • Selection guide

    Sizing a 22/6.6 kV transformer for sequential motor starts

    The 3,500 kW recycle-air compressor's 1,737 A start is about 19.9 MVA, which dips a 7% transformer's secondary roughly 9.3% at 15 MVA, 8.2% at 17 MVA and 7.0% at 20 MVA. With the two running air compressors and the IEC 60076 impedance tolerance counted, only the 20 MVA rating stays inside a 10% ceiling, so that is the unit to specify.

    Power distribution and transformers

  • Selection guide

    Is a 6 kVA transformer enough for a 5 hp motor drive

    A 6 kVA three-phase transformer supplies 7.5 A per line at 460 V and 15.1 A at 230 V. A 5 hp rating is 3.73 kW of shaft output, not input kVA. Measure the machine's simultaneous input current at its heaviest cut: if it stays under the transformer's nameplate current, the 6 kVA unit is enough; if it crosses, order the next standard size.

    Power distribution and transformers