Selection guide
Current transformer burden in VA and ohms for metering CTs
Short answer
A 10 VA, 500/5 metering CT is rated for a total loop burden of 0.4 Ω; a 1.2 Ω loop draws 30 VA at rated current, three times the rating, tripling the secondary voltage and pushing the core toward saturation. Cut lead ohms and terminal resistance first, move the circuit to a 1 A secondary where possible, or raise the CT's VA class.

On this page
- How much burden can a 10 VA, 500/5 metering CT carry?
- What happens to a metering CT when the burden exceeds its rating?
- Which core do I need, metering or protection?
- Where do the extra ohms in a CT secondary loop come from?
- How do I calculate the knee-point voltage a relay needs?
- Which fix comes first for an over-burdened metering CT?
- How do I verify the circuit after the fix?
- Questions asked
Size a metering or protection current transformer by its burden budget: the VA on the nameplate divided by the square of the rated secondary current. For the 10 VA, 500/5 transformer in question that budget is 0.4 Ω, and the 1.2 Ω loop you measured loads it to 30 VA at rated current — three times the rating. The core then runs at three times its designed flux, ratio and phase errors grow, and a metering core clips first on fault multiples. The fix order is fixed: cut lead ohms and terminal resistance, move the circuit to a 1 A secondary where the meter supports it, or raise the transformer's VA or knee-point rating. The sections below run the numbers, separate metering from protection cores, and end with the decision for each case.
How much burden can a 10 VA, 500/5 metering CT carry? #
A 10 VA CT with a 5 A secondary is rated for a total external burden of 10 VA divided by 5 A squared, which is 0.4 Ω; your measured 1.2 Ω loop loads it to 30 VA, three times the nameplate.
A current transformer is a current source: it drives its rated secondary current through whatever impedance the loop presents, so every extra ohm raises the secondary voltage the core must support. The burden budget is the nameplate VA divided by the square of the rated secondary current, and it covers everything external to the transformer: the meter input, both lead conductors and the terminal contacts. The winding resistance sits outside this budget and re-enters only in the knee-point calculation.
Worked example, the arithmetic behind the answer:
Rated burden: 10 VA ÷ (5 A × 5 A) = 10 ÷ 25 = 0.4 Ω
Voltage at rated current: 5 A × 0.4 Ω = 2 V
Measured loop, 1.2 Ω: (5 A × 5 A) × 1.2 Ω = 30 VA
Headroom check: 30 VA ÷ 10 VA = 3× the rating
Voltage on the real loop: 5 A × 1.2 Ω = 6 V, three times the designed 2 V
Because VA burden scales with the square of the secondary current, the same loop ohms cost far less on a 1 A secondary — that is the structural fix in the fix-order section below. Decision: a loop at or under the nameplate budget keeps the transformer in play; anything above it moves you to the next section.
What happens to a metering CT when the burden exceeds its rating? #
Three times the rated burden forces three times the secondary voltage at rated current — 6 V instead of the designed 2 V on this transformer — which triples the core flux, pushes a metering core toward saturation, and makes ratio and phase errors grow.
Flux follows the secondary voltage the CT must develop, so three times the voltage means three times the flux swing at rated current. Past the bend of the excitation curve the excitation current climbs steeply, and excitation current is precisely the part of the primary ampere-turns that never reaches the meter. The failure sequence runs in order: ratio error and phase displacement grow until the accuracy class no longer holds; on fault or motor-start multiples the waveform flat-tops and a true-RMS instrument reads low; and because a metering core is deliberately built to saturate early, its instrument security factor clips the overcurrent first.
The transformer itself is not damaged by an over-burdened loop — the circuit is closed, so no voltage can build. The damage case is the mirror image: a secondary opened while the primary carries current. What flat-topping looks like on an installed unit, and how little current survives it, is covered in why CT saturation at the knee point cuts secondary current.
Light burden is not the mirror problem it appears to be. A protection core shrugs off a load below rating. A metering core is only guaranteed in class across the burden range printed on its datasheet, and strongly under-loaded metering cores drift out of class too — the CT secondary burden sizing for metering underload page works that case.
Which core do I need, metering or protection? #
Read the nameplate accuracy class: a metering core, class 0.2 or 0.5 with an instrument security factor, is built for accuracy at load and saturates early on fault multiples; a protection core, 5P20 or 10P20 with an accuracy limit factor, stays linear to twenty times rated current.
The designation spells the split out. A metering class such as class 0.5 promises ratio error within half a percent, with a matching phase-angle limit, across the working load range, plus the security factor that caps what the core delivers during a fault. A protection designation such as 5P20 promises the composite error stays within 5% up to 20 times rated current at the rated burden; 10P20 relaxes the error to 10% at the same 20-fold limit. Class-X and PX cores are specified by knee-point voltage and winding resistance instead, and the knee-point section below works those numbers.
Cross-fit the two and each fails at the other's job. A metering core feeding a protective relay saturates during exactly the fault the relay exists to see, so the relay under-reads or trips late. A protection core feeding a revenue or energy meter misses its class at normal load, because it is built for linearity at multiples of rated current rather than accuracy at load. Split the duties: two cores on one transformer, or two separate transformers.
Decision: a meter takes a metering core, budgeted by the first section; a relay takes a protection core sized by the knee-point calculation below; a panel that does both takes separate cores. Where a retrofit cannot shut the bus down, the physical choice between window and clamp-on parts is covered in split-core current transformer selection for power meters.
Where do the extra ohms in a CT secondary loop come from? #
The measured ohms in a CT circuit are the meter input burden, both lead conductors and terminal contacts, plus the winding resistance for knee-point math; on long runs the leads dominate, and every lead ohm costs VA at the square of the secondary current.
One safety line before any hands-on work: close the shorting block, de-energize the circuit and verify absence of voltage before you open the panel or break the loop. A CT secondary opened while the primary carries current can drive a hazardous voltage and overheat the core.
Measure the loop end to end with the transformer disconnected, then attribute the ohms part by part:
| Loop part | Where the value comes from | Symptom of a wrong value |
|---|---|---|
| Rated secondary, 1 A or 5 A | Transformer nameplate | Burden converted with the wrong current squared |
| Meter or relay input burden | Device datasheet, in VA or ohms | Taken in VA at the wrong rated current |
| Lead conductors, both ways | Two times length times conductor ohms per metre | One conductor counted, so the burden reads half its true value |
| Terminals and shorting blocks | Measured on the assembled loop | Loose or oxidized contacts add ohms that drift with temperature and vibration |
| Winding resistance | Transformer test sheet or a DC measurement | Left out of the knee-point requirement, which then comes out undersized |
Lead resistance dominates on real runs. Copper at 2.5 mm² runs about 0.007 Ω per metre per conductor, so a route with 50 m of path each way is 2 × 50 × 0.007 = 0.7 Ω — more than the whole nameplate budget of the transformer in the worked example, before the meter input is added. Moving to 6 mm² cuts the same route to about 0.3 Ω; shortening the route helps just as much.
Decision: if the measured total sits far above the datasheet figure and the secondary still tracks the primary linearly, you have a cable or terminal fault, not a wrong transformer — fix the copper and re-measure. If the total really is that high and the readings clip or bend, the transformer is undersized for its loop and the fix order below decides it.
How do I calculate the knee-point voltage a relay needs? #
Size the knee-point voltage from the fault the relay must see: multiply the secondary fault current by the sum of winding resistance and loop resistance, times the factor the relay manual specifies; the worked example below lands at 150 V for a 10 kA primary fault.
The knee-point voltage comes off the excitation curve, secondary voltage plotted against excitation current; under the IEC definition it is the point where a 10% rise in voltage forces a 50% rise in excitation current. ANSI-style curves mark the knee differently, so confirm which definition the relay manual applies before comparing numbers.
For a duty sold by accuracy limit factor, the equivalent voltage requirement is the limit factor times the rated secondary voltage across winding plus burden: a 5P20 core must develop 20 times the rated secondary current through its own winding resistance plus the rated burden. For a relay duty sized to the fault, the requirement takes the measured loop:
Vk ≥ K × Isec_fault × (Rct + Rloop)
N = 500 ÷ 5 = 100 (ratio)
Isec_fault = 10,000 A ÷ 100 = 100 A (10 kA primary fault)
Rct = 0.3 Ω (illustrative, from the transformer test sheet)
Rloop = 1.2 Ω (the measured loop)
K = 1 (illustrative minimum; the relay manual sets it, higher with DC offset)
Vk ≥ 1 × 100 A × (0.3 Ω + 1.2 Ω) = 150 V
Same fault with the loop halved: 100 A × (0.3 Ω + 0.6 Ω) = 90 V
K scales with the DC offset the system X/R ratio can drive through the core, so read it from the relay manual rather than assuming the example's minimum; the 150 V result is a design estimate built from the transformer test sheet and the relay manual, and the class or scheme requirement behind it is confirmed with the equipment documentation and, where a code question is in play, the authority having jurisdiction. For K-class wound CTs, IEEE C57.15 requires a knee-point voltage of at least 70% of the secondary terminal voltage rating — a floor to check the nameplate against.
A metering core that saturates at a few volts cannot support that demand, which is why the duties stay on separate cores. To read the knee on an installed unit, take the transformer out of circuit, inject a rising AC voltage into the secondary with the primary open, record voltage against current, and mark the knee on the plot.
Which fix comes first for an over-burdened metering CT? #
Work the fixes in cost order: cut lead ohms with larger or shorter conductors, clean and re-torque terminals and shorting blocks, move the circuit to a 1 A secondary, which cuts the VA cost of the same ohms twenty-five-fold, then raise the transformer's VA or knee-point rating.
| Fix | What it changes | Effect on this loop | Watch for |
|---|---|---|---|
| Larger or shorter leads | Cuts conductor ohms per metre or run length | The 50 m route falls from about 0.7 Ω on 2.5 mm² to about 0.3 Ω on 6 mm² | Count both conductors every time |
| Clean and re-torque terminals | Removes contact resistance | Recovers tenths of an ohm on aged blocks | Re-measure the loop afterwards |
| Move to a 1 A secondary | VA cost falls with the square of the current | The same loop ohms cost 1.2 VA instead of 30 VA — 25 times less | Meter and relay inputs must be ordered to match |
| Raise the transformer rating | Raises the VA budget or the knee-point voltage | Pick the next class above the loop's measured demand, with margin | Panel space in the switchgear |
| Split the duties | Two cores, two separate budgets | Each core sees only its own burden | Terminal and panel space for the second core |
The first two lines cost an hour and a torque wrench, the third is a design change that pays back on every long run after it, and the last two are purchases. Where the 1 A route is taken, meter and relay inputs must follow the secondary — a mismatched input reads wrong by the ratio of the two ratings, as why a 1 A relay input on 5 A CTs reads five times the current explains.
Decision: bring the loop under the nameplate budget with copper and contacts where you can; make the 1 A move when the run is long and fixed; buy the higher VA class or the protection-grade knee-point when neither is available.
How do I verify the circuit after the fix? #
Three checks close the job: measured loop resistance inside the datasheet's burden range, secondary current tracking primary current divided by the ratio in a straight line across several load points, and — for a protection core — a knee-point voltage above the knee-point section's figure.
Run them in this order:
- Close the shorting block, de-energize the circuit and verify absence of voltage at the terminals before anything is opened.
- With the transformer disconnected from the loop, measure the resistance end to end with a low-resistance ohmmeter and multiply by the square of the rated secondary current; the product must sit inside the burden range printed on the datasheet.
- Reconnect, restore the circuit, then clamp the secondary at several load points: each reading must equal the primary current divided by 100 for this ratio, and the points must fall on a straight line.
- For a protection core, file the excitation curve and check its knee-point voltage against the requirement from the knee-point section.
Decision, case by case. Loop inside the budget and linearity proven: keep the transformer and close the job. Loop inside the budget but the readings still wander: the burden is cleared, so suspect the ratio or the meter rather than the copper. Loop above the budget after the fixes: the 5 A transformer is the wrong part for this loop — take the 1 A secondary or buy the next VA class up, then repeat the checks above.
Questions asked
Can I run with the CT secondary shorted while I wait to replace the meter?
Yes, briefly and deliberately. A closed shorting block gives the secondary a near-zero ohm path, so the transformer delivers its current into the short with no voltage build-up and no damage; the meter simply reads zero for the duration. This is the standard way to remove a meter under load. Use the transformer's own shorting block or a rated shorting terminal, confirm it is fully closed before disconnecting anything, and tag the circuit so nobody reopens a live secondary.
What does the instrument security factor on a metering CT nameplate tell me?
It is the multiple of rated current at which the metering core is designed to saturate, printed as FS5, FS10 or FS20 on IEC-style nameplates. An FS5 core saturates near five times rated current, so a downstream fault cannot drive a destructive current or voltage into the meter; lower numbers protect the meter harder. Check that the available fault current in your study sits above that multiple times rated current — then the meter is being protected as the nameplate intends.
Why does my power meter read low only during motor starts?
Motor starting current runs at several times rated load, exactly the region where an over-burdened metering core leaves its linear range. At normal load the circuit can still hold its class, so daytime readings look right and the error appears only when large motors start, as clipped peaks drag the true-RMS reading down. Measure the loop resistance and compare it with the nameplate burden; if the loop is the cause, work the fixes in cost order rather than replacing the meter.
How much lead resistance can a given CT tolerate on a long run?
Subtract the fixed parts from the nameplate budget: allowable lead loop equals the rated burden in ohms, minus the meter input burden, minus the winding resistance from the test sheet. For a 10 VA, 5 A transformer that budget is 0.4 Ω; if the meter input equals 0.05 Ω and the test sheet lists 0.1 Ω, the two-conductor lead run may add up to 0.25 Ω. Pick a conductor whose ohms per metre fit that figure over the round-trip length.